Plan Review Details - Permit 08120230
Plan Review Stops For Permit 08120230
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-01-12 Cont ID  
Sent By jnguyen Date 2009-01-12 Time 13:48 Rev Time 0.00
Received By jnguyen Date 2009-01-09 Time 10:00 Sent To  
Notes
2009-01-12 13:35:37BRENDA KELLEY MENTIONED THERE WERE TWO RETAIL TENANT
 SPACES ON THE FIRST FLOOR FACING CLEMATIS ST OF THE
 CITY CENTER PARKING GARAGE (AT 500 BANYAN BLVD). I
 EXAMINED THE SITE PLANS & WENT OUT ON LOCATION TO
 INSPECT THE AREA FOR MYSELF. GOING EAST TO WEST, I
 DECIDED TO GIVE THE FIRST TENANT SPACE AN ADDRESS OF
 505 CLEMATIS ST & THE SECOND ONE WAS ASSIGNED 509
 CLEMATIS ST. I SENT OUT AN E-MAIL NOTIFICATION ADVISING
 ALL OF THE RELEVANT PARTIES OF THE NEW SECONDARY
 ADDRESSES & CREATED THEIR SEQUENTIAL UNIT RECORDS 0001
 & 0002 IN COMMUNITYPLUS UNDER PCN# 74434321010250010. I
 ALSO INFORMED PAPA TO FIX THEIR WEB SITE TO SHOW THE
 PRIMARY ADDRESS OF 500 BANYAN BLVD INTEAD OF THE
 INCORRECT ADDRESS, 500 1ST ST FOR THIS PARCEL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-27 Cont ID  
Sent By mjacobs Date 2009-01-27 Time 10:18 Rev Time 0.00
Received By mjacobs Date 2009-01-27 Time 10:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-15 Cont ID  
Sent By mjacobs Date 2008-12-15 Time 07:34 Rev Time 0.00
Received By mjacobs Date 2008-12-15 Time 07:34 Sent To  
Notes
2008-12-12 16:49:42BUILDING PLAN REVIEW
 PERMIT: 08120230
 ADD: 500 BANYAN BLVD (RETAIL SPACE)
 CONT: CATALFUMO CONSTRUCTION LTD.
 TEL: (561)253-2580
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. THIS
 INFORMATION SHALL BE SHOWN ON THE PLANS.
  
 4) THE DRAWINGS FAIL TO INDICATE THE TYPE OF BUILDING
 PER CHAPTER 6, THE USE AND OCCUPANCY PER CHAPTER 3 AND
 TABLE 503.
  
 5) SHEET A1 SHOWS ONE OPEN SPACE FOR THE RETAIL STORE.
 THE OCCUPANT LOAD OF THE SPACE REQUIRES TWO EXITS. FBC
 1014.2.1 (EXCEPTION #2) THE SEPARATION DISTANCE OF THE
 EXIT DOORS OR EXIT ACCESS DOORS SHALL NOT BE LESS THAN
 ONE-THIRD OF THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE AREA SERVED. THE LOCATION OF THE DOORS
 DOES NOT MEET THE REQUIREMENT. SHOW COMPLIANCE.
  
 6) THE ORIGINAL PERMIT SHEET A1.1 REVISION #6 DATED
 9-16-08 SHOWS TWO SEPARATE RETAIL SPACES AT THE SAME
 LOCATION. THE DOORS WERE IN COMPLIANCE WITH THE TENANT
 SEPARATION WALL FOR SPACE #1.101 AND SPACE #1.102. THE
 PLANS SUBMITTED DO NOT MATCH THE PERMIT SET; THE
 SEPARATION WALL IS REMOVED, INDICATING ONE TENANT. A
 REVISION OF SHEET A1.1 SHALL BE SUBMITTED FOR THE
 ORIGINAL PERMIT SET INDICATING THE REMOVAL OF THE WALL
 WHICH ONCE SEPARATED THE TWO TENANTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-06 Cont ID  
Sent By btrobaug Date 2009-02-06 Time 16:50 Rev Time 0.00
Received By btrobaug Date 2009-02-06 Time 16:12 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-26 Cont ID  
Sent By btrobaug Date 2009-01-26 Time 14:17 Rev Time 0.00
Received By btrobaug Date 2009-01-26 Time 12:09 Sent To  
Notes
2009-01-26 13:35:17 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE POWER DENSITY CALCULATION ON SHEET E2 IS
 INCORRECT AS IT USES 2.1 W/SQ.FT. TABLE 13-415.2.C.1
 INDICATES 1.5 W/SQ.FT FOR RETAIL. PLEASE CORRECT THE
 CALCULATION.
  
 2} THE SQUARE FOOTAGE GIVEN IN THE CALCULATION DOES NOT
 CORRELATE WITH THE SQUARE FOOTAGE ON SHEET A1.
 CORRELATE SAME.
  
 3} SHEET E4 ELECTRICAL RISER DIAGRAM THE GEC SIZE IS
 NOT INDICATED FOR MAIN2 OF 3 BUT MUST BE A MINIMUM OF
 #4 PER 250.66. INDICATE SIZE.
  
