Plan Review Details - Permit 08110565
Plan Review Stops For Permit 08110565
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-06-09 Cont ID  
Sent By jwitmer Date 2009-06-09 Time 14:02 Rev Time 0.77
Received By jwitmer Date 2009-06-09 Time 14:02 Sent To  
Notes
2009-06-09 15:16:04PASSED, SEPERATE SUB-PERMIT REQUIRED FOR:
 MECHANICAL, PLUMBING, MED-GAS, ELECTRIC AND ROOFING
  
 PRODUCT APPROVALS FOR ROOFING SUBMITTED:
  
 FLAT DECK
 NOA 08-0221.05
 GAF CONVENTIONAL BUILT-UP ROOF SYSTEM FOR LIGHTWEIGHT
 CONCRETE DECK
 DECK TYPE LIGHTWEIGHT CONCRETE, INSULATED
 DECK DESCRIPTION: CELLULAR OR AGGREGATE LIGHTWEIGHT
 CONCRETE
 SYSTEM TYPE A(2)
 DECK: 18-22 GA STEEL DECK
 BAR JOIST @ 5'-0" O.C.
  
  
 SLOPED:
 NOA 07-1023.06
 MONIER- ESPANA CONCRETE ROOF TILE
 ATTACHMENT: TABLE 7 MEDIUM PADDY POLYFOAM POLYPRO
 MOMENT(FT-LBS) 38.7

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-05-27 Cont ID  
Sent By jwitmer Date 2009-05-27 Time 17:02 Rev Time 0.55
Received By jwitmer Date 2009-05-27 Time 16:30 Sent To PC
Notes
2009-05-27 17:03:38BUILDING PLAN REVIEW
 PERMIT: 08110565
 ADD: 2112 N JOG RD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) RADON FEES OF $32.50.
  
 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-15 Cont ID  
Sent By jwitmer Date 2009-04-15 Time 16:25 Rev Time 3.33
Received By jwitmer Date 2009-04-15 Time 16:25 Sent To  
Notes
2009-04-15 16:44:33BUILDING PLAN REVIEW
 PERMIT: 08110565
 ADD: 2112 N JOG RD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE
 UPDATE COVERSHEET TO INCLUDE THE 2007 SUPPLEMENTS, THE
 PERMIT APPLICATION DATE INDICATES A FIRST TIME
 SUBMITTAL DATE OF NOV. 25, 2008.
  
 2) COMPLIED.
  
 3) SEMI COMPLIED ENERGY CALCULATION METHOD B.
  
 4) COMPLIED.
  
 5) SEMI-COMPLIED. THE ENERGY INPUT DATA REPORT
 INDICATES THE ROOF INSULATION VALUE OF R28.4.THE NOA
 SUBMITTED NOA 08-0221.05 SUB-SYSTEM TYPE A(1) INDICATES
 THE USE OF MULTIPLE LAYERS OF INSULATION CAN BE USED.
 PLEASE PROVIDE A ROOFING SHOP DRAWING FOR THE ROOF
 INSULATION AND HOW THE R VALUE OF 28.4 WILL BE MET?
  
 6) COMPLIED.I
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) THE RESPONSE FOR THIS COMMENT INDICATES STORM
 SHUTTERS WILL NOT BE REQUIRED, ALL WINDOWS FOR THIS
 BUILDING WILL BE IMPACT RESISTANT. PLEASE REVIEW THE
 PRODUCT APPROVALS THAT WERE REVIEWED BY YOUR OFFICE
 WITH A SHOP DRAWING STAMP AS NON-IMPACT. SHEET
 A-101FLOORPLAN DOES NOT INDICATE ANY STORAGE ROOMS FOR
 THE STORM SHUTTERS. THE DESIGNER HAS ELECTED TO USE
 STORM PANELS BUT NO STORAGE AREA IS LOCATED WITHIN THE
 BUILDING. PLEASE PROVIDE STORAGE ROOM AND THE
 FOLLOWING:
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 12) SEMI COMPLIED, A NEW FLAT ROOF PRODUCT APPROVAL HAS
 BEEN SUBMITTED NOA 08-0221.05 SUBSYSTEM TYPE A(1) WITH
 A MAXIMUM DESIGN PRESSURE OF -45. THIS BUILDING DOES
 HAVE A 3'-0" PARAPET ELIMINATING THE REQUIREMENTS FOR
 ZONE 3 FASTENING. THE PERIMETER OF THE BUILDING WILL
 STILL NEED ENHANCED FASTENING FOR ZONE 2 NEEDING TO
 MEET THE REQUIREMENT OF -59.2 PSF.
 THIS NOA LIST LIMITATION# 7 THAT ALLOWS FOR ENHANCED
 FASTENING FOR BOTH THE INSULATION AND BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARD 117. CALCULATIONS PREPARED SIGNED AND SEALED
 BY EITHER A FLORIDA REGISTERED ARCHITECT, FLORIDA
 REGISTERED ENGINEER OR REGISTER ROOF CONSALTANT .
 NOTE COMMENT# 5 WILL ALSO NEED TO BE ADDRESSED AS TO
 THICKNESS OF INSULATION TO REACH A R VALUE OF 28.4.
  
 13) COMPLIED.
  
 14) BUILDING PROVISO: KITCHEN W/ HC SINK.:
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 15 A-B) COMPLIED.
  
 15C) SEMI COMPLIED- FLAT ROOF NOA, SEE COMMENTS 5 & 12.
  
 16-20) COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By jwitmer Date 2008-12-18 Time 14:43 Rev Time 12.00
Received By jwitmer Date 2008-12-17 Time 13:11 Sent To  
Notes
2008-12-18 15:37:15BUILDING PLAN REVIEW
 PERMIT: 08110565
 ADD: 2112 N JOG RD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7133
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS, PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. 106.1* /2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1D) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) MISSING SOILS REPORTS, SHEET S-0.1 FOUNDATION NOTE
 F-1 INDICATES TESTING LAB OF THE PALM BEACHES REPORT#
 07/118-02. PLEASE SUBMIT TWO ORIGINAL SIGNED AND SEALED
 REPORTS.
  
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) PROVIDE THE MINIMUM ENERGY INFORMATION FOR SHELL
 BUILDING,13-400.2.A.2 SHELL BUILDINGS. SHELL BUILDINGS
 SHALL COMPLY WITH THIS CODE BY METHOD B OR METHOD C.
 ONCE ALL ENERGY-RELATED DESIGN PARAMETERS ARE KNOWN,
 METHOD A CALCULATION MAY BE
 SUBMITTED. MINIMUM WALL, ROOF INSULATIONS, MECHANICAL
 EQUIPMENT AND ELECTRICAL FOR THE TOTAL BUILDING. SHEET
 M-1 INDICATES FUTURE TENANT SPACE NO MECHANICAL
 INFORMATION AS WELL AS SHEET E-1 MISSING ELECTRICAL FOR
 FUTURE TENANT AT THIS TIME WITH LIMITED ENERGY
 INFORMATION ONLY FORM B OR C MAY BE SUBMITTED.
  
