Plan Review Details - Permit 08120054
Plan Review Stops For Permit 08120054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-26 Cont ID  
Sent By mjacobs Date 2008-12-26 Time 14:10 Rev Time 0.00
Received By mjacobs Date 2008-12-26 Time 14:10 Sent To  
Notes
2008-12-26 13:57:43PROVISOR: DOOR #302B: AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
  
  
 PROVISOR: DOOR #302B: AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-08 Cont ID  
Sent By mjacobs Date 2008-12-08 Time 14:04 Rev Time 0.00
Received By mjacobs Date 2008-12-08 Time 14:04 Sent To  
Notes
2008-12-08 14:04:30BUILDING PLAN REVIEW
 PERMIT: 08120054
 ADD: 444 WEST RAILROAD AVE. #300
 CONT: PBM DEVELOPMENT INC.
 TEL: (561)368-2544
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12-8-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-02 Cont ID  
Sent By btrobaug Date 2009-09-02 Time 16:41 Rev Time 0.00
Received By btrobaug Date 2009-09-02 Time 16:41 Sent To PC
Notes
2009-09-02 16:43:16 
  
 REVISION #3, SHEETS E2.1, E3.1, E5.1./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-30 Cont ID  
Sent By btrobaug Date 2008-12-30 Time 14:45 Rev Time 0.00
Received By btrobaug Date 2008-12-30 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-09 Cont ID  
Sent By btrobaug Date 2008-12-09 Time 13:26 Rev Time 0.00
Received By btrobaug Date 2008-12-09 Time 08:40 Sent To  
Notes
2008-12-09 13:26:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 13-415.2.ABC.1.1. PAGE #2 OF THE ENERGY GAUGE
 INPUT DATA REPORT, DOES NOT INDICATE THE CORRECT NUMBER
 OF FIXTURES AS SHOWN ON THE PLAN,
  
 2} THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING
 OR A SEPARATELY METERED OR PERMITTED PORTION OF A
 BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING
 AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE
 SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1.
 THE INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN
 ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED
 THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN
 ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-06 Cont ID  
Sent By mwennerg Date 2009-01-06 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2009-01-06 Time 10:22 Sent To  
Notes
2009-01-06 10:23:53***PROVISO***
  
 PER DISCUSSION WITH ARCHITECT OF RECORD, DOORS LEADING
 TO STAIRWELLS ARE (1) HOUR FIRE RATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 14:55 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 14:55 Sent To  
Notes
2008-12-11 15:10:30PLANS APPEAR TO BE CODE COMPLIANT. PLEASE SEE THE
 FOLLOWING FOR CLARIFICATION:
  
 1) DOOR SCHEDULE INDICATES (2) 1 HOUR RATED DOORS AND
 DRAWINGS SHOW (2) 45 MINUTE DOORS. PLEASE CORRELATE
 INFORMATION.
  
 2) IF APPLICABLE, DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS. SEE SHEET FA0.1
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH THIS AND OTHER
 REVIEW COMMENT CORRECTIONS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-05 Cont ID  
Sent By dpalmer Date 2009-10-05 Time 10:52 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 10:52 Sent To M
Notes
2009-10-05 10:56:01TO RR'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 16:51 Sent To  
Notes
2008-12-22 16:53:56TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-15 Cont ID  
Sent By kstevens Date 2008-12-15 Time 11:47 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 09:06 Sent To  
Notes
2008-12-03 09:10:39TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-07 Cont ID  
Sent By rregueir Date 2009-10-07 Time 12:05 Rev Time 0.00
Received By rregueir Date 2009-10-07 Time 12:05 Sent To  
Notes
2009-10-07 12:05:56REVISED M2.1 AND M4.1 DELTA 4 - PROVISOS ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 11:57 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 11:52 Sent To  
Notes
2008-12-14 11:57:33REVIEW #: 1ST
 ACTION: PASS W/ PROVISO
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING RED-LINE NOTES HAVE BEEN PLACED ON PLANS.
 PLEASE MAKE CORRECTION, REVISE AND RESUBMIT CORRECTED
 PLANS FOR REVISION.
  
 **PROVISO**
 PAGE M2.1: THERE ARE TWO VAV BOXES LABELED AS
 "VAV-3-32" AND THERE IS NO VAV 3-21 SHOWN ON FLOOR
 PLAN. PLEASE CORRECT AND REVISE. FBCM 603.1 AND FBCB
 106.1.1.
  
 **PROVISO**
 PAGE M6.1: FLEX DUCT DETAIL CALLS FOR MIN. 1" WIDE
 STRAP FOR FLEX DUCT SUPPORT. THE SUPPORT SHALL BE MIN.
 1 1/2" WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-12-15 Cont ID  
Sent By kstevens Date 2008-12-15 Time 11:43 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 11:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-10 Cont ID  
Sent By aaponte Date 2008-12-10 Time 15:35 Rev Time 0.00
Received By aaponte Date 2008-12-10 Time 15:35 Sent To  
Notes
***NONE***