Plan Review Details - Permit 08120071
Plan Review Stops For Permit 08120071
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-11-02 Cont ID  
Sent By jgomez Date 2009-11-02 Time 10:16 Rev Time 0.00
Received By jgomez Date 2009-11-02 Time 10:16 Sent To PC
Notes
2009-11-02 10:19:12SUBMITTAL PACKAGE APPROVED WITH PROVISO:
  
 1- ACCORDING TO PAGE 8 OF INSTALLATION AND OWNER'S
 MANUAL SUBMITTED, NEED TO PROVIDE 3'0 CLEARANCE ON ALL
 SIDES OF GENERATOR. VERIFY IN FIELD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By jgomez Date 2009-08-19 Time 17:44 Rev Time 0.00
Received By jgomez Date 2009-08-19 Time 17:43 Sent To PC
Notes
2009-08-19 17:58:10BUILDING REVIEW APPROVED WITH PROVISO:
  
 *** 1- NEW GYM AREA CAN NOT BE USED FOR SLEEPING. SEC.
 R309.1 OF 2004 FLORIDA RESIDENTIAL CODE.
 *** 2- FLAT ROOF PRODUCT APPROVAL NOA 07-0730.03
 SUBMITTED:
 A) MARK WHICH APPROVED ASSEMBLY AND BASE SHEET FASTENER
 OPTION IS GOING TO BE INSTALLED.
 B) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 *** 3- SOIL TEST REPORT SUBMITTED:
 A) ENGINEER NEEDS TO PROVIDE HIS SEAL AND LICENSE
 NUMBER.
 B) PROVIDE ENGINEERING FIRM CURRENT CERTIFICATE OF
 AUTHORIZATION AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES.
 *** 4- REVISE SHEET A-1:
 A) REVISE ALL LOADS ON STRUCTURAL NOTE #2 TO MATCH
 LOADS SHOWN ON SHEET S-1.
 B) REVISE STRUCTURAL NOTE #14. WHAT'S 1/2" EXT. PLYWOOD
 VENT SYSTEM REQUIRED?.
 *** 5- PROVIDE SPECIFICATIONS FOR EXISTING GENERATOR TO
 VERIFY REQUIRED CLEARANCES FROM WALL.
 *** 6- ENERGY CALCULATIONS ARE TAKING THE CROSS
 VENTILATION CREDIT. PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE CROSS VENTILATION REQUIREMENTS OF
 SEC. B4.1.3 OF CHAPTER 11 OF 2007 FLORIDA RESIDENTIAL
 CODE (2009 REVISIONS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-07-13 Cont ID  
Sent By jgomez Date 2009-07-13 Time 13:43 Rev Time 0.00
Received By jgomez Date 2009-07-13 Time 13:36 Sent To  
Notes
2009-07-13 13:52:25RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2004 FL. RESIDENTIAL CODE WITH 2007 REVISIONS.
  
 1- A BUILDING PERMIT CAN'T BE ISSUED WITHOUT THE ENERGY
 CALCULATIONS AS REQUIRED BY SEC. 13-103.3 OF 2004 FBC.
 ENERGY CALCULATIONS COMMENTS WERE NOT ADDRESSED AT ALL
 FROM PREVIOUS CHECKLIST. NEED TO PROVIDE COMPLETE
 INFORMATION ON TABLE 6C-2 ON BACK OF FORM SUBMITTED. IT
 WAS ALSO ADVISED TO TAKE INTO CONSIDERATION THE
 PERCENTAGE OF GLASS AREA THAT IS ALLOWED. AREA SHOWN ON
 PLANS DON'T COMPLY WITH TABLE 6C-2 OF ENERGY
 CALCULATIONS SUBMITTED. RE-SUBMIT ENERGY CALCULATIONS
 WITH COMPLETE INFORMATION. ALSO, OWNER/AGENT TO SIGN
 AND DATE BOTTOM OF FORM AS REQUIRED.
  
