2009-01-12 16:57:34 | 2004 FBC W/2007 REVISION |
| ADDITION |
| |
| DENIED BY BUILDING |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| BE REQUIRED. FS 713 |
| |
| 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| ENERGY CALCULATION FORM. FBC 13-6. |
| |
| 4) THE MINIMUM WALL INSULATION IS R-5 PER ENERGY CALC. |
| FORM. REVISE WALL SECTION. FBC 13-602.1.C.1.2 |
| |
| 5) SHOW COMPLIANCE WITH R311.4.3 LANDINGS AT DOORS. |
| THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF EACH |
| EXTERIOR DOOR. |
| EXCEPTION: WHERE A STAIRWAY OF TWO OR FEWER RISERS IS |
| LOCATED ON THE EXTERIOR SIDE OF A DOOR, OTHER THAN THE |
| REQUIRED EXIT DOOR, A LANDING IS NOT REQUIRED FOR THE |
| EXTERIOR SIDE OF THE DOOR. |
| THE FLOOR OR LANDING AT EXTERIOR DOORS REQUIRED BY |
| SECTION R311.4.1 SHALL NOT BE REQUIRED TO COMPLY WITH |
| THIS REQUIREMENT BUT SHALL HAVE A RISE NO GREATER THAN |
| THAT PERMITTED IN SECTION R311.5.3. |
| EXCEPTION: THE LANDING AT AN EXTERIOR DOORWAY SHALL NOT |
| BE MORE THAN 7? INCHES (196 MM) BELOW THE TOP OF THE |
| THRESHOLD, PROVIDED THE DOOR, OTHER THAN AN EXTERIOR |
| STORM OR SCREEN DOOR DOES NOT SWING OVER THE LANDING. |
| THE WIDTH OF EACH LANDING SHALL NOT BE LESS THAN THE |
| DOOR SERVED. EVERY LANDING SHALL HAVE A MINIMUM |
| DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| DIRECTION OF TRAVEL. |
| |
| 6) IN ORDER TO PROVIDE AIR FLOW TO THE SPACES BETWEEN |
| RAFTERS A CONTINUOUS EAVE VENT WILL BE REQUIRED. PLEASE |
| REVISE WALL SECTION. SEE FBC R806.1 VENTILATION |
| REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES |
| FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE |
| UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION |
| FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS |
| PROTECTED AGAINST THE ENTRANCE OF RAIN. VENTILATING |
| OPENINGS SHALL BE PROVIDED WITH CORROSION-RESISTANT |
| WIRE MESH, WITH 1/8 INCH (3.2 MM) MINIMUM TO 1/4 INCH |
| (6.4 MM) MAXIMUM OPENINGS. |
| |
| 7) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL |
| BASED ON THE GRAVITY DESIGN LOADS OF THE ADDITION. |
| R401.2 |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS. ONLY ONE OF |
| EACH WAS SUBMITTED. FBC 106.1* CITY AMENDMENTS. |
| |
| 9) ON THE PRODUCT APPROVAL FOR THE GAF BUILT-UP ROOF |
| SYSTEM, SPECIFY WHICH ONE OF THE FASTENING OPTIONS FOR |
| THE NON-INSULATED WOOD DECK ON PAGE 17 OF THE NOA WILL |
| BE USED. ALSO SUBMIT TWO COPIES OF SIGNED AND SEALED |
| RAS 117 CALCULATIONS FOR ENHANCED FASTENING FROM AN |
| ARCHITECT OR ENGINEER AS REQUIRED BY LIMITATION NUMBER |
| 7 ON PAGE 19 OF THE NOA. FBC R301.2.1 |
| |