 4) NOTE SHEET A-105 DETAIL 1, SECTION A-A , B-B AND
 DETAIL 1 SHEET A-106 ALL INDICATE THE USE OF R-19
 INSULATION LAID DIRECTLY UPON A ARMSTRONG SUSPENDED
 CEILING SYSTEM.
  
 13-404.1.ABC.1 ROOF/CEILING THERMAL ENVELOPES.
 THE ROOF OR CEILING WHICH FUNCTIONS AS THE BUILDING?S
 THERMAL ENVELOPE SHALL BE INSULATED TO AN R-VALUE OF AT
 LEAST R-10. ROOF INSULATION SHALL NOT BE INSTALLED ON A
 SUSPENDED CEILING WITH REMOVABLE CEILING PANELS.
  
 5) THE OTHER ISSUE THAT WILL TIE TO THE ENERGY
 CALCULATIONS VERSES THE PRODUCT APPROVAL FOR THE FLAT
 ROOF IS A DISCREPANCY. THE ENERGY CALCULATIONS DO
 INDICATE THE USE OF A BAR JOIST AND METAL DECK ROOFING
 SYSTEM WITH A R-19 BATT SYSTEM. IF METHOD ?C? IS CHOSEN
 PLEASE REVIEW THE PRESCRIPTIVE FOR METAL BUILDING ROOFS
 13-401.1.C.1.2.
  
 PLEASE ALSO REVIEW THE PRODUCT APPROVAL FOR THE FLAT
 ROOF SYSTEM, THE PRODUCT SUBMITTED NOA 07-0228.05 JOHN
 MANSVILLE BITUMEN ROOFING SYSTEMS OVER CONCRETE DECKS,
 PLEASE REVIEW DECK TYPE ALL INDICATE CONCRETE DECKS
 INSULATED, REQUIRING INSULATION ABOVE THE
 CONCRETE DECK AND THE SECOND ISSUE IS UNDER THE DECK
 DESCRIPTION ALL ARE 2500 PSI STRUCTURAL CONCRETE DECKS
 OR CONCRETE PLANK DECKS, NOT A METAL DECK AND BAR JOIST
 SYSTEM.
  
 6) IN THE NEW ENERGY CALCULATIONS PLEASE VERIFY THAT
 EXTERIOR DOOR OPENINGS ARE FILLED IN ON THE INPUT DATA
 REPORT, FORM IS LEFT BLANK. 13-403, DOORS.
  
 7) THE COVER SHEET INDICATES THE BUILDING TYPE AS A V-B
 FULLY SPRINKLED, THE INDEX DOES NOT INDICATE ANY FIRE
 SPRINKLER PLANS IN THE SET. 106.3.5.1.1(5) FIRE
 SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC FIRE
 SPRINKLERS.
  
 8) SHEET A-101 PLANS ARE NOT CLEAR AS TO IF THE
 ACCOUNTING OFFICE IS A SEPARATE TENANT OR IF THEY ARE
 THE ACCOUNTANT FOR THE DENTIST( BOOK KEEPING PART OF
 THE DENTAL BUSINESS). IF THE ACCOUNTANT IS A SEPARATE
 TENANT IT APPEARS THEY SHARE A COMMON RESTROOM. PLANS
 DO NOT INDICATE RATED TENANT SEPARATION WALLS.
 708.1(5). EXCEPTION# 1 DOES ALLOW FOR BUSINESS
 OCCUPANCIES NOT TO HAVE FIRE RESISTANCE RATINGS WHEN NO
 AREA BETWEEN FIRE PARTITIONS HAVING A 1-HOUR
 FIRE-RESISTANCE RATING EXCEEDS 3,000 SQ FT. THIS
 BUILDING HAS A NET FLOOR FOOT PRINT OF 3,200 SQ FT
 SOMEWHERE WITHIN THE STRUCTURE A FIRE PARTITION WILL BE
 REQUIRED.
  
 9) SHEET A-101 DOOR# 1-A100B & DOOR 2-A100B BOTH ARE
 MISSING THE 18? ON THE LATCH SIDE. 11-4.13.6.
 DOOR 1-A100B ALSO NEEDS TO REFER TO REVIEW 11-4.4.1
 PROTRUDING OBJECTS.
  
 10) SHEET A-101 DOOR# 1-A107-B SWINGS OVER 50% OF THE
 REQUIRED CORRIDOR. 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 11) SHEET A-101FLOORPLAN DOES NOT INDICATE ANY STORAGE
 ROOMS FOR THE STORM SHUTTERS. THE DESIGNER HAS ELECTED
 TO USE STORM PANELS BUT NO STORAGE AREA IS LOCATED
 WITHIN THE BUILDING. PLEASE PROVIDE STORAGE ROOM AND
 THE FOLLOWING:
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 12) SHEET A-103 & S-3.0 INDICATES THE TYPE OF ROOFING
 SPECIFICATION TO BE USED ON THE FLAT ROOF DECK. THE
 DESIGNER OF RECORD IS REQUESTING A GAF ROOFING PRODUCT
 TO BE USED. SUBMITTED NOA A JOHN MANSVILLE PRODUCT
 WHICH WAS STAMPED AND REVIEWED BY THE DESIGNER OF
 RECORD. PLEASE REVISE SO THE SPECS AND SUBMITTALS WILL
 COINCIDE. PLEASE CIRCLE THE SUBSYSTEM TO BE INSTALLED
 IN THE PRODUCT APPROVAL, REVIEW THE PRESSURES THE
 SYSTEM IS LISTED FOR , IT MAY REQUIRE ENHANCED
 FASTENING SEE SYSTEMS LIMITATION EITHER 7 OR 9 FOR A
 MIAMI-DADE NOA.
  
 13A) A-105 VERSES THE INPUT DATA REPORT FROM THE ENERGY
 CALCULATIONS, WALLS, IN THE INPUT DATA REPORT ALL WALLS
 ARE DESIGNED AS BLOCK WALLS PLEASE NOTE THE FUTURE
 TENANT BUILD-OUT IS A METAL STUD WALL PLEASE CORRECT.
 THE OTHER ISSUE IS THE ENERGY INPUT REPORT ALSO
 INDICATES THE USE OF ?? ISO BOARD AND INSTALLATION OF
 5/8? GYPSUM PLEASE SEE DETAIL# 2 AND INSULATION NOTE#1
 FOR BLOCK AND METAL STUD.
  