 2- OWES $ 237.60 FOR UPDATED VALUATION. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 NOTE: THIS MAY BE RECORDED LATER AT TIME OF PERMIT PICK
 UP.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) FLAT ROOF MODIFIED BITUMEN. NOA 03-0501.02 SUBMITTED
 EXPIRED ON 11/06/08. NEED TO PROVIDE CURRENT NOA. ALSO,
 NEED TO PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING
 AT PERIMETER AND CORNER AREAS. IF NOA REQUIRES
 CALCULATIONS TO BE SIGNED AND SEALED, THEN PROVIDE
 SIGNED AND SEALED CALCULATIONS.
 NOTE: TAKE INTO CONSIDERATION THAT BUILDING IS LOCATED
 ON EXPOSURE 'C" WHEN PROVIDING THE RAS 117
 CALCULATIONS. ALSO, ON PREVIOUS COMMENTS IT WAS
 MENTIONED THAT NAIL SPACING OF 5" O.C. WOULDN'T WORK
 FOR ZONE 3.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS (REPEAT COMMENT). PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR.
  
 C) POLYFOAM TO BE USED FOR ROOF TILE FASTENING. SEE
 TILE PRODUCT APPROVAL. (REPEAT COMMENT).
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE (REPEAT COMMENT. NOT
 ADDRESSED AT ALL).
  
 7- SHEET A-1: ON PREVIOUS CHECKLIST IT WAS NOTED THAT
 DOOR LEADING TO SLEEPING ROOM WAS NOT ALLOWED (SEC.
 R309.1). PLANS WERE REVISED TO SHOW NEW GYM INSTEAD OF
 MOTHER IN LAW SUITE. PROVIDE CLARIFICATION AND REVISE
 PERMIT APPLICATION TO DESCRIBE NEW GYM INSTEAD OF
 MOTHER IN LAW SUITE.
 NOTE: TYPE OF DOOR LEADING TO THE NEW GYM STILL NEEDS
 TO COMPLY WITH SEC. R309.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 8- REVISE SIZE OF MULLION SHOWN ON MULLIONS DETAILS.
 (REPEAT COMMENT). SEE MULLION PRODUCT APPROVAL FOR SIZE
 OF MULLION THAT MEETS THE CALCULATED DESIGN PRESSURES.
  
 9- REVISE STRUCTURAL NOTE #2 TO INCLUDE ALL LOADS,
 INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2004 FLORIDA RESIDENTIAL CODE (REPEAT
 COMMENT. NOT ADDRESSED AT ALL).
  
 10- REVISE NOTE: # 14 OF STRUCTURAL NOTES ON SHEET A-1.
 NAILS REQUIRE MIN. 1 3/4" EMBEDMENT INTO THE HORIZONTAL
 STRUCTURAL MEMBERS. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL). SEE ASTM C-1063 FOR MIN. SIZES REQUIRED.
  
 11- PLANS SHOW EXISTING GENERATOR. PROVIDE GENERATOR
 SPECIFICATIONS TO CHECK MINIMUM DISTANCE REQUIRED FROM
 THE NEW WALL TO THE EXISTING GENERATOR. PLANS SHOW
 2'-0" CLEARANCE. THIS COMMENT IS TO AVOID CONFLICT IN
 THE FUTURE IF THE EXISTING GENERATOR REQUIRES MORE THAN
 2'-0" CLEARANCE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-26 Cont ID  
Sent By jgomez Date 2008-12-26 Time 16:50 Rev Time 0.00
Received By jgomez Date 2008-12-26 Time 10:57 Sent To PC
Notes
2008-12-26 17:16:14RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- FENCES ARE DONE UNDER A SEPARATE PERMIT. APPLY FOR
 THE FENCE PERMIT UNDER A SEPARATE PERMIT APPLICATION.
  
 2- SQUARE FOOTAGE SHOWN ON PLANS STAMPED BY PALM BEACH
 COUNTY FOR IMPACT FEES IS DIFFERENT. BRING PLANS TO
 PALM BEACH COUNTY TO UPDATE TOTAL SQUARE FOOTAGE TO
 MATCH PROPOSED.
  
 3- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC.
 106.8 OF CITY AMENDMENTS TO FBC 2004. THEREFORE OWES
 $237.60 FOR UPDATED VALUATION AND RADON FEES.
  
 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS.
 B) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS.
 C) ROOF TILE. NOA 03-0501.02 SUBMITTED IS EXPIRED. NEED
 CURRENT ONE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 7- SPECIFY HOW IS THE ROOF TILE ATTACHED AS REQUIRED BY
 SEC. 106.1.1.2 OF CITY AMENDMENTS TO FBC 2004. IF USING
 POLYFOAM, THEN PROVIDE THE CORRESPONDING PRODUCT
 APPROVAL.
  
 8- FLAT ROOF NAIL ENHANCING LETTER SUBMITTED CALLS FOR
 NAILS AT 5"O.C. THIS NAILING SPACING DOESN'T WORK FOR
 ZONE #3. REVISE AS REQUIRED.
 ***ALSO, REVISE PERMIT NUMBER ON LETTER TO MATCH NEW
 PERMIT NUMBER.
  
 9- ENERGY CALCULATIONS:
 A) NEED TO COMPLETE INFORMATION ON TABLE 6C-2 ON BACK
 OF FORM.
 ***NOTE: TAKE INTO CONSIDERATION PERCENTAGE OF GLASS
 THAT IS ALLOWED.
  
 B) OWNER/AGENT TO SIGN AND DATE AT BOTTOM OF FORM.
  
 10- SHEET A-1:
 A) DOOR FROM GARAGE TO SLEEPING AREA IS NOT ALLOWED BY
 SEC. R309..1 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE SIZE OF MULLION SHOWN ON TYP. MULLION DETAIL
 TO MATCH SIZE SELECTED ON MULLION PRODUCT APPROVAL.
  
 C) REVISE STRUCTURAL NOTE #2 TO INCLUDE ALL DEAD LOADS
 AND LIVE LOADS, INCLUDING THE ATTIC LIVE LOADS AS
 REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL
 CODE. CLEARLY SPECIFY TOP AND BOTTOM CHORDS LOADS.
 ALSO, REVISE REFERENCE TO CHAPTER 16 FBC. NEED TO
 REFERENCE SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE,
 NOT THE CHAPTER 16 OF FBC.
  
 D) STRUCTURAL NOTE #3: PROVIDE CALCULATIONS TO SHOW
 THAT 2000 PSI SOIL BEARING CAPACITY IS ADEQUATE TO
 SUPPORT PROPOSED STRUCTURE. SEC. R401.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE: COORDINATE INFORMATION WITH SOIL TEST
 RECOMMENDATIONS.
  
 E) REVISE REFERENCE ON NOTE #12. REFER TO THE
 RESIDENTIAL CODE, NOT THE FBC.
  
 F) WHERE IS DETAIL "A" REFERENCED ON NOTE #13?
  
 G) REVISE NOTE #14. SEE ASTM C926 AND ASTM C1063 FOR
 MINIMUM SIZE OF NAIL REQUIRED. (1 3/4" MIN. EMBEDMENT
 IS REQUIRED INTO THE WOOD FRAMING).
  
 H) REVISE MASONRY NOTE "M". REFERENCE RESIDENTIAL CODE,
 NOT THE FBC.
  
 11- SHEET A-2:
 A) FOOTING F12.12 SHOWN ON FOUNDATION PLAN IS NOT SHOWN
 ON THE FOOTING SCHEDULE. REVISE AS REQUIRED.
  
 B) CONCRETE SLAB SPECS ON FOUNDATION CALL FOR CONCRETE
 TO HAVE 2500PSF STRENGTH. CORRECT SPECS ARE PSI NOT
 PSF. REVISE AS REQUIRED.
  
 C) PROVIDE CALCULATIONS SHOWING THAT 2000PSF SOIL
 BEARING CAPACITY IS ADEQUATE TO SUPPORT PROPOSED
 STRUCTURE.
 NOTE: COORDINATE WITH SOIL TEST REPORT RECOMMENDATIONS.
 SEC. R401.2 2004 FLORIDA RESIDENTIAL CODE.
  
