Plan Review Details - Permit 08120102
Plan Review Stops For Permit 08120102
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-14 Cont ID  
Sent By rmcdouga Date 2009-01-14 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2009-01-14 Time 09:57 Sent To M
Notes
2009-01-14 10:02:03BUILDING PROVISO
  
 SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE
 OUT-SWING IMPACT RATED GLAZED EXTERIOR ALUMINUM DOOR
 FOR APPROVAL PRIOR TO INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-05 Cont ID  
Sent By rmcdouga Date 2008-12-05 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2008-12-05 Time 09:17 Sent To E
Notes
2008-12-05 09:17:302004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) ON SHEET A.1 THE FLOOD ZONE IS INCORRECTLY SPECIFIED
 AS "C". THE CORRECT ONE IS "A5". FBC 106.1.1* CITY
 AMENDMENTS AND SEC. 94-541 CITY OF WPB MUNICIPAL CODE.
  
 2) ON A.1 THE LEVEL OF ALTERATION IS SPECIFIED AS LEVEL
 1 AND IT IS ACTUALLY LEVEL 2. FBC EXISTING BUILDING
 CHAPTER 3 SECTION 304.
  
 3) ON A.1 THE ADDRESS OF THE PROJECT IN THE TITLE BLOCK
 IS INCORRECTLY SPECIFIED AS 313 GREGORY PLACE. PLEASE
 CORRECT. SEE FAC 61G-16.004 AND FBC 106.1.1* CITY
 AMENDMENTS.
  
 4) THE S.1 SHEETS THAT WERE SUBMITTED DO NOT MATCH.
 THEY CONTAIN DIFFERENT INFORMATION. BOTH SETS OF PLANS
 ARE REQUIRED TO CONTAIN IDENTICAL INFORMATION. ONE OF
 THE SHEETS SPECIFIES A PROPOSED BARN IN WELLINGTON FOR
 THE PROJECT IDENTIFICATION IN THE TITLE BLOCK. PLEASE
 CORRECT. SEE FAC 61G-16.004 AND FBC 106.1.1* CITY
 AMENDMENTS.
  
 5) PROVIDE A STRUCTURAL DETAIL INDICATING HOW THE
 EXTERIOR BATHROOM WINDOWS WILL BE ENCLOSED. FBC R601.2
  
 6) ON SHEET A1 THE SHOWER ELEVATIONS ARE LABELED DEMO
 PLAN. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-01-27 Cont ID  
Sent By btrobaug Date 2009-01-27 Time 07:36 Rev Time 0.00
Received By btrobaug Date 2009-01-27 Time 07:24 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 13:22 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 12:21 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-12-05 Cont ID  
Sent By btrobaug Date 2008-12-05 Time 14:28 Rev Time 0.00
Received By btrobaug Date 2008-12-05 Time 12:43 Sent To M
Notes
2008-12-05 14:28:13 
  
 PROVISO/REDLINED
  
 313.1.1 NOTE. 410.4(D) SHOWER LIGHT, 680.43(A)(3) NOT
 LABELED GFI, 680.43(B)-NO HEIGHT GIVEN, MAY NEED
 GFI./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-26 Cont ID  
Sent By adarroug Date 2009-01-26 Time 10:49 Rev Time 0.00
Received By adarroug Date 2009-01-26 Time 10:49 Sent To E
Notes
2009-01-26 10:49:21TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-17 Cont ID  
Sent By adarroug Date 2008-12-17 Time 09:47 Rev Time 0.00
Received By adarroug Date 2008-12-17 Time 09:47 Sent To E
Notes
2008-12-17 09:47:50TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 15:28 Rev Time 0.00
Received By kstevens Date 2008-12-04 Time 15:06 Sent To  
Notes
2008-12-04 15:06:56TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-12-07 Cont ID  
Sent By rregueir Date 2008-12-07 Time 11:05 Rev Time 0.00
Received By rregueir Date 2008-12-07 Time 11:03 Sent To P
Notes
2008-12-07 11:05:03SEPARATE MECHANICAL PERMIT REQUIRED FOR NEW BATH
 EXHAUST AND MODIFIED DRYER EXHAUST SYSTEMS. PERMIT
 APPLICATION MAY BE SUBMITTED BY MECHANICAL, A/C
 CONTRACTORS OR OWNER/BUILDER.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-28 Cont ID  
Sent By lwagner Date 2009-01-28 Time 10:47 Rev Time 0.00
Received By lwagner Date 2009-01-28 Time 10:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-13 Cont ID  
Sent By kstevens Date 2009-01-13 Time 14:53 Rev Time 0.00
Received By kstevens Date 2009-01-13 Time 14:53 Sent To M
Notes
2009-01-13 15:00:39DENIED
 REFERENCE:
 FBC-2004 PLUMBING
  