 13B)A-105DETAIL# 2 THE WALL INSULATION DOES NOT
 CONTINUE TO THE LOCATION WHERE THE ROOFING INSULATION
 WILL BE REQUIRED (BENEATH THE ROOF DECK) WALL
 INSULATION SHALL BE CONTINOUSOUS13-400 APPENDIX B
 2.2.1.1.
  
 13C) A-105 DETAIL# 2 HAS A NOTE S.S. NOTE# 1, THIS NOTE
 INDICATES A SYNTHETIC STUCCO SYSTEM STO OR EQUAL.
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 14) SHEET A-107 KITCHEN W/ HC SINK. PLANS INDICATE WHAT
 APPEARS TO BE DOORS AND A BOTTOM SHELF. 11-4.24.5 CLEAR
 FLOOR SPACE. A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY
 48 INCHES (760 MM BY 1219 MM) COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK.
  
 15) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 AND
 1609.6.2.2 COMPONENTS AND CLADDING WILL REQUIRE PRODUCT
 APPROVALS, MISSING PRODUCT APPROVALS ARE:
 15A) WALL LOUVERS RULE 9B-72 (31)?
 15B) EFIS WALL AND SOFFIT SYSTEMS RULE 9B(31)?
 15C) ROOF FLAT DECK RULE 9B72(31)( D) WRONG REPORT
 SUBMITTED FOR STRUCTURAL CONCRETE AND
 PLANK DECKS SHEET S-2.0 INDICATES METAL DECK WITH LIGHT
 WEIGHT CONCRETE.
 16) MONIER ROOF TILE CIRCLE THE METHOD OF ATTACHMENT.
 1609.6.2.2./ 1715.2.1.
  
 17) PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE ARE
 GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT. CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION 1609 OR IN
 ACCORDANCE WITH FRSA/RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION. TILE SHALL BE APPLIED ACCORDING
 TO THE MANUFACTURER?S INSTALLATION INSTRUCTIONS OR
 RECOMMENDATIONS OF THE FRSA/RTI 07320- 04.
  
  
 18) SHEET S-0.1 THE PLANS INDICATE THE WIND INFORMATION
 DESIGNED TO ASCE 7-05. 2004 FBC 1609.1.1 & CHAPTER 35
 REFERENCED STANDARDS RECOGNIZES ASCE 7-02 . ALSO
 1603.1.4 WIND DESIGN DATA. PLEASE CORRECT.
  
 19) SHEET S-0.1 NOTE F-2 REFERENCES THE RESIDENTIAL
 CODE WITH SECTION R1816, PLEASE UPDATE.
  
 20) SHEET S-0.1 VENTILATION NOTE# 1 REFERENCES THE
 SOUTH FLORIDA BUILDING CODE WITH NO VENTILATION
 REQUIRED. PLEASE REVIEW SECTION 1203.2 FOR EAVE VENTS
 AS WELL AS VENTS REQUIRED AT LEAST 3 FEET ABOVE THE
 EAVE OR CORNICE VENTS. COMMENTARY ADDRESSES EXCEPTION
 IF ROOF SPACES ARE NOT CREATED(E.G., SOLID CONCRETE
 ROOF SECTIONS), VENTILATION IS NOT REQUIRED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 14:46 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 14:23 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 14:23 Sent To  
Notes
2009-05-15 14:24:03**DENIED 3RD REVIEW **
  
 1) NOTE: THE PREVIOUS NOTES STATED TO PLEASE BE SURE
 AND UPDATE AND COORDINATE ALL PLANS AND DOCUMENTS WITH
 THE CHANGES OF SITE LIGHTING TO THE BUILDING.
 THE SAME EXACT ENERGY CALCULATIONS WERE SUBMITTED BACK
 WITH NO CHANGES TO THE EXTERIOR LIGHTING IN THE INPUT
 DATA REPORT. PLEASE SEE FBC 13-415.2.ABC.1.3 WHICH
 REQUIRES ALL LIGHTING FOR EXTERIOR PORTIONS TO BE
 FIGURED.
 DO NOT REVISE ONE SHEET ON THE IDR AS WAS SUBMITTED FOR
 BUILDING. THE INFORMATION ON THE IDR WILL AFFECT
 SUMMARY SHEET AND TOTALS ON THE CALCULATIONS. THERE ARE
 MULTIPLE SHEETS IN THE CALCULATIONS SUMMARY AND IDR
 WHICH NEED TO BE REVISED. THE CERTIFICATION SHEETS AS
 WELL ALL NEED TO BE REVISED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-04-20 Cont ID  
Sent By dpalmer Date 2009-04-20 Time 12:15 Rev Time 0.00
Received By dpalmer Date 2009-04-20 Time 12:15 Sent To  
Notes
2009-04-20 12:15:44** DENIED **
  
  
  
 1) NOTE: PLANS STATE METHOD *C* AND THE SUBMITTED FLA
 COM IS METHOD *B*. MAY NOT USE BOTH PER 13-415.2.ABC.1.
 THE EXTERIOR SITE PLANS ALSO CONTAINS SITE LIGHTING
 CIRCUITED TO THIS BUILDING WHICH IS NOT IN THE IDR. THE
 NOTES ON SITE PLANS MENTIONS THE SITE WILL BE ON THE
 BASE PROPERTY SERVICE HOWEVER AS NOTED THE CIRCUITS ARE
 FROM THIS BUILDING. ALL LIGHTING ON THIS SEPARATE LEGAL
 PCN SHALL BE FED FROM THIS BUILDING NOT THE SITE
 BUILDING OR SITE SERVICE. PLEASE COORDINATE ALL PLANS.
 BASED ON THE LEGAL SITE SURVEY THERE ARE SOME LIGHT
 POLES ON THIS PROPERTY NOT CIRCUITED TO THIS BUILDING
 AND A POLE ON THE BASE SITE OF THE SHOPPING CENTER
 WHICH WOULD BE FED FROM THE SHOPPING CENTERS ELECTRICAL
 SERVICE?
 ALL PLANS AND SHEETS NEED TO COORDINATE AND BE UPDATED.
 PLEASE TAKE A LOOK AT THE SITE SURVEY FOR THIS LEGAL
 PROPERTY.
 6 FIXTURES SHOULD BE FED FROM THIS BUILDING AND ONLY
 ONE WOULD BE FED FROM SHOPPING CENTER ELECTRICAL
 SERVICE. THIS IS BASED ON THE LEGAL SITE SURVEY.
  