 D) REVISE ROOF SHEATHING SPECIFICATIONS SHOWN ON ROOF
 FRAMING PLAN AND SECTION 7/A-2 TO MATCH SPECIFICATIONS
 SHOWN ON PLYWOOD SHEATHING NAILING SCHEDULE AND CLEARLY
 IDENTIFY ROOF ZONE 3. SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By btrobaug Date 2009-08-20 Time 12:08 Rev Time 0.00
Received By btrobaug Date 2009-08-20 Time 12:08 Sent To B
Notes
2009-08-20 12:09:07TO JULIO./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 16:32 Rev Time 0.00
Received By btrobaug Date 2009-06-22 Time 16:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-12-12 Cont ID  
Sent By btrobaug Date 2008-12-12 Time 09:23 Rev Time 0.00
Received By btrobaug Date 2008-12-12 Time 08:56 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-10-28 Time 12:24 Sent To  
Notes
2009-10-28 12:24:31TO: J. GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-13 Cont ID  
Sent By jgomez Date 2009-08-13 Time 08:53 Rev Time 0.00
Received By jgomez Date 2009-08-13 Time 08:49 Sent To  
Notes
2009-08-13 08:54:03SENT TO RESIDENTIAL BOX R4.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-12 Cont ID  
Sent By kstevens Date 2009-06-12 Time 10:59 Rev Time 0.00
Received By kstevens Date 2009-06-12 Time 10:59 Sent To  
Notes
2009-06-12 11:12:22SENT TO RESIDENTIAL BOARD R21

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 09:37 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 09:37 Sent To E
Notes
2008-12-11 09:37:56TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-26 Cont ID  
Sent By jgomez Date 2008-12-26 Time 17:16 Rev Time 0.00
Received By jgomez Date 2008-12-03 Time 16:38 Sent To  
Notes
2008-12-03 16:39:04TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By rmcdouga Date 2009-08-20 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2009-08-20 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-07-29 Cont ID  
Sent By rmcdouga Date 2009-07-29 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2009-07-29 Time 15:07 Sent To  
Notes
2009-07-29 15:09:09COMMENTS FROM PREVIOUS REVIEW WERE NOT ADDRESSED. SEE
 COMMENTS FROM FIRST REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-17 Cont ID  
Sent By hmoser Date 2008-12-17 Time 14:22 Rev Time 0.00
Received By hmoser Date 2008-12-17 Time 14:17 Sent To P
Notes
2008-12-17 14:26:0312/17/08
 PLEASE PROVIDE HANGING DETAIL FOR THE AIR-HANDLER, AND
 LOCATION OF RETURN AIR GRILL .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-08-13 Cont ID  
Sent By kstevens Date 2009-08-13 Time 13:43 Rev Time 0.00
Received By kstevens Date 2009-08-13 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 16:12 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 10:52 Rev Time 0.00
Received By kstevens Date 2008-12-18 Time 10:52 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By mcruz Date 2009-08-20 Time 11:58 Rev Time 0.00
Received By mcruz Date 2009-08-20 Time 11:57 Sent To B
Notes
2009-08-20 11:58:01**APPROVED PER J ROACH. NO CAHANGES IN STRUCTURE'S
 DIMENSIONS, RESTAMP ONLY. STRUCTURE SHALL NOT BE USED
 AS A DWELLING UNIT.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-24 Cont ID  
Sent By jroach Date 2009-06-24 Time 14:15 Rev Time 0.00
Received By jroach Date 2009-06-24 Time 11:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By mcruz Date 2008-12-09 Time 15:03 Rev Time 0.00
Received By mcruz Date 2008-12-09 Time 14:08 Sent To I
Notes
2008-12-09 14:56:08PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. THE PROPOSED "MOTHER-N-LAW SUITE" IS ENCROACHING
 INTO THE REQUIRED REAR SETBACK ONE (1) FOOT. PURSUANT
 TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS.
  
 PLEASE CORRECT TO COMPLY WITH THE ABOVE PROVISION.
  
 3. NOTE: THE "MOTHER-N-LAW SUITE" SHALL MAINTAIN AN
 INTERIOR CONNECTION AND SHALL NOT HAVE ANY KITCHEN
 FACILITIES OR 220 CONNECTIONS. PLEASE INDICATE THIS ON
 THE PLANS.
  
 4. THE PLANS (SHEET A-2) SHOW A DETAIL FOR A
 FENCE/GATES. PLEASE PROVIDE THIS UNDER A SEPERATE
 PERMIT AND SHOW THE LOCATION OF THE PROPOSED
 FENCE/GATES ON A SURVEY. ALSO PROVIDE AN ELEVATION
 DETAIL OF THE PROPOSED FENCE/GATES.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  