 4} THE GEC FOR MAIN 3OF 3 IS LABELED AS 4-600KMCM.
 ALTHOUGH NOT A VIOLATION, IF PART OF THE PERMITTED SET
 OF PLANS THEY MUST BE INSTALLED, OR A REVISION WILL BE
 MUST BE SUBMITTED TO MAKE A CHANGE IN THE FUTURE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By btrobaug Date 2008-12-16 Time 16:11 Rev Time 0.00
Received By btrobaug Date 2008-12-16 Time 14:38 Sent To  
Notes
2008-12-16 16:08:18 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 THE FORE REFERENCE STANDARDS SHALL BE NOTED ON THE
 PLANS.
  
 1} PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4, PROVIDE
 PERFORMANCE CALCULATIONS FOR REVIEW PER 13-415.2.
  
 2} THE CONDUCTORS FOR THE AIR HANDLERS DO NOT COMPLY
 WITH THE OCP IN THE PANEL SCHEDULES PER 310.16, AND DO
 NOT CORRELATE WITH THE MANUFACTURERS SPEC'S ON SHEET
 MO.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-02-09 Cont ID  
Sent By mawillia Date 2009-02-09 Time 10:41 Rev Time 0.00
Received By mawillia Date 2009-02-09 Time 10:26 Sent To  
Notes
2009-02-09 10:36:22*****APPROVED*****
  
  
 PLAN SHEETS A1, E1, AND E2 WERE STAMPED, INITIALED, AND
 DATED; PLAN SHEET FP1 WAS PREVIOUSLY FIRE-STAMPED ON
 01/28/2009.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 13:30 Rev Time 0.00
Received By mawillia Date 2009-01-28 Time 12:24 Sent To  
Notes
2009-01-28 12:26:48*****PROVISO*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WIITH NFPA 241. ON
 SHEET A1, DELETE REFERENCE TO 2008 NFPA 241; AT THE
 TIME OF ORIGINAL SUBMITTAL, THE 2000 EDITION OF NFPA
 241 WAS REFERENCED.
  
 (PLAN SHEET FP1 WAS STAMPED, INITIALED, AND DATED; THE
 FOLLOWING SHEETS ARE TO BE FIRE-STAMPED WHEN THE ABOVE
 COMMENT AS WELL AS THE ELECTRICAL REVIEWER'S COMMENTS
 HAVE BEEN SATISFIED: A1, E1, AND E2.)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-17 Cont ID  
Sent By mawillia Date 2008-12-17 Time 16:14 Rev Time 0.00
Received By mawillia Date 2008-12-17 Time 15:36 Sent To  
Notes
2008-12-17 16:14:45*****UNSAT*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WIITH NFPA 241.
  
 2. IN ORDER TO PREVENT DELAY IN EMERGENCY RESPONSE, HOW
 DOES RESCUE PERSONNEL DISTINGUISH THE PROJECTED TENANT
 SPACE FROM THE OTHER TENANT SPACE(S) ON THE FLOOR
 AND/OR THE BUILDING. PLEASE BE ADVISED THAT IF A SUITE
 NUMBER IS REQUIRED, THAT SUITE NUMBER SHALL BE INCLUDED
 IN THE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 3. ON SHEET A1 - CAPTION 3 - LIFE SAFETY PLAN, PLEASE
 EXPLAIN WHY THERE IS NO FIRE ALARM STROBE LOCATED IN
 EACH RESTROOM.
  
 4. SPECIFY THE NEW INTERIOR FINISH MATERIAL FOR THE
 WALLS AND CEILING IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2009-04-27 Cont ID  
Sent By rregueir Date 2009-04-27 Time 14:17 Rev Time 0.00
Received By rregueir Date 2009-04-27 Time 14:17 Sent To  
Notes
2009-04-27 14:18:00SENT TO RREGUEIRO DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 09:15 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 09:15 Sent To  
Notes
2009-01-22 09:19:34TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 11:08 Rev Time 0.00
Received By rregueir Date 2008-12-11 Time 09:04 Sent To PC
Notes
2008-12-11 09:04:45TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-05-05 Cont ID  
Sent By rregueir Date 2009-05-05 Time 10:27 Rev Time 0.00
Received By rregueir Date 2009-05-04 Time 16:57 Sent To PC
Notes
2009-05-05 10:27:26DETAIL #5 FOR THROUGH-PENETRATIONS SHALL BE APPLIED TO
 BOTH DUCTS PENETRATING THE TENANT SEPARATION WALL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-05 Cont ID  
Sent By rregueir Date 2009-02-05 Time 19:17 Rev Time 0.00
Received By rregueir Date 2009-02-05 Time 19:17 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 11:08 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 10:41 Sent To PC
Notes
2008-12-20 11:08:12REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS, REVISE PLANS
 ACCORDINGLY AND RESUBMIT FOR REVIEW:
  