 13-415.2,13-415.2.ABC.1.1,.1.2 AND.1.3
  
 2) NOTE: ***** NOTE FOR INFORMATIONAL. THE ACCOUNTING
 OFFICE AS SHOWN UNDER SUITE 101A MAY NOT BE A SEPARATE
 LEGAL TENANT. THIS MUST BE THE SAME TENANT AS THE
 DENTAL OFFICE. A TENANT MUST HAVE ACCESS TO ALL OVER
 CURRENT PROTECTION DEVICES AT ALL TIMES. SEPARATE
 TENANTS MAY NOT SHARE ELECTRICAL CIRCUITS ALL COMING
 FROM ONE PANEL LOCATED IN ANOTHER TENANTS SPACE.
 ** THIS WILL BE NOTED ON PLANS AS ALL ONE TENANT.
 THIS NOTE #2 IS NOTED ONLY FOR INFORMATION SO THAT
 DESIGN TEAM AND OWNER HAVE A CLEAR UNDERSTANDING THAT
 101 AND 101A IS ONE TENANT.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By dpalmer Date 2008-12-24 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2008-12-24 Time 08:51 Sent To  
Notes
2008-12-24 08:52:16** DENIED REVIEW**
  
  
  
  
 1) NOTE: PLEASE SEE FBC 13-106.1. THIS IS NOT A
 COMPLETE BUILDING AS APPLIED. THE SUBMITTED ENERGY
 CALCULATIONS ARE METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE WHICH MAY NOT BE USED.
 PLEASE SEE THE SECTION ABOVE GIVEN WHICH CLEARLY GIVES
 TWO POSSIBLE METHODS WHICH MAY BE USED. THE METHOD *A*
 SUBMITTED FOR WHOLE BUILDING COMPLIANCE IS NOT CODE
 COMPLIANT EVEN IF IT WERE POSSIBLE TO BE USED. NOT ALL
 ITEMS IN THE INPUT DATA REPORT ARE COMPLETE. ONE
 EXAMPLE WOULD BE EXTERIOR LIGHTING WHICH IS BLANK.
  
 2) NOTE: PLEASE SEE SHEET A-104 AS THE BUILDING AS
 SUBMITTED LENDS TO A BUSINESS OCCUPANCY NOT RETAIL AS
 SHOWN ON THE SEPARATE SUBMITTED ENERGY CALCULATIONS
 WHICH STATE BUILDING AS RETAIL.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SUBMITTED METHOD *B* IS ALSO
 INCOMPLETE. ONE EXAMPLE IS EXTERIOR LIGHTING.
 13-415.2.ABC.1.1,.1.2 AND .1.3.
 13-400.B.3, 13-415.2.ABC.1.1,.1.2,.1.3.
 ** THIS IS ONLY ONE EXAMPLE: THERE ARE OTHER ITEMS
 WHICH ARE NOT CORRECT ON THE IDR>.
  
 ** ALSO METHOD *C* IS SHOWN ON PLANS FOR LIGHTING
 COMPLIANCE. PLEASE SEE 13-415.2.ABC.1 AS MULTIPLE
 METHODS OF CALCULATIONS IS NOT PERMITTED.
  
 3) NOTE: THE METHOD *B* CALCULATIONS SUBMITTED CONTAIN
 A PRINTED NAME FOR PREPARED BY * MR. ARTHUR SLACK*. THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION DOES
 NOT CONTAIN ANY LICENSE INFORMATION FOR SAID INDIVIDUAL
 AS REQUIRED.
 PLEASE SEE FBC 13-101.1 AS THE RESPONSIBLE DESIGNER OF
 RECORD SHALL MEET LICENSING UNDER FLORIDA STATUTES
 471,481 AND 489 WHEN MEETING EXCEPTIONS. THIS
 INDIVIDUAL AS SHOWN DOES NOT CONTAIN THE LICENSING AS
 REQUIRED. THIS IS A COMMERCIAL BUILDING. PLEASE SEE FS
 481.029, 471.003.
 PLEASE ALSO SEE THE LOCATION IN WHICH MECHANICAL
 DESIGNER OF RECORD SHOULD BE CONTAINS A SIGNATURE AND
 SEAL FROM MR. GORDON BUCK WHICH IS NOT ON RECORD AS THE
 MECHANICAL OR ELECTRICAL DESIGNERS. SOME SETS HAVE THIS
 INDIVIDUAL LISTED ON MULTIPLE LINES, USE OF WHITE OUT
 ETC WHICH IS NOT PERMITTED. THESE DOCUMENTS ARE BEING
 RETAINED BY THIS OFFICE. THE LICENSED STRUCTURAL
 ENGINEER BEING LISTED AS THE MECHANICAL DESIGNER
 SIGNING, AND SEALING ENERGY CALCULATIONS IS NOT
 PERMITTED UNLESS MEETING REQUIREMENTS.
 PLEASE SEE FS 471.025. PART 3. NOTED BELOW FORM THE
 STATUTES.
 (3) NO LICENSEE SHALL AFFIX OR PERMIT TO BE AFFIXED HIS
 OR HER SEAL, NAME, OR DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID DOCUMENT, OR OTHER
 DOCUMENT THAT DEPICTS WORK WHICH HE OR SHE IS NOT
 LICENSED TO PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN.
 3) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS.
 SOME OF THESE HAVE APPARENTLY BEEN HANDWRITTEN ON THE
 PLAN WHICH IS NOT PERMITTED. THIS WILL NEED TO BE
 REVISED WHEN MAKING OTHER CORRECTIONS.
 FS 471.025.
 FBC 106.5
  
 4) NOTE: PLEASE PROVIDE EQUIPMENT GROUNDING CONDUCTORS
 AFTER THE FIRST MEANS OF DISCONNECT. THERE ARE NONE
 SHOWN ON RISER?
 PLEASE SEE 250.24, 250.6, 250.110, 250.122 ETC AS THESE
 ARE REQUIRED AFTER THE 600AMP MAIN AS SHOWN.
 PLEASE ALSO INDICATE THE REQUIRED FLOATING NEUTRAL KIT
 AT METERS.
  
 5) NOTE: PLEASE COORDINATE AIC RATINGS. SEE LP-1 WHICH
 INDICATES 65K ON PANEL AND 22K ON RISER.
 110.9
 FBC 106.1.1 FOR COORDINATION AND CLARITY.
  
