Plan Review Details - Permit 08120295
Plan Review Stops For Permit 08120295
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-31 Cont ID  
Sent By jwitmer Date 2008-12-31 Time 10:45 Rev Time 2.22
Received By jwitmer Date 2008-12-31 Time 10:32 Sent To  
Notes
2008-12-31 11:57:12BUILDING PLAN REVIEW
 PERMIT: 08120295
 ADD: 124 N. DIXIE HWY
 CONT: LTI DEVELOPMENT
 TEL: (561)718-6243
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) PLANS LACK WIND DESIGN INFORMATION: 1603.1.4 WIND
 DESIGN DATA. THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM
 OF THE BUILDING:
 2A). BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B) WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C). WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) IMPACT FIXED GLASS
 3B) STOREFRONT DOORS
  
 4) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) SHEET A1.0A CONSTRUCTION NOTE# 4 INDICATES THE
 REMOVAL OF A 24"X24" COLUMN AND REPLACING IT WITH A
 6"X6'X3/8 INCH STEEL COLUMN. WHAT IS THE COLUMN HOLDING
 UP? WILL THE STEEL IN THE BEAM ABOVE HAVE SUFFICIENT
 LAP WITH THE SMALLER COLUMN HEAD? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 7) SHEET A1.0A NOTE# 5 INDICATES THE USE OF FIBERGLASS
 RESIN PANELS, PLEASE PROVIDE ADDITIONAL INFORMATION,
 HOW THEY WILL BE ATTACHED, FLAME SPREAD AND SMOKE
 DEVLOPMENT SECTION 803 AND TABLE 803.5.
  
 8) SHEET A1.0A NOTE # 6 & 7, INDICATE LOWERING THE
 LFLOOR LEVEL 2 1/2 INCHES WIWTH A 1/12 SLOPE. THE
 BOTTOM OF THE RAMP REQUIRES A 6'-0" LANDING PLEASE SEE
 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT
 BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL CLEARENCE.
  
 9) SHEET A1.0A PLANS INDICATE THE USE OF A FIRE WALL
 PIPE PENETRATION, FIRE WALL IS EITHER 3 OR 4 HR
 RATINGS, PLEASE PROVIDE UL LISTING OR MANUFACTURES FIRE
 STOP ASSEMBLY NUMBER 712.3.1.2.
  
 10) SHEET A1.0A PLANS FAIL TO INDICATE ACCESSIBLE
 TABLES. 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED
 IN THIS SECTION, RESTAURANTS AND CAFETERIAS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 11-4.1 TO
 SECTION 11-4.35. WHERE FIXED TABLES (OR DINING COUNTERS
 WHERE FOOD IS CONSUMED BUT THERE IS NO SERVICE) ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF
 THE FIXED TABLES (OR A PORTION OF THE DINING COUNTER)
 SHALL BE ACCESSIBLE AND SHALL COMPLY WITH SECTION
 11-4.32 AS REQUIRED IN SECTION 11-4.1.3(18).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By dpalmer Date 2008-12-26 Time 15:59 Rev Time 0.00
Received By dpalmer Date 2008-12-26 Time 15:59 Sent To  
Notes
2008-12-26 15:59:50** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING SCHEDULE FOR
 LIGHTING BEING CONTROLLED BY LCP.
 PLEASE INDICATE THE REQUIRED MINIMUM 10HR BATTERY BACK
 UP FOR THE ASTRONOMICAL TIME CLOCK.
 PLEASE SEE SECTION FOR LIGHTING THAT IS REQUIRED TO BE
 CONTROLLED AT POINT OF ENTRANCE AND SO THAT THE
 OCCUPANT CAN VISUALLY SEE ALL LIGHTING BEING CONTROLLED
 OR MEET EXCEPTIONS. AS THIS HAS BEEN A COMMON NOTED ON
 OTHER PROJECTS PERHAPS A SMALL TYPICAL DETAIL FOR THE
 TYPICAL KEYPAD BEING USED WHICH SHOWS THE OVER RIDES AS
 BEING LIT, AND A TYPICAL LABELING OF THE SAME OVER
 RIDES. PLEASE CALL TO GO OVER THIS IF DESIRED.
 A TYPICAL KEYPAD IS USED ON MANY PROJECTS WHICH
 INDICATES THE LIGHTED OVER RIDES AND SIGNAGE.
 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
 .1.4 FOR EXTERIOR.
  
