Plan Review Details - Permit 08120370
Plan Review Stops For Permit 08120370
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-07-10 Cont ID  
Sent By shill Date 2009-07-10 Time 13:24 Rev Time 0.00
Received By shill Date 2009-07-10 Time 13:24 Sent To  
Notes
2009-07-10 13:24:59***CONTRACTOR REQUIRED***
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO:
 ROW PERMIT REQUIRED FOR FIXTURES
 BLDG/ELEC PERMITS MAY BE REQUIRED PRIOR TO FIXTURE
 INSTALLATION
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-16 Cont ID  
Sent By shill Date 2009-03-16 Time 16:50 Rev Time 0.00
Received By shill Date 2009-03-16 Time 16:50 Sent To  
Notes
2009-03-16 16:54:46****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEW, NOT ADDRESSED.
  
 3. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB; ALL
 LABOR AND MATERIAL.
  
 4. PROVIDE INFORMATION REGARDING MATERIAL TO BE HUNG
 FROM THE BRACKETS.
  
 5. 2ND REVIEW; SEE ELECTRIC COMMENTS.
  
 6. PROVIDE A SITE PLAN SHOWING THE LOCATIONS FOR THE 72
 BRACKETS. ONLY BRACKETS INSTALLED ONTO
 BUILDINGS/STRUCTURES LOCATED ON THIS PARCEL ID ARE TO
 BE INCLUDED IN THIS PERMIT. BRACKETS INSTALLED ONTO
 OTHER BUILDINGS/STRUCTURES ARE TO BE INCLUDED IN
 SEPARATE PERMITS. FBC*106.
  
 2ND REVIEW; SEE ZONING COMMENTS.
  
 7. WIND RESISTANCE WAS NOT ADDRESSED IN THE ENGINEERING
 CALCULATIONS. SEE FBC1609.
  
 8. WEIGHT OF THE MATERIAL TO BE SUPPORTED BY THE
 BRACKETS APPEARS TO BE 250 POUNDS. PROVIDE INFORMATION
 ON THE SITE PLAN SHOWING WEIGHT AT EACH LOCATION.
 CONTRACTOR STATES THAT THERE ARE 72 BRACKETS; NO
 INFORMATION ABOUT LOCATION OR DISTANCE APART. ARE ALL
 72 BRACKETS, 250# EACH, TOTAL OF 18000 POUNDS,
 INSTALLED ON ONE WALL ON ONE BUILDING? NOT ENOUGH
 INFORMATION PROVIDED TO DETERMINE CODE COMPLIANCE.
 FBC16, FBC*106.
  
 9. DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-22 Cont ID  
Sent By shill Date 2008-12-22 Time 13:34 Rev Time 0.00
Received By shill Date 2008-12-22 Time 13:34 Sent To ENG
Notes
2008-12-22 13:39:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. THE TITLE BLOCK FOR THE ENGINEER IS TO INCLUDE ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
 2. DOCUMENTS ARE TO BE SUBMITTED IN ACCORDANCE WITH
 FAC61G15-23.002. THE CALCULATIONS/SPECIFICATIONS SHOULD
 HAVE AN INDEX SHEET IN COMPLIANCE WITH THIS SECTION.
  
 3. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB; ALL
 LABOR AND MATERIAL.
  
 4. PROVIDE INFORMATION REGARDING MATERIAL TO BE HUNG
 FROM THE BRACKETS.
  
 5. PROVIDE INFORMATION REGARDING ELECTRIC FOR THIS JOB.
 ELECTRIC INFORMATION REQUIRED; ELECTRIC PERMIT MAY BE
 REQUIRED.
  
 6. PROVIDE A SITE PLAN SHOWING THE LOCATIONS FOR THE 72
 BRACKETS. ONLY BRACKETS INSTALLED ONTO
 BUILDINGS/STRUCTURES LOCATED ON THIS PARCEL ID ARE TO
 BE INCLUDED IN THIS PERMIT. BRACKETS INSTALLED ONTO
 OTHER BUILDINGS/STRUCTURES ARE TO BE INCLUDED IN
 SEPARATE PERMITS. FBC*106.
  
 7. WIND LOADS WERE NOT ADDRESSED IN THE ENGINEERING
 CALCULATIONS. SEE FBC1609.
  
 8. WEIGHT OF THE MATERIAL TO BE SUPPORTED BY THE
 BRACKETS APPEARS TO BE 250 POUNDS. PROVIDE INFORMATION
 ON THE SITE PLAN SHOWING WEIGHT AT EACH LOCATION.
 CONTRACTOR STATES THAT THERE ARE 72 BRACKETS; NO
 INFORMATION ABOUT LOCATION OR DISTANCE APART. ARE ALL
 72 BRACKETS, 250# EACH, TOTAL OF 18000 POUNDS,
 INSTALLED ON ONE WALL ON ONE BUILDING? NOT ENOUGH
 INFORMATION PROVIDED TO DETERMINE CODE COMPLIANCE.
 FBC16, FBC*106.
  
 9. DECLARE GOVERNING CODE, INCLUDING 2007
 REVISIONS/SUPPLEMENTS.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 07:56 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 07:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-12 Cont ID  
Sent By dpalmer Date 2009-03-12 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2009-03-12 Time 11:28 Sent To  
Notes
2009-03-12 11:28:59** DENIED 2ND RESUB **
  
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW. NO
 ADJUSTMENTS TO PERMIT APPLICATION OR PLANS WERE MADE.
 NO INFORMATION WAS SUBMITTED FOR ANY ELECTRICAL ON
 EITHER PERMIT.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 09:51 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 09:51 Sent To B
Notes
2008-12-24 09:51:24** DENIED REVIEW **
  
 1) NOTE: VALUE FOR COMPLETE SCOPE OF WORK FOR PERMANENT
 INSTALLATIONS SHALL INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ITEMS
 ARE OWNER SUPPLIED.
 FBC 108.3.
 IT IS NOT POSSIBLE TO HAVE A VALUE OF ALL THAT IS BEING
 INSTALLED FOR $2,450.00 SEE COMMENTS FROM BUILDING
 REVIEWER.
  