 6) NOTE: PLEASE SEE NOTES ON PANEL WHICH INDICATE ALL
 CONDUCTORS TO BE #12 UNLESS OTHERWISE NOTED. HOWEVER
 ITEMS WHICH CONTAIN OVER CURRENT PROTECTION HIGHER THAN
 20AMPS ON PANEL SCHEDULE DOES NOT LIST ANY OTHER
 CONDUCTOR SIZES. PLEASE COMPLETE PANEL SCHEDULES WITH
 ALL CONDUCTOR SIZES PER 240.4, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.1
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION AND DETAILS
 FOR LIGHTING CONTROLS. PLEASE SEE PLANS AS THERE WAS NO
 SYMBOL LEGEND FOR WHAT MAY APPEAR TO BE DEVICES FOR
 LIGHTING CONTROLS.
 PLEASE SEE 13-415.1.ABC.1, .1.2, .1.3 AND .1.4.
 NO INFORMATION SHOWN FOR EXTERIOR LIGHTING CONTROLS.
  
 8) NOTE: THE VACANT FUTURE TENANT SPACE WILL BE
 REQUIRED TO CONTAIN A EMERGENCY BACK UP LIGHT
 FIXTURE(S) OF SOME SORT WIRED PER 700.12F AND 700.16.
 NFPA1017.8,7.9.
  
 9) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE LISTED ON THE PLANS.
 FBC 2004 W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 *** AS THERE IS INFORMATION NOT YET SUBMITTED THERE MAY
 BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2009-06-09 Cont ID  
Sent By jwitmer Date 2009-06-09 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2009-06-09 Time 15:20 Sent To  
Notes
2009-06-09 15:29:25SEE ENGINEERING STOP PASSED BY E FABIAN

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-01-06 Cont ID  
Sent By   Date 2009-01-06 Time 1:54 Rev Time 0.00
Received By efabian Date 2009-01-06 Time 13:58 Sent To  
Notes
2009-01-06 13:19:16PLEASE PROVIDE REVISED CIVIL PLANS TO INCLUDE THE
 COMMENTS PER PPRC FROM DECEMBER 10, 2008 MEETING AS
 OUTLINED:
  
 1. PLEASE MOVE PROPOSED (DUAL) R.P.P.A. / BFP FOR
 DOMESTIC POTABLE WATER SUPPLY OUT OF DRAINAGE EASEMENT
 AND ON TO PRIVATE PROPERTY AND PROVIDE A 5 FOOT
 PERIMETER UTILITIY EASEMENT.
  
 2. PROVIDE THE CITY'S STANDARD DETAIL OF THE DUAL
 REDUCED PRESSURE PRINCIPAL ASSEMBLY / BACK FLOW
 PREVENTER ON SHEET C-5
  
 3. SHOW SANITARY CONNECTION & PIPE SIZE (AND EASEMENT
 IF REQUIRED)
  
 4. PARKING SPACES AT N.E. CORNER OF PARCEL SHOULD BE A
 MINIMUN OF 5 FEET FROM THE PROPERTY LINE TO ALLOW FOR
 SUFFICIENT SPACE, TRAFFIC FLOW/CLEARANCE AND A 5 FOOT
 LANDSCAPE BUFFER
  
 IT IS ACKNOWLEDGED THAT DUMPSTERS FOR TRASH REMOVAL ON
 THE SHOPPING CENTER PROPERTY ARE SHARED IN THE GENERAL
 PLAZA'S VICINITY AND WILL NOT REQUIRE A SEPARATE
 DUMPSTER TO SERVE THIS BUILDING
  
 FOR QUESTIONS / COMMENTS PLEASE CONTACT EMERY P. FABIAN
 @ 494-1078
  
  

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 2 Status P Date 2009-05-26 Cont ID  
Sent By efabian Date 2009-05-26 Time 15:59 Rev Time 0.00
Received By efabian Date 2009-05-26 Time 15:58 Sent To  
Notes
***NONE***

Review Stop ENG-A ENGINEERING FORMAL REVIEW
Rev No 1 Status F Date 2009-04-24 Cont ID  
Sent By efabian Date 2009-04-24 Time 16:05 Rev Time 0.00
Received By efabian Date 2009-04-24 Time 16:04 Sent To  
Notes
2009-04-24 16:30:30FAILED - PLEASE NOTE THAT A FORMAL REVIEW BY
 ENGINEERING SERVICES CONSTITUTES ADDITIONAL DOCUMENTS,
 WHICH I CAN ASSIST YOU WITH, AS FOLLOWS:
  
 1. COMPLETION OF THE ENGINEERING SERVICES DEPARTMENT'S
 (AVAILABLE ON-LINE AT THE CITY'S WEB-SITE AT
 WWW.CITYOFWPB.ORG) INTER-ACTIVE CERTIFIED ENGINEER'S
 COST ESTIMATE FORM.
  
 2. SITE DEVELOPMENT PLAN REVIEW FEE AS OUTLINED IN THIS
 DEPARTMENT'S FEE DIRECTORY (3% OF THE PREVIOUSLY STATED
 COST ESTIMATE FORM).
  
 PLEASE CONTACT THE PLAN REVIEWER FOR ASSISTANCE
 REGARDING THESE ITEMS AND OTHER CONSTRUCTION
 ADMINISTRATION RELATED CONCERNS AT:
  
 EMERY P. FABIAN, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 CITY HALL
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH FL 33401
 (561)-494-1048 OFFICE
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-05-22 Cont ID  
Sent By mawillia Date 2009-05-22 Time 13:58 Rev Time 0.00
Received By mawillia Date 2009-05-22 Time 13:14 Sent To  
Notes
2009-05-22 13:58:31******APPROVED*****
  
 *THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A-101, A-102, A-104, A-108,
 E-2, C1, AND C5 WERE STAMPED, INTIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-05-01 Cont ID  
Sent By mawillia Date 2009-05-01 Time 11:14 Rev Time 0.00
Received By mawillia Date 2009-05-01 Time 10:17 Sent To  
Notes
2009-05-01 10:29:41******DENIED*****
  
 *THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED. FOR SUGGESTION
 ON HOW TO ADDRESS THE COMMENT, SEE THE ATTACHED
 CAPITALIZED ITEM
  
  
 1 THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. SEE SHEETS LS-1 &
 LS-2.
  
 2. ANY EXISTING AND/OR PROPOSED FIRE HYDRANT(S) SHALL
 BE IN SERVICE PRIOR, DURING, AND AFTER CONSTRUCTION.
 ADD COMMENT TO SHEET C5
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 INTERIOR FINISH MATERIALS HAVE BEEN INDICATED, HOWEVER
 BE ADVISED THAT THE 2003 EDITION OF NFPA 101 SHALL BE
 REFERENCED (THE CORRECT CODE REFERENCES ARE SHOWN ON
 SHEETS CS AND A-101)
  
  
 *NEW COMMENTS:
  
 A. PLAN SHEET LS-2 NOT STAMPED/SEALED AND SIGNED.
  
 B. PLAN SHEET EP1 (WHICH WAS INCLUDED IN THE FIRST
 SUBMITTAL) COULD NOT BE LOCATED WITH THIS SUBMITTAL. BE
 ADVISED THAT THE COVER SHEET (CS) INDICATES THAT THERE
 IS A EP1 SHEET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 16:27 Rev Time 0.00
Received By mawillia Date 2009-01-28 Time 15:32 Sent To  
Notes
2009-01-28 15:36:02******DENIED*****
  
  
 1 THE ACTUAL/CORRECT ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. SEE SHEETS C1 THRU
 C5, EP1, AND LS-1 & LS-2.
  
