Plan Review Details - Permit 08120022
Plan Review Stops For Permit 08120022
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-30 Cont ID  
Sent By shill Date 2009-03-30 Time 17:05 Rev Time 0.00
Received By shill Date 2009-03-30 Time 17:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-03-17 Cont ID  
Sent By shill Date 2009-03-17 Time 14:35 Rev Time 0.00
Received By shill Date 2009-03-17 Time 14:35 Sent To  
Notes
2009-03-17 14:37:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR
 ISSUANCE. ONLY ONE SITE PLAN HAS BEEN SUBMITTED AS AN
 "OLD SET," BUT THIS IS REQUIRED TO SHOW SCOPE AND
 LOCATION OF WORK. FBC*106.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-09 Cont ID  
Sent By shill Date 2009-02-09 Time 10:07 Rev Time 0.00
Received By shill Date 2009-02-09 Time 10:07 Sent To  
Notes
2009-02-09 10:23:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1. CALCULATIONS ARE TO BE IN ACCORDANCE WITH
 FAC61G15-23.002. PLEASE INCLUDE ALL REQUIRED
 INFORMATION AND ORIGINAL SIGNATURE. (CHRIS ARLANDSON
 PE)
  
 2. A CERTIFICATE OF AUTHORIZATION IS REQUIRED FOR A
 COMPANY TO PRACTICE ENGINEERING IN FLORIDA FS471.023
 AND THIS NUMBER IS TO BE INCLUDED IN THE TITLE BLOCK
 FAC61G15-23.002. (ROMCKE ENGINEERING CO)
  
 3. SEE FAC 61G15-23.001 REGARDING SEALS ACCEPTABLE TO
 THE BOARD. (CHRIS ARLANDSON PE)
  
 A SET HAS BEEN RETAINED. PLEASE SUBMIT TWO SIGNED,
 SEALED, DATED ORGINALS WHEN RESUBMITTING.
  
 NEW COMMENT:
  
 4. CALCULATIONS, THE SEAL IS TO INCLUDE THE DATE,
 FS471. (CHRIS ARLANDSON PE)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By shill Date 2008-12-11 Time 16:19 Rev Time 0.00
Received By shill Date 2008-12-11 Time 16:19 Sent To  
Notes
2008-12-11 16:21:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. CALCULATIONS ARE TO BE IN ACCORDANCE WITH
 FAC61G15-23.002. PLEASE INCLUDE ALL REQUIRED
 INFORMATION AND ORIGINAL SIGNATURE.
  
 2. A CERTIFICATE OF AUTHORIZATION IS REQUIRED FOR A
 COMPANY TO PRACTICE ENGINEERING IN FLORIDA FS471.023
 AND THIS NUMBER IS TO BE INCLUDED IN THE TITLE BLOCK
 FAC61G15-23.002.
  
 3. SEE FAC 61G15-23.001 REGARDING SEALS ACCEPTABLE TO
 THE BOARD.
  
 A SET HAS BEEN RETAINED.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-11 Cont ID  
Sent By btrobaug Date 2009-03-11 Time 11:11 Rev Time 0.00
Received By btrobaug Date 2009-03-11 Time 10:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By btrobaug Date 2009-02-03 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2009-02-03 Time 14:34 Sent To B
Notes
2009-02-03 15:27:06 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} IN REFERENCE TO THE SITE/PHOTOMETRIC PLAN, THE
 ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 A) THE CA IS EXPIRED, THE "COBURN" NAME HAS BEEN
 REMOVED FROM THE TITLE BLOCK, SEE DBPR INFORMATION.
 B) THE ENGINEER CAN USE HIS PERSONAL TITLE BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By btrobaug Date 2008-12-11 Time 15:17 Rev Time 0.00
Received By btrobaug Date 2008-12-11 Time 13:34 Sent To B
Notes
2008-12-11 14:53:03 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY. THE COST OF THE WORK BEING OVER
 $50,000 1. 471.003 REQUIRES AN ELECTRICAL OR PLUMBING
 OR AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A
 VALUE OF $50,000 OR LESS; AND 2(A) REQUIRES AN
 AGGREGATE SERVICE CAPACITY OF 600 AMPERES (240 VOLTS)
 OR LESS ON A RESIDENTIAL ELECTRICAL SYSTEM OR 800
 AMPERES (240 VOLTS) OR LESS ON A COMMERCIAL OR
 INDUSTRIAL ELECTRICAL SYSTEM;
  
