Plan Review Details - Permit 08120118
Plan Review Stops For Permit 08120118
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-08 Cont ID  
Sent By btrobaug Date 2008-12-08 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2008-12-08 Time 13:53 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-04 Cont ID  
Sent By btrobaug Date 2008-12-04 Time 16:06 Rev Time 0.00
Received By btrobaug Date 2008-12-04 Time 15:11 Sent To I
Notes
2008-12-04 16:00:08 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN ELECTRODE
 ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR
 FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH,
 CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE
 BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT
 LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING
 OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT
 SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED
 TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR
 OTHER EFFECTIVE MEANS. ADD TO THE RISER DIAGRAM.
  
 2} 408.36(D) SUPPLIED THROUGH A TRANSFORMER- WHERE A
 PANELBOARD IS SUPPLIED THROUGH A TRANSFORMER, THE
 OVERCURRENT PROTECTION REQUIRED BY 408.36(A), (B), AND
 (C) SHALL BE LOCATED ON THE SECONDARY SIDE OF THE
 TRANSFORMER. PANEL "B" MUST PROVIDE SECONDARY
 PROTECTION FOR THE 45KVA TRANSFORMER BY INSTALLING A
 MAIN, OR ADDING A DISCONNECT WITH OCP PER 450.3(B).
  
 3} PER THE FBC THE USE IS "A3" ASSEMBLY, ART GALLERY,
 THEREFORE 1 WATT PER SQUARE FOOT SHOULD BE USED FOR THE
 LIGHTING LOAD CALCULATION FOR ASSEMBLY HALLS 220.12.
  
 4} PER FLORIDA STATUTE 471.003 AN ENGINEER MUST DESIGN
 THIS SERVICE. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE. IN THIS CASE ENGINEERING IS REQUIRED
 BECAUSE THE SERVICE VOLTAGE IS OVER 240 VOLTS AND
 $50,000.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-04 Cont ID  
Sent By btrobaug Date 2008-12-04 Time 16:07 Rev Time 0.00
Received By btrobaug Date 2008-12-04 Time 14:46 Sent To PC
Notes
2008-12-04 14:46:42TO "BTROBAUG" DESK