 2. ANY EXISTING AND/OR PROPOSED FIRE HYDRANT(S) SHALL
 BE IN SERVICE PRIOR, DURING, AND AFTER CONSTRUCTION.
  
 3. ON SHEET A-104, ADD VERBAGE AS FOLLOWS: AS PER WEST
 PALM BEACH CODE, THE BUIDING'S ADDRESS NUMBERS SHALL BE
 NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE; SUITE NUMBERS SHALL BE AT LEAST 3" HEIGHT
 AND AT LEAST 1" IN WIDTH/STROKE (SUITE NUMBERS OF AT
 LEAST 2"IN HEIGHT NEEDED ON REAR DOORS) . IT IS
 RECOMMENDED BY THIS WRITER THAT THE BUILDING ADDRESS
 NUMBERS BE AT LEAST 8" IN HEIGHT (REQUIREMENT OF PALM
 BEACH COUNTY) SINCE THIS SITE AREA OVERLAPS WITH PALM
 BEACH COUNTY.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
 THIS MAY BE ADDED TO TO SHEET A-108 UNDER THE FINSH
 SCHEDULE.
  
 5. FIRE DOORS (IF REQUIRED) SHALL COMPLY WITH NFPA 80.
 ADD COMMENT TO SHEET A-108 UNDER THE DOOR SCHEDULE.
  
 6. INDICATE THE LOCATION OF THE 2A10:BC RATED FIRE
 EXTINGUISHERS WHICH SATIFIES THE 75'TRAVEL DISTANCE.
  
 7. EXPLAIN WHY THERE IS NO EXIT/EMERGENCY LIGHTING IN
 THE VACAMT/FUTURE TENANT SPACE?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMD
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-06-09 Cont ID  
Sent By jwitmer Date 2009-06-09 Time 15:16 Rev Time 0.00
Received By jwitmer Date 2009-06-08 Time 13:51 Sent To  
Notes
2009-06-08 13:52:19TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By mjacobs Date 2009-04-20 Time   Rev Time  
Received By mjacobs Date 2009-04-10 Time 16:10 Sent To  
Notes
2009-04-13 14:38:09TO COMM BD #27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-28 Cont ID  
Sent By mawillia Date 2009-01-28 Time 15:32 Rev Time 0.00
Received By mawillia Date 2008-12-01 Time 09:06 Sent To  
Notes
2008-12-01 09:08:00TO "COMM" BD#3/PLANS ON RACK/LARGE FOLDED PLANS, AND
 BINDERS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By rregueir Date 2009-04-29 Time 10:15 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 09:16 Sent To  
Notes
2009-04-29 10:15:15REVIEW #: 2ND
 ACTION: PASSED WITH **PROVISO**
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 **PROVISO**
 PROVIDE GRAVITY OPERATED (BACKDRAFT) DAMPER IN LIEU OF
 MOTORIZED DAMPER ON OUTSIDE AIR INTAKE DUCT TO MEET
 EXCEPTION UNDER FBC-B 13-409.1.ABC.3.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-27 Cont ID  
Sent By rregueir Date 2008-12-27 Time 11:48 Rev Time 0.00
Received By rregueir Date 2008-12-22 Time 19:53 Sent To  
Notes
2008-12-27 11:47:58REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED FOR COMPLIANCE WITH THE FOLLOWING:
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS: BOTH A METHOD A AND A METHOD B
 CALCULATION WERE SUBMITTED FOR THIS PROJECT.
 NONRESIDENTIAL BUILDINGS WHICH WILL BE FINISHED IN
 SECTIONS AT A TIME AFTER CONSTRUCTION OF THE SHELL
 SHALL COMPLY WITH EITHER METHOD B OR C OF SUBCHAPTER
 13-4 OF THE CODE PRIOR TO GRANTING OF A PERMIT TO BUILD
 IN ACCORDANCE WITH FBCB 13-101.1.6. ALL ASSUMPTIONS
 MADE ABOUT FEATURES NOT INSTALLED UNTIL LATER THAT ARE
 NOT ON THE BUILDING PLANS SHALL BE LISTED AND APPENDED
 TO THE COMPLIANCE FORM SUBMITTED TO THE BUILDING
 DEPARTMENT IN ACCORDANCE WITH THIS SECTION. PROVIDE
 METHOD B OR C CALCULATIONS FOR THE ENTIRE BUILDING WITH
 APPENDED ASSUMPTIONS FOR UNFINISHED PORTIONS OF THE
 BUILDING.
  
 2. ENERGY CALCULATIONS: THE METHOD B CALCULATIONS
 INDICATE THEY WERE PREPARED BY "ARTHUR SLACK." ENERGY
 CODE CALCULATIONS SHALL BE MADE A PART OF THE PLANS AND
 SPECIFICATIONS OF THE BUILDING. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT PLANS AND SPECIFICATIONS BE PREPARED
 BY AN ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE
 STATE OF FLORIDA IN ACCORDANCE WITH FBCB 13-103.2. THIS
 MEANS THE PREPARER OF THE ENERGY CALCULATIONS SHALL BE
 PREPARED BY AN ARCHITECT, ENGINEER, INSTALLING
 MECHANICAL CONTRACTOR OR FLORIDA CERTIFIED COMMERCIAL
 ENERGY RATER. NO LICENSE INFORMATION COULD BE FOUND FOR
 ARTHUR SLACK ON THE ENERGY CALCULATIONS OR THE FLORIDA
 DBPR WEBSITE. FRED POPPER MAY SERVE AS THE PREPARER,
 DESIGNER OF RECORD AND OWNER/AGENT UNDER THESE
 SECTIONS. IT IS NOT CLEAR WHAT PART MR. GORDON BUCK
 PLAYS IN THE PREPARATION OR CERTIFICATION OF THESE
 CALCULATIONS.
  