 2) NOTE: PLEASE COMPLETE THE FIXTURE INFORMATION,
 LEGEND AND PLANS. PLEASE SEE FIXTURES SUCH AS FIXTURE
 *C* WHICH IS SHOWN ON PLANS IS NOT ON ANY LEGEND.
 PLEASE SEE FBC 13-415.2.ABC.1.1, AND .1.2. ALL WATTAGES
 ARE BASED ON THE RATING OF THE FIXTURE NOT THE BULB
 WATTAGES USED.
 PLEASE SEE 13-415.2.ABC.1.2 (3.) AS THIS GIVES THE
 MINIMUM VA TO BE 30VA PER FT OF TRACK OR THE TOTAL
 NUMBER OF FIXTURES AT THE RATED VA PER FIXTURE WHICH
 EVER IS GREATER.
  
 3) NOTE: PLEASE SEE 220.43A ALONG WITH COMMENTARY
 ATTACHED BELOW DIRECTLY FROM THE NEC. THE LOAD USED TO
 SIZE THE BRANCH CIRCUIT MAY BE THE 180VA ONLY WHEN
 SIZING THE BRANCH OR THE 200VA PER FT. HOWEVER PER
 220.43A, THE LOAD REQUIRED TO SIZE FEEDERS IS 200VA PER
 FOOT NOT 180VA PER RECEPTACLE. I HAVE EXTRACTED THE
 SECTION FROM THE CODE. PLEASE READ THE LAST TWO
 SENTENCES AS THIS IS FROM THE HANDBOOK COMMENTARY WHICH
 CLEARLY NOTES THE LOAD TO BE FIGURED FOR FEEDERS.
  
 **** 220.43 SHOW-WINDOW AND TRACK LIGHTING
 (A) SHOW WINDOWS FOR SHOW-WINDOW LIGHTING, A LOAD OF
 NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200
 VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW
 WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE.
 FPN:SEE 220.14(G) FOR BRANCH CIRCUITS SUPPLYING SHOW
 WINDOWS.
  
 THE CALCULATION OF 200 VOLT-AMPERES FOR EACH LINEAR
 FOOT OF A SHOW WINDOW IS REQUIRED TO DETERMINE THE
 FEEDER LOAD. SEE THE COMMENTARY FOLLOWING 220.14(G) FOR
 LOAD CALCULATIONS FOR BRANCH CIRCUITS IN SHOW WINDOWS.
  
 ***
  
 4) NOTE: PLEASE SEE 600.5, 215.3, 230.42 ETC AS THE
 SIGN CIRCUIT IS A LIGHTING LOAD TO BE SHOWN AT 125%.
  
 5) NOTE: NO LIGHTING FOR EGRESS PATH UP TO ELECTRIC
 EQUIPMENT PANELS IS SHOWN. PLEASE SEE 700.12F, 700.16,
 NFPA-101 7.8.1.3, 7.8.1.2.2, 7.9.1.2, 7.9.2.2, FBC
 1006.1.2 ETC
  
 6) NOTE: PLEASE FBC 108.3. ALL EQUIPMENT, DESIGN COST,
 MATERIALS AND LABOR SHALL BE INCLUDING EVEN IF ANY OF
 THESE ITEMS ARE OWNER SUPPLIED.
 THE APPLIED VALUE FOR SCOPE AS SHOWN IS LOW. THIS
 COMMENT IS NOT FOR THE DESIGNER.
  
 7) NOTE: PLEASE COORDINATE PANELS AND RISER. SEE PANEL
 *A* SHOWN AS MLO AND ON RISER AS MCB.
 225,230, 215, 240, ETC
 FBC 106.1.1, 106.1.2 FOR COORDINATION AND CLARITY.
  
