Plan Review Details - Permit 08110321
Plan Review Stops For Permit 08110321
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-15 Cont ID  
Sent By mjacobs Date 2008-12-15 Time 10:04 Rev Time 0.00
Received By mjacobs Date 2008-12-11 Time 10:04 Sent To  
Notes
2008-12-11 10:04:43 
 BUILDING PLAN REVIEW
 PERMIT: 08110321
 ADD: 7600 S. DIXIE HWY
 CONT: LB ROWE INC.
 TEL: (561)835-1499
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 12/15-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
 2) OK
 3) OK
 4) OK
 5) OK
 6) OK
 7) OK
 8) OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-26 Cont ID  
Sent By mjacobs Date 2008-11-26 Time 13:40 Rev Time 0.00
Received By mjacobs Date 2008-11-26 Time 13:40 Sent To  
Notes
2008-11-26 13:40:47BUILDING PLAN REVIEW
 PERMIT: 08110321
 ADD: 7600 S. DIXIE HWY
 CONT: LB ROWE INC.
 TEL: (561)835-1499
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-26-08
 REVIEW: 1
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) THE DESCRIPTION ON THE APPLICATION DOES NOT MATCH
 THE PLANS. THE APPLICATION SHALL DESCRIBE THE PROJECT
 IN DETAIL SO THAT THE PLAN REVIEWERS MAY GET A BETTER
 UNDERSTANDING OF THE WORK INVOLVED WITH THE PROJECT. IF
 THE OCCUPANCY TYPE IS CHANGED, WHICH THE PLANS SHOW,
 PLEASE CHECK THE BOX ON THE APPLICATION.
  
 3) SHEET A-1.01 NOTE #16 STATE NEW FLOORING TRANSITION;
 PLEASE PROVIDE A CROSS SECTION DETAIL DRAWING OF THE
 FLOOR AREA WHERE THE TRANSITION TAKES PLACE. THE
 CHANGES IN LEVEL SHALL BE IN ACCORDANCE WITH FBC
 11-4.5.2. THE PLANS NEED TO INDICATE THE ACCESSIBLE
 PARKING AND ROUTE TO THE BUILDING. FBC 11-4.6.2
  
 4) SHEET A-0.00: THE LIFE SAFETY PLANS DOORS DO MEET
 THE REQUIREMENTS OF FBC 1041.2.1 WHICH STATES EXIT
 ACCESS DOORS SHALL BE PLACED A DISTANCE APART NOT LESS
 THAN ONE- HALF OF THE OVERALL DIAGONAL DIMENSION OF THE
 BUILDING AREA. THERE ARE OTHER EXIT DOORS SHOWN ON THE
 PLANS, HOWEVER, THE DRAWINGS DO NOT INDICATE IF THEY
 LEAD TO A PUBLIC WAY WHICH SHALL BE UN-OBSTRUCTED
 INCASE OF EMERGENCY.
  
 5) THE VALUE ON THE PERMIT APPLICATION IS LOW. THE
 VALUE SHALL BE THE TOTAL COST INCLUDING ELECTRIC,
 PLUMBING, INTERIOR FINISHES, ARCHITECTURAL DESIGN FEES,
 MARKETING COST AND OVERHEAD AND PROFIT. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND MEANS COST
 ANALYSIS SERVICES 108.3* PLEASE INDICATE A FAIR MARKET
 VALUE ON THE APPLICATION.
  
 6) FBC106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561)805-6726
 FAX (561) 805-6676
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-11-24 Cont ID  
Sent By btrobaug Date 2008-11-24 Time 14:26 Rev Time 0.00
Received By btrobaug Date 2008-11-24 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-11-24 Cont ID  
Sent By mwennerg Date 2008-11-24 Time 15:29 Rev Time 0.00
Received By mwennerg Date 2008-11-24 Time 15:29 Sent To  
Notes
2008-11-24 15:30:201) IN ADDITION TO ALL APPLICABLE CODES, CONSTRUCTION,
 ALTERATION AND DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM REMODEL IF APPLICABLE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-09 Cont ID  
Sent By adarroug Date 2008-12-09 Time 08:41 Rev Time 0.00
Received By adarroug Date 2008-12-09 Time 08:41 Sent To  
Notes
2008-12-09 08:47:30TO "BOB"#4
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 11:14 Sent To  
Notes
2008-11-20 08:48:53TO "BOB"#5
2008-11-18 11:17:54WAITING FOR "BOB"
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-16 Cont ID  
Sent By lwagner Date 2008-12-16 Time 15:04 Rev Time 0.00
Received By lwagner Date 2008-12-16 Time 15:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 16:25 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 16:24 Sent To  
Notes
2008-12-01 16:34:32DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. APPLICATION DOES NOT INCLUDE PLUMBING IN THE
 DESCRIPTION OF THE PROJECT. APPLICATION REQUIRES THAT
 APPLICANT DESCRIBES THE PROJECT IN DETAIL AND TO
 INDICATE IF THERE IS A CHANGE OF OCCUPANCY OR NOT.
 SECTION 106.1.2.
  
 2. THE SINK ADDED TO THE LOUNGE SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL & ELEVATION SHOWING COMPLIANCE
 WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
  
 3. SEE COMMENT 5 OF THE BUILDING PLAN REVIEW ABOUT THE
 VALUE OF THE PERMIT APPLICATION. SECTION 108.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-12-02 Cont ID  
Sent By eschneid Date 2008-12-02 Time 17:46 Rev Time 0.00
Received By eschneid Date 2008-12-02 Time 17:46 Sent To  
Notes
2008-12-02 17:47:28NOT REQ.
  
 INTERIOR RENOVATIONS UNDER 50% VALUE.