 2} IF THE HEADS ARE BEING REPLACED PROVIDE
 MANUFACTURERS SPECIFICATIONS (WITH WATTAGE AND VOLTAGE)
 FOR SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-05 Cont ID  
Sent By adarroug Date 2009-03-05 Time 09:30 Rev Time 0.00
Received By adarroug Date 2009-03-05 Time 09:30 Sent To Z
Notes
2009-03-05 09:31:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-27 Cont ID  
Sent By adarroug Date 2009-01-27 Time 08:51 Rev Time 0.00
Received By adarroug Date 2009-01-27 Time 08:51 Sent To Z
Notes
2009-01-27 08:51:37TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 09:56 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 09:56 Sent To E
Notes
2008-12-11 09:59:41TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-11 Cont ID  
Sent By shill Date 2008-12-11 Time 16:21 Rev Time 0.00
Received By shill Date 2008-12-01 Time 16:40 Sent To  
Notes
2008-12-01 16:40:45TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2009-03-10 Cont ID  
Sent By mcruz Date 2009-03-10 Time 14:02 Rev Time 0.00
Received By mcruz Date 2009-03-10 Time 14:02 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-03 Cont ID  
Sent By mcruz Date 2009-02-03 Time 10:26 Rev Time 0.00
Received By mcruz Date 2009-02-02 Time 13:53 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-10 Cont ID  
Sent By mcruz Date 2008-12-10 Time 12:30 Rev Time 0.00
Received By mcruz Date 2008-12-10 Time 10:47 Sent To I
Notes
2008-12-10 12:07:33PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE IF ANY TREES WILL BE REMOVED AS A RESULT OF
 THE PROPOSED PROJECT. IF YES, A TREE ALTERATION/REMOVAL
 PERMIT WILL BE REQUIRED. CONTACT ROBERT KUSSNER, CITY
 LANDSCAPE PLANNER, AT (561) 822-1462 FOR THE
 APPLICATION.
  
 3. INDICATE IF THE PROPOSED INSTALLATION/REPLACEMENT OF
 POLES ARE ENCROACHING INTO ANY PARKING SPACES, I.E.
 EAST SIDE OF BLDG NEAR CANOPY AREA. PURSUANT TO THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-485(L): ENCROACHMENTS.
 REQUIRED OFF-STREET PARKING SPACES SHALL NOT BE
 ENCROACHED UPON BY ELECTRICAL OR MECHANICAL EQUIPMENT,
 PIPES, OR SIMILAR OBSTRUCTIONS. REQUIRED OFF-STREET
 PARKING SPACES MAY BE ENCROACHED UPON BY STRUCTURAL
 SUPPORT COLUMNS; HOWEVER, SUCH ENCROACHMENTS SHALL NOT
 INTERFERE WITH THE NORMAL OPENING AND CLOSING OF
 VEHICLE DOORS. ENCROACHMENTS OF THIS NATURE SHALL BE
 REVIEWED AND APPROVED BY THE CITY ENGINEER PRIOR TO
 ISSUANCE OF A BUILDING PERMIT.
  
 4. SHOW ON PLANS ALL OVER HEAD POWER LINES.
  
 5. INCLUDE/CORRECT THE FOLLOWING INFORMATION IN TABULAR
 DATA:
 - NUMBER OF EXISTING AND PROPOSED.
 - ENLARGE TABLE AND FONT SIZE.
 - PLEASE CLARIFY. THE TABLE INDICATES THERE ARE 3
 EXISTING POLES (TYPE 4). ARE THESE BEING REPLACED AS
 WELL?
  
 6. THERE SEEMS TO BE TWO (2) POLE SYMBOLS ADJACENT TO
 THE EAST PROPERTY LINE. PLEASE CLARIFY.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
  