 1. SHT PE.1 NEW SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. THE TUB, SHOWER, AND WASH MACHINE
 SHALL BE TRAPPED. SECTION 1002.1. THE WASH MACHINE
 REQUIRES A STANDPIPE PER SECTION 1002.1 & SHALL CONFORM
 TO SECTION 802.4. THE RISER INDICATES TRAPS FOR THE LAV
 UNDERGROUND. THE TRAPS SHALL BE PLACED AS CLOSE AS
 POSSIBLE TO THE FIXTURE OUTLET AND THE VERTICLE
 DISTANCE FROM THE FIXTURE OUTLET TO THE TRAP WEIR SHALL
 NOT EXCEED 24 INCHES. SECTION 1002.1. PLEASE SEE RED
 LINE INFORMATION ON ONE SET OF PLANS AND CORRECT PLANS
 SO THEY MEET THESE CODE REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By kstevens Date 2008-12-09 Time 15:06 Rev Time 0.00
Received By kstevens Date 2008-12-09 Time 15:06 Sent To  
Notes
2008-12-09 15:23:46DENIED
 REFERENCE:
 FBC-2004 RESIDENTIAL
 FBC-2004 FUEL GAS
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
  
 1. SHT A-1 ADDRESS IN THE TITLE BLOCK DOES NOT REFLECT
 THE ADDRESS ON THE APPLICATION NOR THE ADDRESS ON THE
 OTHER SHEETS. SECTION 106.1.1.
  
 2. SHT A-1 THE LEVEL OF ALTERATION IS INCORRECT.
 SECTION 303.4.
  
 3. SHT A-1 DETAIL FOR THE SHOWER IS TITLED "DEMOLITION"
 PLEASE CLARIFY. SECTION 106.1.1.
  
 4. SHT A-1 DEMOLITION PLAN. IN THE REMOVAL OF ANY PART
 OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 PLEASE INDICATE ON THE RISER DIAGRAM WHERE THE WASH
 MACHINE CONNECTION TO THE SANITARY IS CAPPED. OFF
 SECTION 704.5.
  
 5. SHT PE.1 THE SANITARY RISER DIAGRAM SUBMITTED IS FOR
 THE KITCHEN AND ANOTHER SINK NOT INDICATED ON THE FLOOR
 PLAN. WORK IN THE KITCHEN AREA IS NOT INDICATED ON THE
 APPLICATION. PLEASE SUBMIT A SANITARY RISER DIAGRAM FOR
 THE BATHROOM AND THE LAUNDRY ROOM SHOWING ALL PIPE
 SIZES, TRAPS, VENTS AND CONNECTION LOCATION TO EXISTING
 BUILDING DRAIN. SECTION 106.3.5.1.3(4)(6)(13).
  
 6. A SEPARATE GAS PERMIT IS REQUIRED FOR THE GAS WATER
 HEATER. SEE ATTACHED SHEET WITH REQUIREMENTS FOR A GAS
 PERMIT. INFORMATION REQUIRED WHEN APPLYING FOR GAS
 PERMIT.
  
 7. SHT S.1 HAS INFORMATION THAT IS DIFFERENT FOR EACH
 SHEET SUBMITTED. PLEASE SUBMIT 2 SETS OF PLANS WITH THE
 SAME INFORMATION FOR REVIEW. SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  