 3. PAGE M-1: FLOOR PLAN SHOWS RETURN AIR GRILLS IN
 CEILING OF OFFICE A110 AND LAB A111 BUT REFLECTIVE
 CEILING PLAN ON A102 SHOWS ONLY SUPPLY REGISTERS.
 PLEASE COORDINATE PLANS SHOWING COMPLIANCE WITH THE
 REQUIREMENTS OF FBCM 601.4 AND 603.1.
  
 4. PAGE M-1: THE EXTERIOR WALL O.A. INTAKE CALLS FOR
 350 CFM WHILE THE OA CALCULATIONS ON M-2 CALL FOR 400
 TOTAL CFM. ALSO, AHU-2 IS SHOWN ON FLOOR PLAN TO BE
 BALANCED FOR 50 CFM OF O.A., NOT THE 100 CFM SHOWN ON
 THE O.A. CALCULATIONS SCHEDULE. PLEASE COORDINATE FLOOR
 PLANS WITH SCHEDULE IN ACCORDANCE WITH FBCM 603.1.
  
 5. PAGE M-1: O.A. INTAKE SHOWS MANUAL DAMPERS AND
 DETAIL ON M-2 CALLS FOR OPPOSED BLADE BALANCING DAMPERS
 WHILE NOTE ON EQUIPMENT SCHEDULE CALLS FOR MOTORIZED
 DAMPER AS REQUIRED PER FBCB 13-409.1.ABC.3.2. NO
 MOTORIZED DAMPER IS SHOWN ON FLOOR PLAN. PLEASE
 COORDINATE PLANS, SCHEDULES AND DETAILS TO SHOW
 COMPLIANCE WITH THIS SECTION.
  
 6. PAGE M-1: FLOOR PLAN CALLS FOR TWO LOUVERS INSTALLED
 AT O.A. INTAKES. LOUVERS ARE DEFINED AS PANEL WALLS IN
 ACCORDANCE WITH FAC RULE 9B-72. PROVIDE PRODUCT
 APPROVALS FOR THESE LOUVERS APPROVED IN WRITING BY THE
 DESIGNER OF RECORD IN ACCORDANCE WITH FBCB 106.3.3.
  
 7. PAGES M-1 AND M-2: THE SYMBOLS SHOWN ON THE SYMBOL
 LEGEND DO NOT CORRESPOND WITH THE ONES USED ON THE
 FLOOR PLAN. FOR AN EXAMPLE: SEE THE SYMBOL USED FOR THE
 DUCT MOUNTED SMOKE DETECTOR. PLEASE CLARIFY AND
 COORDINATE FLOOR PLAN WITH SCHEDULE IN ACCORDANCE WITH
 FBCB 106.1.1.
  
 8. PAGE M-2: THE O.A. CALCULATIONS SCHEDULE STATES "AS
 PER... TABLE 2." NO TABLE 2 COULD BE FOUND IN ASHRAE
 62.1-2004. PLEASE CLARIFY. THE DESIGN OUTDOOR AIRFLOW
 REQUIRED IN THE BREATHING ZONE OF THE OCCUPIABLE SPACE
 SHALL BE CALCULATED IN ACCORDANCE WITH CALCULATION 6-1
 USING TABLE 6-1 IN ACCORDANCE WITH FBCM 403.4 AND
 ASHRAE 62.1-2004 SECTION 6.2.2.1.
  
 9. PAGE M-2: NOTE #9 CALLS FOR REFRIGERANT PIPING TO BE
 CHARGED WITH R-22 WHILE THE A/C SCHEDULE CALLS FOR THE
 USE OF R410A. THE REFRIGERANT SHALL BE THAT WHICH THE
 EQUIPMENT OR APPLIANCE WAS DESIGNED TO UTILIZE OR
 CONVERTED TO UTILIZE IN ACCORDANCE WITH FBCM 1102.2 AND
 FBCM 304.1. PLEASE CLARIFY TO DEMONSTRATE COMPLIANCE
 WITH THESE SECTIONS.
  
 10. PAGES M-1 AND M-3: FLOOR PLAN SHOWS DUCT SMOKE
 DETECTOR AT AHU-1 INSTALLED ON SUPPLY (SEE COMMENT #7
 ABOVE) SIDE OF AHU WHILE THE DUCT DETECTOR DETAIL ON
 M-3 SHOWS THE DETECTOR BEING INSTALLED ON THE RETURN
 SIDE. PLEASE COORDINATE FLOOR PLAN WITH DETAIL AND SHOW
 COMPLIANCE WITH FBCM 606.2.1, WHICH REQUIRES THE
 DETECTOR TO BE IN THE SUPPLY AIR SYSTEM.
  
 11. PAGE M-3: THERE ARE THREE DIFFERENT DETAILS ON THIS
 PAGE WHICH SHOW DIFFERING CONFIGURATIONS OF THE
 AUXILIARY/SECONDARY DRAIN PROTECTION BEING PROVIDED AT
 THE AHU. SOME SHOW A SECONDARY DRAIN LINE FROM THE
 AUXILIARY DRAIN PAN AND SOME DO NOT. ALL OF THEM CALL
 FOR A WATER LEVEL DETECTION DEVICE. IF A SECONDARY
 DRAIN LINE IS TO BE USED, PLEASE SHOW THE TERMINATION
 LOCATION TO SHOW IT WILL TERMINATE AT A CONSPICUOUS
 LOCATION IN ACCORDANCE WITH FBCM 307.2.3(1).
 NOTE: THE SECONDARY DRAIN LINE IS NOT REQUIRED IF A
 WATER LEVEL DETECTION DEVICE IS INSTALLED IN/ON THE
 AUXILIARY DRAIN PAN IN ACCORDANCE WITH FBCM 307.2.3(3).
  
 12. PAGE M-3: THE DIFFUSER DETAIL ON THIS PAGE CALLS
 FOR FLEX DUCT TO BE SUPPORTED WITH 1 INCH STRAP. IN NO
 CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT
 IS IN DIRECT CONTACT WITH IT BE LESS THAN 1 1/2 INCHES
 WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 13. PAGE M-3: THE ACCU DETAIL ON THIS PAGE CALLS FOR
 THE CU TO BE BOLTED "TO WITHSTAND 5 WINDS." PLEASE
 CLARIFY THE INTENT OF THIS STATEMENT, DEMONSTRATING
 COMPLIANCE WITH FBCM 301.13. ALSO, PROVIDE
 MANUFACTURER'S DATA SHOWING THESE OUTDOOR APPLIANCES
 ARE DESIGNED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH THIS SAME SECTION.
  
