Plan Review Details - Permit 08120340
Plan Review Stops For Permit 08120340
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By jwitmer Date 2009-04-07 Time 12:52 Rev Time 2.22
Received By jwitmer Date 2009-04-07 Time 12:52 Sent To  
Notes
2009-04-07 13:28:42BUILDING PLAN REVIEW
 PERMIT: 08120340
 ADD: 410 EVERNIA ST # 115
 CONT: R. W. MARRELL
 TEL: (321)609-1686
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 06/09
 2ND REVIEW
 ACTION:PROVISO:
  
 PLANS INDICATE A WALL DETAIL TYPICAL WALL DETAIL SHEET
 A1 BUT THERE IS NO INFORMATION HOWW THE 2X12'S WILL BE
 ANCHORED AT THE EXTERIOR WALLS OF THE UNIT. ? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
 PLEASE PROVIDE BY FRAMING INSPECTION.
  
 4/07/09 SPOKE WITH ARCHITECT JEFFERY D. BRASSUER ABOUT
 RED LINING ( BLUE INK) PLANS, MR BRAUSSER GAVE
 APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-01-05 Cont ID  
Sent By jwitmer Date 2009-01-05 Time 13:43 Rev Time 0.77
Received By jwitmer Date 2009-01-05 Time 13:43 Sent To  
Notes
2009-01-05 14:18:00BUILDING PLAN REVIEW
 PERMIT: 08120340
 ADD: 410 EVERNIA ST # 115
 CONT: R. W. MARRELL
 TEL: (321)609-1686
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS AND
 2004 EXISTING BUILDING CODE.
 PLEASE PROVIDEE TO WHAT LEVEL ALTERATION THIS PROJECT
 WILL BE? EXISTING BUILDING CODE 301.5 THE DESSIGNER OF
 RECORD OR AN OWNER MUST ELECT THE LEVEL OF ALTERATION
 PURSUANT TO SECTION 303,304 AND 305 OF THIS CODE.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H )NUMBER OF FLOORS WITHIN THE BUILDING
  
 3) THE LIVE/ WORK LOFT, IS THIS A MEZANINE AS INDICATED
 IN THE FIRE SPRINKLER PLAN. SEE AATTACHMENT OF HOW TO
 CALCULATE THE ALLOWABLE FLOOR AREA WHEN WALLS ARE ADDED
 BENEATH THE MEZZANINE LEVEL. SECTION 505.2.AREA OF
 MEZZANINE . THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF
 THE AREA OF THAT ROOM OR SPACE IN WHICH THEY ARE
 LOCATED. THE ENCLOSED PORTIONS OF ROOMS SHALL NOT BE
 INCLUDED IN A DETERMINATION OF THE SIZE OF THE ROOM IN
 WHICH THE MEZZANINE IS LOCATED. IN DETERMINING THE
 ALLOWABLE MEZZANINE AREA, THE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. WITH THE
 ADDITIONAL WALLS BELOW THE MEZANINE THE ALLOWABLE SPACE
 IS DECREASED FOR THE MEZZANINE LEVEL.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-15 Cont ID  
Sent By dpalmer Date 2009-04-15 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2009-04-15 Time 15:45 Sent To  
Notes
2009-04-15 15:53:55*** REDLINED
  
  
 MAY NOT USE TWIST TIMER IN BATHROOM FOR FAN. FBC
 11-4.27.4 SPOKE TO ARCHITECT, IS OK, WITH REDLINED
 PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 17:02 Sent To  
Notes
2008-12-26 17:02:51** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE LISTED ON ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE.
 240.4,310.16, 408.4
 FBC 106.1.1,106.1.2, 106.3.5.1.2, 106.5. CLARITY,
 COORDINATION AND ADDITIONAL INFORMATION OF RECORD
 PLANS.
  
 3) NOTE: PLEASE OBTAIN MORE INFORMATION ON THE BASE
 BUILDING ELECTRICAL SERVICE WHICH FEEDS THIS TENANT
 SPACE.
 THE SERVICE RISER AS SHOWN IS NOT ENTIRELY ACCURATE.
 THIS SPACE IS NOT FED BY A SEPARATE SERVICE FROM FPL.
 PLEASE REVISE RISER.
 230,225,215.5 ETC
  
 4) NOTE: PLEASE KNOW THAT ALL CONDUITS, CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT IS REQUIRED TO
 CONTAIN EQUIPMENT GROUNDING CONDUCTORS. 250.6,250.24
 ETC. THE METER AS SHOWN IS TENANT METER AND IS REQUIRED
 TO CONTAIN A FLOATING NEUTRAL.
  
 5) NOTE: PLEASE SEE NEC 517.1 FOR HEALTH CARE. THIS IS
 NOW SHOWN AS A DOCTOR?S OFFICE USED FOR EXAMS WHICH IS
 REQUIRED TO MEET 517 PART II. PLEASE SEE 517.10 AND
 REVISE ALL WIRING AS REQUIRED.
 PLEASE KNOW BASED ON A MIXED OCCUPANCY AS SUBMITTED THE
 WIRING METHODS IN THE MEDICAL/EXAM OFFICES SHALL MEET
 517 AS NOTED.
  
 6) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE
 WITH NEC 220. PLEASE SEE 220.112,220.14, 220.42,
 220.43, 220.44 ETC.
 PLEASE SEE 215.3,230.42 FOR ALL CONTINUOUS LOADS WHICH
 ARE REQUIRED TO BE SHOWN AT 125% AND 422.13 FOR
 ELECTRICAL STORAGE TYPE WATER HEATERS.
 THE LOAD CALCULATIONS AS SUBMITTED ARE FOR A
 RESIDENTIAL UNIT ONLY.
  