 8) NOTE: PLEASE SEE NEC 210.8B2 FOR ALL 15AMP AND 20AMP
 RECEPTACLES CIRCUITS INSIDE KITCHEN AREAS WHICH ARE
 REQUIRED TO BE GFI OR GFI PROTECTED. THIS IS REQUIRED
 WHETHER OR NOT THEY ARE RECEPTACLES ONLY FEEDING
 COUNTER SPACES.
  
 9) NOTE: PLEASE SEE NOTE AT THE BOTTOM OF SHEET 2.1E
 WHICH REFERENCES TO SEE SHEET 3.2P FOR ELECTRICAL ON
 ROOF-TOP, HOWEVER THERE IS NO SHEET 3.2P IN PLANS
 SUBMITTED.
 THERE IS HOWEVER A SHEET 3.2M WHICH INDICATES THE ROOF
 TOP ELECTRICAL. THIS SEEMS TO HAVE BEEN A MISPRINT AND
 COULD HAVE BEEN REDLINED. HOWEVER SHOULD BE REVISED AT
 THIS TIME WITH OTHER COMMENTS.
  
 10) NOTE: PLEASE REVISE CODE REFERENCE ON ELECTRICAL
 PLANS. THE COVER SHEET IS CORRECT HOWEVER SEE 2.0E.
 FBC 2004 W/2007 REVISIONS.
 ALSO ANOTHER ITEM WHICH COULD HAVE BEEN REDLINED
 HOWEVER PLANS WERE COMING BACK FOR CORRECTIONS.
  
 11) NOTE: WHERE IS THE LIGHTING CONTROL PANEL GOING TO
 BE LOCATED? NOT SHOWN ON LIGHTING OR POWER PLANS.
 110.26, 240.24 ETC
 FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION, AND CLARITY OF RECORD PLANS.
  
 12) NOTE: PLEASE SEE 422.13 AS THE ELECTRIC STORAGE
 TYPE WATER HEATER LOAD IS REQUIRED TO BE SHOWN AT 125%.
 PLEASE SEE THE 2005 NEC HANDBOOK WHICH PROVIDES A
 COMMENTARY OF THE REVISION IN THE 2005 NEC.
 PLEASE SEE THE LAST SENTENCE OF COMMENTARY.
  
 13) NOTE: PLEASE SEE POWER PLANS. THE WATER HEATER IS
 BEING SHOWN IN THE BATHROOM ON A RECEPTACLE WHICH IS
 NOT PERMITTED. ANOTHER WATER HEATER IS SHOWN ON THE
 SECOND FLOOR EQUIPMENT ROOM AREA LAYOUT HOWEVER THIS
 SEEMS TO BE THE SAME WATER HEATER. EACH UNIT SHOWN
 CONTAINS THE SAME CIRCUIT B-37, 39.
 PLEASE SEE 422.30,31 A DISCONNECTING MEANS OF SOME TYPE
 IS REQUIRED. THE WATER HEATER ON THE SECOND FLOOR DOES
 ACTUALLY SHOW THE REQUIRED DISCONNECT.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-07 Cont ID  
Sent By mwennerg Date 2009-01-07 Time 15:02 Rev Time 0.00
Received By mwennerg Date 2009-01-07 Time 15:02 Sent To  
Notes
2009-01-07 15:07:42***DENIED***
  
 1) HOOD/SUPPRESSION TO MEET ALL REQUIREMENTS OF UL 300
 (WET CHEMICAL SYSTEMS) AND NFPA 96.
  
 2) AN AUDIBLE/VISUAL DEVICE IS REQUIRED TO NOTIFY
 OCCUPANTS IN THE EVENT OF SUPPRESSION ACTIVATION.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR HOOD
 AND SUPPRESSION SYSTEMS.
  