 14. PAGES M-2 AND E0: THE A/C EQUIPMENT SCHEDULE ON M-2
 CALLS FOR MOCP OF 15 AMPS FOR CU-2 WHILE THE PANEL
 SCHEDULE ON PAGE E0 CALLS FOR A 20 AMP BREAKER. PLEASE
 VERIFY WHICH OF THESE IS CORRECT AND PROVIDE THE
 CORRECTLY SIZED OCP BREAKER IN ACCORDANCE WITH FBCM
 304.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2009-04-27 Cont ID  
Sent By kstevens Date 2009-04-27 Time 16:36 Rev Time 0.00
Received By kstevens Date 2009-04-27 Time 16:36 Sent To  
Notes
2009-04-27 16:39:04CERTIFICATIONS WITH PICTURE I.D. REQUIRED FOR THE
 QUALIFER, THE BRAZER & THE INSTALLED AT THE TIME OF
 APPLICATION FOR MED-GAS FAC 61G4-15.031(1)(2)(A)(B) &
 FS 489.108, 489.1136.

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 10:21 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 09:50 Sent To  
Notes
2009-01-22 10:22:52DENIED
 REFERENCE:
 NFPA-99C
  
 1. SHT P-1 PLAN KEY NOTES NUMBER 8 IS NOT APPROVED.
 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER 4-5.2.2,
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND VENTED
 DRAIN. SECTION 405.2.1.3.
  
 2. ALL CENTRAL VACUUM (FLUID SUCTION) SYSTEMS. THE
 EXHAUSTS FROM A VACUUM PUMP SERVICE A VACUUM (FLUID
 SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR
 ABOVE THE ROOF. SECTION 713.6.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-27 Cont ID  
Sent By kstevens Date 2009-04-27 Time 16:34 Rev Time 0.00
Received By kstevens Date 2009-04-27 Time 16:34 Sent To  
Notes
2009-04-27 16:36:07PASSED/PROVISO
 WALLS SHALL COMPLY WITH SECTION 1210.2. -- 29 INCH
 CLEARANCE REQUIRED AT ACCESSIBLE LAV. SECTION
 11-4.19.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-01-22 Cont ID  
Sent By kstevens Date 2009-01-22 Time 09:50 Rev Time 0.00
Received By kstevens Date 2009-01-22 Time 09:50 Sent To  
Notes
2009-01-22 10:21:36DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 NFPA-99C
  
 1. SHT A-108 FINISH SCHEDULE INDICATES PAINTED WALLS
 FOR THE TOILET ROOM A-105. PER SECTION 1210.2 WALLS
 WITHIN 2 FEET OF THE WATER CLOSET SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE
 THE FLOOR. PAINTED SURFACES DOES NOT MEET THE HARD
 REQUIREMENT OF THIS CODE SECTION. PLEASE INDICATE
 METHOD OF COMPLIANCE.
  
 2. SHT A-108 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___LAV:
 A. 11-4.19.2 CLEARANCE HEIGHT
 B. 11-4.19.5 FAUCETS
  
 3. SHT P-1 PLAN KEY NOTES NUMBER 3 & NUMBER 4 INDICATES
 EXISTING 4" SANITARY LINE AND NUMBER 5 INDICATES 3/4"
 WATER LINE CONNECTING TO EXISTING. PLEASE CLARIFY AS
 THIS IS A NEW BUILDING. SECTIONS 106.1.1, 106.1 &
 107.1.
  
 4. SHOW THE LOCATION & INDICATE THE SIZE OF THE WATER
 SERVICE AND SHOW THE REQUIRED RPZV BACKFLOW AT THE
 METER. SECTIONS 603.1 & 608.13.2.
  
 5. SHT P-1 PLAN KEY NOTES NUMBER 8 IS NOT APPROVED.
 LIQUIDS FROM A LEVEL 3 VACUUM SYSTEM, PER 4-5.2.2,
 SHALL BE DIRECTLY CONNECTED TO THE SANITARY DRAINAGE
 SYSTEM THROUGH AN APPROPRIATELY TRAPPED AND VENTED
 DRAIN. SECTION 405.2.1.3.
  
 6. ALL CENTRAL VACUUM (FLUID SUCTION) SYSTEMS. THE
 EXHAUSTS FROM A VACUUM PUMP SERVICE A VACUUM (FLUID
 SUCTION) SYSTEM SHALL DISCHARGE SEPARATELY TO OPEN AIR
 ABOVE THE ROOF. SECTION 713.6.
  
 7. SHT P-2 THE SANITARY & DOMESTIC WATER RISER DIAGRAMS
 SHOW THE SYSTEMS CONNECTING TO EXISTING SYSTEMS. PLEASE
 CLARIFY AS THIS IS A NEW BUILDING. SECTIONS 106.1.1,
 106.1 & 107.1.
  
 8. SHT P-2 TANKLESS WATER HEATER DETAIL. FULL OPEN
 VALVES ARE REQUIRED ON THE WATER SUPPLY PIPE TO EVERY
 WATER HEATER. SECTION 606.1(7). PLEASE INDICATE VALVES
 ON DETAIL.
  
 9. SHT P-2 DOMESTIC WATER RISER DIAGRAM SHOWS A 1/2"
 WATER SUPPLY LINE TO THE VACUUM SYSTEM. THE WATER LINE
 SHALL BE PROVIDED WITH PROTECTION AGAINST BACKFLOW &
 CONTAMINATION OF THE WATER SUPPLY SYSTEM. SECTION
 608.3. PLEASE INDICATE METHOD. PLEASE SUBMIT MANUF.
 SPECIFICATIONS & INSTALLATION INSTRUCTIONS FOR THE
 VACUUM SYSTEM. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 10. THE ENERGY CALCULATIONS DO NOT INDICATE WATER
 HEATER - 3 NOR DOES IT INCLUDING THE REQUIRED PIPING
 INSULATION. CHAPTER 13 ENERGY EFFICIENCY
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2009-05-21 Cont ID  
Sent By kdfreema Date 2009-05-21 Time 10:19 Rev Time 0.00
Received By kdfreema Date 2009-05-21 Time 10:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-04-23 Cont ID  
Sent By kdfreema Date 2009-04-23 Time 14:32 Rev Time 0.00
Received By kdfreema Date 2009-04-23 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-12-02 Cont ID  
Sent By kdfreema Date 2008-12-02 Time 10:13 Rev Time 0.00
Received By kdfreema Date 2008-12-02 Time 10:13 Sent To  
Notes
2008-12-02 10:14:59***FAILED***
  
 FORMAL SITE PLAN REVIEW MUST BE APPROVED BEFORE ZONING
 CAN APPROVE THIS PERMIT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 OR [email protected] WITH QUESTIONS.