 1. PAGE M1 SHOWS A PLENUM RETURN CEILING CAVITY. IN
 ADDITION, THIS PAGE ALSO SHOWS TWO CEILING MOUNTED
 BATHROOM EXHAUST FANS (EF1 AND EF2). THESE FANS ARE
 DISCHARGING THROUGH AN EXHAUST DUCT WHICH IS LOCATED IN
 THE PLENUM CEILING CAVITY. THIS DUCT WOULD BE UNDER A
 POSITIVE PRESSURE. EXHAUST DUCTS UNDER POSITIVE
 PRESSURE SHALL NOT PASS THROUGH DUCTS OR PLENUMS IN
 ACCORDANCE WITH FBCM 601.3. PLEASE SHOW AN EXHAUST
 CONFIGURATION WHICH DOES NOT PLACE A POSITIVELY
 PRESSURIZED EXHAUST DUCT WITHIN THE PLENUM SPACE IN
 ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-02-04 Cont ID  
Sent By kstevens Date 2009-02-04 Time 11:58 Rev Time 0.00
Received By kstevens Date 2009-02-04 Time 11:58 Sent To  
Notes
2009-02-04 11:59:07PASSED PROVISO -- DRINKING FOUNTAIN SPOUT SHALL COMPLY
 WITH SECTION 11-4.15.2 SPOUT HEIGHT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-16 Cont ID  
Sent By kstevens Date 2008-12-16 Time 09:14 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 09:14 Sent To  
Notes
2008-12-16 09:41:14DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SUBMIT A CODE SUMMARY. SHOW OCCUPANCY OF BUILDING,
 DESIGN CRITERIA (FBC-2004 W/2005, 2006 2007 REVISIONS),
 INDICATE SQUARE FOOTAGE, ETC. SECTION 106.1.1
  
 2. SHT A1 MOST OCCUPANCIES REQUIRE A DRINKING FOUNTAIN.
 ONCE THE OCCUPANCY IS DECLARED, AND IF REQUIRED, A
 DRINKING FOUNTAIN SHALL BE SHOWN ON THE FLOOR PLAN.
  
 3. IF A DRINKING FOUNTAIN IS REQUIRED, THEN SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL
 SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 4. SHT A4 SHOW COMPLIANCE WITH SECTION 11-4.16.5 FLUSH
 CONTROLS. DETAILS 04(A) & 05(A) SHOW CONTROLS ON THE
 WALL SIDE. CORRELATE WITH DETAIL 01 WHICH SHOWS &
 INDICATES THE CONTROLS ON THE WIDE SIDE.
  
 5. ALL SHEETS WITH MEINHARDT ENGINEERING TITLE BLOCK.
 THE STATE OF FLORIDA INDICATE FOR EB 25980 THE NAME AS
 MEINHARDT OF TEXAS INC. AND THE ADDRESS AS 5429 LBJ
 FREEWAY SUITE 300 DALLAS TAXAS, BUT THE TITLE BLOCKS DO
 NOT INDICATE THIS. PLEASE HAVE THE TITLE BLOCKS REFLECT
 THE NAME AND ADDRESS AS INDICATED IN THE FLORIDA STATE
 DBPR RECORDS. THE FLORIDA INFORMATION CAN ALSO BE
 INCLUDED IN THE TITLE BLOCKS. FAC 61G15-23.002(2) & FS
 471.025.
  
 6. SHT P0 WATER ISOMETRIC WATER RISER DIAGRAM. IDENTIFY
 THE FITTING AT THE TOP OF THE DROP AS IT IS NOT
 INDICATED IN THE PLUMBING LEGEND. IF IT IS AN AIR
 CHAMBER, PLEASE DELETE AS AIR CHAMBERS ARE NOT
 APPROVED. IF IT IS A WATER HAMMER ARRESTOR, THEN THE
 WATER HAMMER ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 & SECTION 604.9.
  
 7. SHT P1 SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM
 INDICATING ALL PIPE SIZES, TRAPS, AND THE POINT OF
 DISPOSAL. SECTIONS 106.3.5.1.3 AND 314.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-03 Cont ID  
Sent By mflis Date 2009-02-03 Time 09:07 Rev Time 0.00
Received By mflis Date 2009-02-03 Time 09:07 Sent To  
Notes
2009-02-03 09:08:24ZONING REVIEW: PASSED
  
 ** PLANS REVISED TO REMOVE HUNG CEILING
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-15 Cont ID  
Sent By mflis Date 2008-12-15 Time 09:03 Rev Time 0.00
Received By mflis Date 2008-12-15 Time 09:03 Sent To  
Notes
2008-12-15 09:37:03ZONING REVIEW: FAILED
  
 ** UNDER DOWNTOWN ACTION COMMITTEE CASE 07-14, THE
 BOARD GRANTED A VARIANCE TO ALLOW A CEILING HEIGHT NO
 LESS THAN 9'-0" IN HEIGHT. THESE PLANS INDICATE CEILING
 HEIGHT AT 8'-0" CLEAR. PLEASE ADJUST.
  
 MATT FLIS - 822-1445
  