 4) PROVIDE DETRAILS ILLUSTRATING ASSOCIATED EQUIPMENT
 AND LOCATION OF THE MANUAL MEANS OF ACTIVATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 16:04 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 16:04 Sent To  
Notes
2009-01-27 16:09:51DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
  
 1. SHT 3.0P SUBMIT THE FOLLOWING INFORMATION REQUIRED
 FOR THE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL).
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- INDICATE THE
 PIPE SIZE OF ALL VALVES. THEY SHALL BE FULL SIZE AS PER
 TABLE 402.4(2). THE PIPE SIZE TO THE UPPER PIZZA OVEN
 IS INDICATED AS 3/4". MINIMUM 1" IS REQUIRED. TABLE
 402.4(2).
  
 C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 16:34 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 16:29 Sent To  
Notes
2008-12-15 16:29:16TO "COMM" BD#24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-01-26 Cont ID  
Sent By hmoser Date 2009-01-26 Time 10:55 Rev Time 0.00
Received By hmoser Date 2009-01-26 Time 10:55 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 16:09 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 16:09 Sent To  
Notes
2009-01-27 16:31:34DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 CITY WPB MUNICIPAL CODE
  
 1. SHT 3.0P WATER RISER DIAGRAM. NO WATER SUPPLY IS
 SHOWN TO THE DISHWASHER, NOR TO THE ICE MAKER. PLEASE
 INDICATE ON THE RISER AND SHOW THE REQUIRED WATER
 HAMMER ARRESTORS. SECTIONS 106.1.1 & 604.9. -- THERE IS
 A 1/2" COLD WATER LINE TO "SODA". THIS REQUIRES
 PROTECTION FROM BACKFLOW PER SECTION 608.16.1. PLEASE
 SHOW ON SUPPLY LINE.
  
 2. SHT 3.0P SEE GAS REVIEW FOR COMMENTS ON GAS RISER
 DIAGRAM. TABLE 402.4(2).
  
 3. SHT 3.2M THE SANITARY RISER DIAGRAM DOES NOT RELFECT
 THE FLOOR PLAN FOR THE FLOOR SINK AT THE 3 COMPARTMENT
 SINK. PLEASE CORRELATE. SECTION 106.1.1. -- PLEASE
 CLARIFY "STEAM" FOR INDIRECT FLOOR SINK. PER SECTION
 701.7 WASTEWATER WHEN DISCHARGED INTO THE BUILDING
 DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT HIGHER
 THAN 140 DEGREES F, (60 DEG C). WHEN HIGHER
 TEMPERATURES EXIST, APPROVED COOLING METHODS SHALL BE
 PROVIDED.
  
 4. THE GREASE INTERCEPTOR SHALL BE APPROVED BY THE
 UTILITY DEPT. INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 HOLLY MCGRATH, LABORATORY SUPERVISOR BY PHONE (561)
 822-2271, OR BY FAX (561) 822-2279 OR BY E-MAIL
 [email protected]. ARTICLE III SECTION 90-124(7). A
 WRITTEN DETERMINATION SHALL BE SUBMITTED FOR PERMIT
 APPROVAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-19 Cont ID  
Sent By mflis Date 2008-12-19 Time 16:50 Rev Time 0.00
Received By mflis Date 2008-12-19 Time 16:50 Sent To  
Notes
2008-12-19 17:06:40ZONING REVIEW: FAILED
  
 1) NO DEMOLITION PLANS ARE INDICATED. PLEASE NOTE ALL
 INTERIOR AND EXTEIOR WORK WHICH WILL REQUIRE
 DEMOLITIONS.
 2) EXTERIOR BUILDING ELEVATIONS SHALL BE PROVIDED
 INDICATING NEW WINDOWS AND EXTERIOR FINISHES.
 3) SIDEWALK SEATING AND TABLES SHALL BE PERMITTED
 SUBJECT TO SIDEWALK PERMIT APPROVAL (ISSUED SEPARATELY
 BY THE PLANNING DEPARTMENT PRIOR TO BUSINESS
 OPERATION). ALL EXTERIOR SEATING SHALL PROVIDE A
 MINIMUM 44" CLEAR PATH ON ALL PUBLIC SIDEWALKS AND
 SHALL NOT BLOCK ANY ACCESS OR EQUIPMENT. SEE PLANNING
 DEPARTMENT FOR SIDEWALK CAFE PERMIT APPLICATION.
  
 MATT FLIS - 822-1445