Plan Review Details - Permit 08120480
Plan Review Stops For Permit 08120480
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-06 Cont ID  
Sent By rmcdouga Date 2009-04-06 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2009-04-06 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-25 Cont ID  
Sent By rmcdouga Date 2009-03-25 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2009-03-25 Time 11:28 Sent To  
Notes
2009-03-25 11:33:17STATUS WILL BE CHANGED TO P WHEN PLANS HAVE BEEN
 REVIEWED AND STAMPED BY P.B.COUNTY FOR IMPACT FEES AND
 HAVE BEEN RETURNED WITH COPY OF THE PAID RECEIPT. ALSO
 OWNER/AGENT SIGNATURE IS REQUIRED ON THE ENERGY
 CALCULATION FORMS AND RECORDED COPY OF NOC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-13 Cont ID  
Sent By rmcdouga Date 2009-01-13 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2009-01-13 Time 08:01 Sent To  
Notes
2009-01-12 16:57:342004 FBC W/2007 REVISION
 ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORM. FBC 13-6.
  
 4) THE MINIMUM WALL INSULATION IS R-5 PER ENERGY CALC.
 FORM. REVISE WALL SECTION. FBC 13-602.1.C.1.2
  
 5) SHOW COMPLIANCE WITH R311.4.3 LANDINGS AT DOORS.
 THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF EACH
 EXTERIOR DOOR.
 EXCEPTION: WHERE A STAIRWAY OF TWO OR FEWER RISERS IS
 LOCATED ON THE EXTERIOR SIDE OF A DOOR, OTHER THAN THE
 REQUIRED EXIT DOOR, A LANDING IS NOT REQUIRED FOR THE
 EXTERIOR SIDE OF THE DOOR.
 THE FLOOR OR LANDING AT EXTERIOR DOORS REQUIRED BY
 SECTION R311.4.1 SHALL NOT BE REQUIRED TO COMPLY WITH
 THIS REQUIREMENT BUT SHALL HAVE A RISE NO GREATER THAN
 THAT PERMITTED IN SECTION R311.5.3.
 EXCEPTION: THE LANDING AT AN EXTERIOR DOORWAY SHALL NOT
 BE MORE THAN 7? INCHES (196 MM) BELOW THE TOP OF THE
 THRESHOLD, PROVIDED THE DOOR, OTHER THAN AN EXTERIOR
 STORM OR SCREEN DOOR DOES NOT SWING OVER THE LANDING.
 THE WIDTH OF EACH LANDING SHALL NOT BE LESS THAN THE
 DOOR SERVED. EVERY LANDING SHALL HAVE A MINIMUM
 DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL.
  
 6) IN ORDER TO PROVIDE AIR FLOW TO THE SPACES BETWEEN
 RAFTERS A CONTINUOUS EAVE VENT WILL BE REQUIRED. PLEASE
 REVISE WALL SECTION. SEE FBC R806.1 VENTILATION
 REQUIRED. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN. VENTILATING
 OPENINGS SHALL BE PROVIDED WITH CORROSION-RESISTANT
 WIRE MESH, WITH 1/8 INCH (3.2 MM) MINIMUM TO 1/4 INCH
 (6.4 MM) MAXIMUM OPENINGS.
  
 7) SPECIFY THE REQUIRED BEARING CAPACITY OF THE SOIL
 BASED ON THE GRAVITY DESIGN LOADS OF THE ADDITION.
 R401.2
  
 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS. ONLY ONE OF
 EACH WAS SUBMITTED. FBC 106.1* CITY AMENDMENTS.
  
 9) ON THE PRODUCT APPROVAL FOR THE GAF BUILT-UP ROOF
 SYSTEM, SPECIFY WHICH ONE OF THE FASTENING OPTIONS FOR
 THE NON-INSULATED WOOD DECK ON PAGE 17 OF THE NOA WILL
 BE USED. ALSO SUBMIT TWO COPIES OF SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR ENHANCED FASTENING FROM AN
 ARCHITECT OR ENGINEER AS REQUIRED BY LIMITATION NUMBER
 7 ON PAGE 19 OF THE NOA. FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-03-24 Cont ID  
Sent By btrobaug Date 2009-03-24 Time 13:55 Rev Time 0.00
Received By btrobaug Date 2009-03-24 Time 13:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 08:49 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 08:35 Sent To B
Notes
2008-12-29 08:49:29 
  
 NOTE: THE PROJECT DESCRIPTION ON THE APPLICATION
 INDICATES ADDING A STORAGE ROOM, THE ADDION ON THE
 FLOOR PLAN IS LABELED "DEN". THE ROOM IS COMPLIANT WITH
 THE 2005 NEC FOR EITHER APPLICATION AND THEREFORE WILL
 PASS THE ELECTRICAL REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-06 Cont ID  
Sent By adarroug Date 2009-03-06 Time 08:21 Rev Time 0.00
Received By adarroug Date 2009-03-06 Time 08:21 Sent To Z
Notes
2009-03-06 08:24:59EXPEDITED--DHCD
  
 TO "Z" BOX/RESUB--NEW SHEETS FOR "ELECT"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-26 Cont ID  
Sent By adarroug Date 2008-12-26 Time 15:42 Rev Time 0.00
Received By adarroug Date 2008-12-26 Time 15:42 Sent To E
Notes
2008-12-26 15:42:53TO "BTROBAUGH" DESK/PER "LMARTINEZ"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-13 Cont ID  
Sent By rmcdouga Date 2009-01-13 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2008-12-22 Time 10:12 Sent To  
Notes
2008-12-22 10:13:17TO "SFR" "Z"

Review Stop Z ZONING
Rev No 2 Status P Date 2009-03-11 Cont ID  
Sent By mcruz Date 2009-03-11 Time 09:16 Rev Time 0.00
Received By mcruz Date 2009-03-11 Time 09:03 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By mcruz Date 2008-12-26 Time 12:24 Rev Time 0.00
Received By mcruz Date 2008-12-26 Time 12:07 Sent To I
Notes
2008-12-26 12:23:56PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B): OVERHANGS SHALL NOT PROJECT MORE THAN THREE
 (3) FEET INTO A REQUIRED SETBACK.
  
 3. THE SURVEY INDICATES THERE IS A CONCRETE PATIO IN
 THE REAR IF THE HOUSE. HAS THERE BEEN A SHED
 SUBSEQUETLY PLACED ON THE PAD? IF YES, INDICATE THE
 SEPARATION DISTANCE OF THE PROPOSED ADDITION TO THE
 EXISTING SHED. NOTE: PURSUANT TO SECTION 94-304(B)(3)
 OF THE ZLDR, ACCESSORY STRUCTURES SHALL BE LOCATED NO
 CLOSER THAN SIX (6) FEET TO THE PRINCIPAL STRUCTURE.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  