 2) NOTE: PLEASE PROVIDE DOCUMENTATION ON LISTED
 EQUIPMENT/SNOW FLAKES OR OTHER DECORATIONS WHICH WILL
 CONTAIN ELECTRICAL LIGHTING FOR ILLUMINATION. ALL ITEMS
 MUST BE LISTED BY A NATIONAL RECOGNIZED TESTING
 LABORATORY.
 110.3
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-12-23 Cont ID  
Sent By mgonzale Date 2008-12-23 Time   Rev Time 1.00
Received By mgonzale Date 2008-12-23 Time   Sent To ENG
Notes
2008-12-23 14:47:12*** PASSED WITH PROVISO ***
  
 CONTACT THE RIGHT-OF-WAY REVIEWER, WINDEL PALMER,
 PROJECT COORDINATOR, THE TRAFFIC ENGINEERS OFFICE AT:
 1000 ? 45TH STREET, SUITE 15
 WEST PALM BEACH, FL 33407
 TELEPHONE: (561) 494-1040
 FAX: (561) 494-1069
  
 FORM CAN BE DOWNLOADED VIA WEB:
 HTTP://WWW.CITYOFWPB.ORG/ENGINEERING/ENG_INFO.HTM#RIGHT
 OFWAY
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2009-03-03 Time 10:50 Rev Time 0.00
Received By adarroug Date 2009-03-03 Time 10:50 Sent To Z
Notes
2009-03-03 10:51:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-03-03 Cont ID  
Sent By adarroug Date 2008-12-24 Time 10:40 Rev Time 0.00
Received By adarroug Date 2008-12-18 Time 09:42 Sent To  
Notes
2008-12-18 09:42:14TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By eschneid Date 2009-07-10 Time 17:24 Rev Time 0.25
Received By eschneid Date 2009-07-10 Time 17:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2009-03-09 Cont ID  
Sent By eschneid Date 2009-03-09 Time 17:46 Rev Time 0.25
Received By eschneid Date 2009-03-09 Time 17:46 Sent To E
Notes
2009-03-09 17:51:59FAILED
  
 1) REPEAT COMMENT - A SITE PLAN AND ELEVATIONS SHOWING
 THE MOUNTING BRACKET LOCATIONS IS REQUIRED.
  
 2) REPEAT COMMENT - THE MOUNTING BRACKETS HAVE ALREADY
 BEEN INSTALLED AND THUS STAFF HAS SEEN THAT THEY ARE ON
 DIFFERENT BUILDINGS, EACH WITH A DIFFERENT PARCEL
 CONTROL NUMBER. A SEPARATE PERMIT IS REQUIRED FOR EACH
 PARCEL CONTROL NUMBER THAT SHOWS THE SPECIFIC
 CONDITIONS OF THE WORK ON THAT PARCEL.
  
 3) REPEAT COMMENT - THE CITYPLACE STAMP IS REQUIRED.
  
 4) THE DECORATIONS WERE LIGHTED. HOW IS THE ELECTRICITY
 SUPPLIED?
  
 4) NOTE THAT A RIGHT-OF-WAY PERMIT/AIR RIGHTS EASEMENT
 WILL BE REQUIRED FOR THE CABLES AND BRACKETS THAT
 ENCROACH OVER THE RIGHT-OF-WAY. PLEASE CONTACT BRIAN
 MOREE OR VINCE NOEL @ (561) 494-1040 FOR DETAILS.
  
 5) THE APPROVED MINOR AMENDMENT REQUIRES THAT THE
 BRACKETS BE PAINTED TO MATCH THE ADJACENT WALL COLOR.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-19 Cont ID  
Sent By eschneid Date 2008-12-19 Time 08:26 Rev Time 0.25
Received By eschneid Date 2008-12-19 Time 08:23 Sent To B
Notes
2008-12-19 08:40:49FAILED
  
 1) AS PREVIOUSLY STATED TO CITYPLACE MANAGEMENT, A
 MINOR AMENDMENT IS REQUIRED FOR THE MOUNTING BRACKET
 AND CABLES ACROSS ROSEMARY CONCEPT.
  
 2) A SITE PLAN AND ELEVATIONS, INCLUDING COLOR PLAN,
 SHOWING THE MOUNTING BRACKET LOCATIONS IS REQUIRED.
  
 3) THE MOUNTING BRACKETS AND CABLES HAVE ALREADY BEEN
 INSTALLED AND THUS STAFF HAS SEEN THAT THEY ARE ON
 DIFFERENT BUILDINGS, EACH WITH A DIFFERENT PARCEL
 CONTROL NUMBER. A SEPARATE PERMIT IS REQUIRED FOR EACH
 PARCEL CONTROL NUMBER THAT SHOWS THE SPECIFIC
 CONDITIONS OF THE WORK ON THAT PARCEL.
  
 4) THE CITYPLACE STAMP IS REQUIRED ON THE PERMIT PLANS.
  
 5) NOTE THAT A RIGHT-OF-WAY PERMIT/AIR RIGHTS EASEMENT
 WILL BE REQUIRED FOR THE CABLES AND BRACKETS THAT
 ENCROACH OVER THE RIGHT-OF-WAY. PLEASE CONTACT BRIAN
 MOREE OR VINCE NOEL @ (561) 494-1040 FOR DETAILS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.