 7) NOTE: PLEASE SEE 600.5 FOR REQUIRED SIGN CIRCUIT.
 PLEASE SURE THE MINIMUM VA REQUIRED FOR THE SIGN
 CIRCUIT AT A CONTINUOUS LOAD RATING IS FIGURED INTO THE
 CALCULATIONS.
 (1200VA AT 125%).
  
 8) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, .1.3
 AND .1.4 FOR MINIMUM REQUIRED LIGHTING CONTROLS FOR NEW
 INSTALLED.
 PLEASE SEE 13-415.1.ABC.1. THIS IS A TENANT SPACE IN A
 BUILDING GREATER THAN 5K SQ FT.
  
 9) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE LEVELS
 CALCULATIONS FOR NEW BUSINESS AREAS. PLEASE BE SURE TO
 SEE 13-415.2, 13-415.2.ABC.1.1,.1.2.
 PLEASE BE SURE TO SUBMIT A FIXTURE LEGEND FOR ALL NEW
 FIXTURES AND PLEASE BE SURE ALL WATTAGES ETC ARE SHOWN.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-04-09 Cont ID  
Sent By mwennerg Date 2009-04-09 Time 15:26 Rev Time 0.00
Received By mwennerg Date 2009-04-09 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-16 Cont ID  
Sent By mwennerg Date 2009-01-16 Time 15:14 Rev Time 0.00
Received By mwennerg Date 2009-01-16 Time 15:13 Sent To  
Notes
2009-01-16 15:25:35***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY TO COMPLY WITH NFPA 101, 2003. PLEASE ADD NOTE
 TO DRAWINGS.
  
 2) PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 3) PLEASE SHOW THE LOCATION(S) OF THE REQUIRED 2A-10B,C
 RATED FIRE EXTINGUISHERS.
  
 4) FIRE SPRINKLER REMODEL TO COMPLY WITH NFPA 13, 2002
 EDITION. IN ADDITION, SEPARATE SHOP DRAWINGS AND
 PERMITS REQUIRED FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL IF APPLICABLE PRIOR TO EQUIPMENT INSTALLATION.
  
 5) WORK SHALL NOT INTERFERE WITH OR INTERUPT THE
 BUILDING FIRE PROTECTION SYSTEMS.
  
 6) PLEASE ADD THE NUMERICAL ADDRESS TO EACH SHEET
 SUBMITTED FOR REVIEW.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-27 Cont ID  
Sent By adarroug Date 2009-03-27 Time 11:31 Rev Time 0.00
Received By adarroug Date 2009-03-27 Time 11:31 Sent To  
Notes
2009-03-27 11:32:15TO IN-BOX "C8"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 13:40 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 16:19 Sent To  
Notes
2008-12-16 16:29:18TO "COMM" BD#25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 20:00 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 20:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 17:14 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 17:07 Sent To  
Notes
2009-01-24 17:14:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS SPACE WAS ORIGINALLY DESIGNED AS A RESIDENTIAL
 (R2) OCCUPANCY. SHOW HOW THE REQUIRED RATE OF
 VENTILATION IS TO BE PROVIDED FOR THE NEW PROPOSED USE
 AND RECONFIGURED SPACES IN ACCORDANCE WITH FBCEB 809.1
 AND FBCM 403.3. ADDITIONAL COOLING LOADS ON EXISTING
 EQUIPMENT MAY REQUIRE A RECALCULATION OF COOLING LOADS
 IN ACCORDANCE WITH THESE SECTIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 15:11 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 12:17 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 12:17 Sent To  
Notes
2009-01-28 13:40:39DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-1 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___LAV:
 A. 11-4.19.2 CLEARANCE (29" REQD)
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
  
 2. SHT A-1 SHOW THE WATER CLOSET 1'6" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE. CHAPTER 11 FIGURE 28. --
 SHOW THE LAV MINIMUM 15" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE. (FIXTURE SHALL BE CENTERED ON THE 30"
 MEASUREMENT OF THE 30"X48" CLEAR FLOOR SPACE).
  
 3. SHT A-1 TOILET ROOM. PLEASE INDICATE THE LENGTH AND
 WIDTH DIMENSIONS OF THE TOILET ROOM AND INDICATE
 COMPLIANCE WITH THE FINISH REQUIREMENTS PER SECTIONS
 1210.1 & 1210.2. FLOOR REQUIREMENTS & WALLS WITHIN 2
 FEET OF THE WATER CLOSET SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE. SECTION 106.1.2.
  
 4. SHT MEP-1 PLUMBING NOTES, CODE CRITERIA INDICATES
 COMPLIANCE WITH THE STANDARD PLUMBING CODE. THE CODE
 ADOPTED IS THE FBC-2004 PLUMBING CODE WITH 2007
 AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-29 Cont ID  
Sent By mflis Date 2008-12-29 Time 14:32 Rev Time 0.00
Received By mflis Date 2008-12-29 Time 14:32 Sent To  
Notes
2008-12-29 14:33:40ZONING REVIEW: NOT REQUIRED
  
 ** INTERIOR BUILD-OUT FOR GROUND-FLOOR UNIT ONLY
  
 ** NOTE THAT "SITE LOCATION MAP" ON A-1 IS INCORRECT.
 STREETS AND PROJECT ARE NOT PROPERLY LOCATED.
  
 MATT FLIS - 822-1445