Plan Review Details - Permit 08110407
Plan Review Stops For Permit 08110407
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-12-17 Cont ID  
Sent By mgonzale Date 2008-12-17 Time 12:00 Rev Time 1.00
Received By mgonzale Date 2008-12-17 Time 11:32 Sent To ENG
Notes
2008-12-17 12:00:28***** PASSED WITH PROVISOS *****
  
 #1 PLANS DATED 11/20/08 REFLECT PIPING IN THE R.O.W.,
 THIS IS UNACCEPTABLE!
 #2 SEE PLANS DATED 11/20/08, I HAVE APPROVED AS
 REDLINED. PRIVATE PIPING (ON-SITE PIPING MUST STAY
 ON-SITE OR HUG PROPERTY LINE
 UNTIL POINT OF CONTACT WITH SEWER LATERAL TIE-IN. ONE
 CLEAN-OUT IS REQUIRED.
 #3 (PLUMBING PLAN REVIEW HAS BEEN ADVISED OF THE
 APPROVAL)
 #4 CLEAN-OUT MUST HAVE A RING AND COVER AS PER CITY OF
 WPB APPROVED MATERIAL LIST
 HTTP://WWW.CITYOFWPB.ORG/ENGINEERING/UPLOADS/2008-10-24
 -16-12-10-APPROVEDMATERIALSLIST10-24-08.PDF
 #5 RIGHT OF WAY PERMIT MUST BE UP TO DATE AND
 CONTRACTOR MUST CALL FOR INSPECTION PRIOR TO POURING
 CONCRETE.
 #6 PLUMBING INSPECTION OF PIPING AND ELEMENTS WITHIN
 PROXIMITY OF THE ROW MUST ALSO BE CALLED IN AND
 CLEARED.
 #7 SIDEWALK MUST MEET ADA ACCESABILITY STANDARDS AND
 SLOPE.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-11-20 Cont ID  
Sent By mgonzale Date 2008-11-20 Time 14:34 Rev Time 1.00
Received By mgonzale Date 2008-11-20 Time 14:34 Sent To ENG
Notes
2008-11-20 14:32:54- PASSED WITH PROVISOS -
  
 LOCATION OF THE GREASE TRAP IS ACCEPTABLE.
 CLEAN-OUT SHOULD BE PLACED WHERE IT IS NOT A
 TRIPPING HAZARD AND JUST OUTSIDE OF THE PROPERTY LINE.
 CONTACT ENGINEERING FINAL WALK THRU INSPECTION AND
 QUESTIONS.
 ROW PERMIT IS REQUIRED. ANY QUESTIONS CONTACT:
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR (561) 494-1040
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 CITY'S WEB SITEHAS ALL OUR REFERENCE MATERIAL YOU NEED
 TO COMPLY:
 FEEL FREE TO SEE THE LINKS BELOW:
 WWW.CITYOFWPB.ORG
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-12-16 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-12-16 Time 11:01 Sent To ENG
Notes
2008-12-16 11:01:50TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-16 Cont ID  
Sent By adarroug Date 2008-11-20 Time 11:00 Rev Time 0.00
Received By adarroug Date 2008-11-20 Time 11:19 Sent To  
Notes
2008-11-20 11:19:48TO "P" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved