Plan Review Details - Permit 08110263
Plan Review Stops For Permit 08110263
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-03-04 Cont ID  
Sent By jwitmer Date 2009-03-04 Time 07:44 Rev Time 0.55
Received By jwitmer Date 2009-03-04 Time 07:44 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-03 Cont ID  
Sent By jwitmer Date 2009-02-03 Time 10:12 Rev Time 1.77
Received By jwitmer Date 2009-02-03 Time 10:12 Sent To  
Notes
2009-02-03 10:18:48BUILDING PLAN REVIEW
 PERMIT: 08110263
 ADD: 4631 N CONGRESS AV
 CONT: "PLAN REVIEW/
 TEL: (561)635-6935/ NAT HEALY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 TUESDAY FEB.03/2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) NEW COMMENT DOOR 102 IT APPEARS THE DIMENSION OF
 1'-0" IS MISLABELED, IT APPEARS TO BE THE CORRECT 1'-6"
 REQUIRED BY 11-4.13.6. NOTE THE FIRE EXTINGUISHER
 LOCATED NEXT TO THE DOOR MAY CAUSE AN ISSUE IF GREATER
 THAN 4" AWAY FROM THE WALL. 11-4.4 PROTRUDING OBJECTS.
  
 3) NEW COMMENT, DOOR # 113TO THE DATA CLOSET IS NOT IN
 COMPLIANCE WITH: 1008.1.8.8 DURING ITS SWING, ANY DOOR
 IN A MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST
 ONE HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE THAN 7 INCHES
 (178 MM) INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-12-10 Cont ID  
Sent By jwitmer Date 2008-12-10 Time 07:21 Rev Time 2.22
Received By jwitmer Date 2008-12-10 Time 07:21 Sent To  
Notes
2008-12-10 07:49:40BUILDING PLAN REVIEW
 PERMIT: 08110263
 ADD: 4631 N CONGRESS AV
 CONT: "PLAN REVIEW/
 TEL: (561)635-6935/ NAT HEALY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS NOT INCLUDING ALL
 AMENDMENTS.
  
 2) ENERGY CALCULATIONS PLEASE REVIEW 13-400.0.C.4
 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
  
 RENOVATION. ANY STRUCTURAL REPAIR, RECONSTRUCTION OR
 RESTORATION TO A STRUCTURE, THE COSTS OF WHICH EQUALS
 OR EXCEEDS, OVER A ONE-YEAR PERIOD, A CUMULATIVE TOTAL
 OF 30 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE
 WHEN THAT VALUE IS ASSESSED, EITHER:
 1. BEFORE THE IMPROVEMENT OR REPAIR IS STARTED; OR
 2. BEFORE THE DAMAGE OCCURRED, IF THE STRUCTURE HAS
 BEEN DAMAGED.
 FOR THE PURPOSES OF THIS CODE, RENOVATION OCCURS WHEN
 THE FIRST ALTERATION OF ANY WALL, CEILING, FLOOR, OR
 OTHER STRUCTURAL PART OR MECHANICAL SYSTEM OF THE
 BUILDING COMMENCES, WHETHER OR NOT THAT ALTERATION
 AFFECTS THE EXTERNAL DIMENSIONS OF THE STRUCTURE.
  
 WITH THIS ONLY BEING A PLAN REVIEW AND NOT A PERMIT
 APPLICATION IT APPEARS THE WORK TO BE COVERED UNDER
 THIS PERMIT WILL NOT MEET THE 30% OF THE VALUE OF THE
 BUILDING, REQUIRING FORM 400 C, ONCE THE VALUE IS KNOWN
 WE WILL HAVE THE CRITERIA TO ASSESS WHICH METHOD B OR C
 SHOULD HAVE BEEN USED.
  
 3) SHEET A-1 DOES NOT INDICATE WHAT AREAS ARE ALREADY
 THERE AND WHAT IS TO BE CONSIDERED NEW WORK. ADDITIONAL
 INFORMATION REQUIRED 106.1.2.
  
 4) SHEET A-3 DETAIL 4 & 5 BOTH INDICATE SOFFIT DETAILS
 BUT DO NOT PROVIDE WHAT TYPE OF ATTACHMENT METHOD WILL
 BE USED TO INSTALL SOFFITS TO DECK ABOVE? 2508.1, TABLE
 2508.1 & GA-216.
  
 5) SHEET A-4 INDICATES WALL ASSEMBLIES FOR RATED WALLS
 BUT DOES NOT PROVIDE FLOOR PENETRATIONS FOR HORIZONTAL
 ASSEMBLIES. 712.4.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-03-02 Cont ID  
Sent By dpalmer Date 2009-03-02 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2009-03-02 Time 17:24 Sent To  
Notes
2009-03-02 17:24:35*** REDLINED PLANS***
  
 *NOTE: E-1 WAS REVISED FOR HEIGHTS OF DEVICES FOR ADA
 COMPLIANCE ALONG WITH PULL STATIONS HOWEVER THE MINIMUM
 CANDELA LEVELS AS NOTED IN PREVIOUS REVIEWS WERE NOT
 INDICATED.
 THE MINIMUM CD LEVEL IS 75 PER FBC 11-4.28.3(4).
 REDLINED ON SHEET E-1. PLANS STAMPED OK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-09 Cont ID  
Sent By dpalmer Date 2009-02-09 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2009-02-09 Time 17:14 Sent To  
Notes
2009-02-09 17:15:03** DENIED **
  
 ** PLANS ARE COMING BACK FOR SOME OTHER COMMENTS.
 PLEASE SEE COMMENT BELOW.
  
 1) NOTE: ON THE PREVIOUS REVIEW A REQUEST FOR ANY HORN
 AND STROBE DEVICES NEED TO BE SHOWN ON PLANS. DEVICES
 HEIGHTS AND LEVELS NEED TO BE SHOWN ON PLANS.
 RESPONSE MENTIONS THIS WILL BE UNDER SEPARATE PERMITS
 HOWEVER ANY REQUIRED SYSTEMS PER FS 633 MUST BE SHOWN
 ON BASE BUILDING PLANS FOR BASE CODE COMPLIANCE.
 ANY SEPARATE PERMITS WILL ALSO BE DONE AT A LATER DATE.
 CALLED ARCHITECT TO CLARIFY.
 FBC 11-4.28.1, .2 AND .3.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-12-03 Cont ID  
Sent By dpalmer Date 2008-12-03 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2008-12-03 Time 08:40 Sent To  
Notes
2008-12-03 08:40:59 
 ** DENIED REVIEW**
  
  
  
 1) NOTE: PLANS SUBMITTED FOR PLAN REVIEW ONLY. EVEN
 ONCE ALL ITEMS FOR CODE COMPLIANCE ARE MET AND PERMIT
 APPLICATION HAS NOT BEEN MADE REVIEW WILL REMAIN IN
 FAILED STATUS. ITEMS SUCH AS LICENSING, CODES ETC ARE
 REVIEWED AT TIME OF APPLICATION.
  
 2) NOTE: PLEASE BE SURE THE RELEVANT CODES ARE
 ADJUSTED. CODES ON THE COVER SHEET COMPARED TO
 ELECTRICAL PLANS FOR EXAMPLES ARE NOT THE SAME.
 PLEASE SEE COVER SHEET WHICH SHOULD REFLECT 2004 FBC W/
 2007 REVISIONS.
 PLEASE SEE COVER SHEET WHICH SHOULD REFLECT THE 2005
 NFPA-70 (NATIONAL ELECTRICAL CODE) PLANS SHOW 2002.
 LIFE SAFETY SHEET DOES CONTAIN THE CORRECT 2005 NEC
 HOWEVER ELECTRICAL PLANS STATE *LATEST*.
 PLEASE ADJUST ALL SHEETS AS APPLICABLE.
  
 3) NOTE: PLEASE SEE FBC 13-101.1.3 AND SECTION 202 FOR
 DEFINITIONS. PLEASE EXPLAIN HOW FLA-COM FORM *B* BE
 USED. PLEASE KNOW BASED ON DEFINITIONS, PLANS
 SUBMITTED, NO PERMIT APPLICATION FOR VALUE THE METHOD
 *B* MAY NOT BE USED.
 PLEASE SEE 13-400.C FOR EXAMPLE WHICH MENTIONS WHEN NOT
 MEETING THE DEFINITION OF A RENOVATED BUILDING, BASIC
 PRESCRIPTIVE REQUIREMENTS MUST BE MET.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 TABLES 13-415.2.B, OR 13-415.2.C. PLEASE CALL TO GO
 OVER AS SOME INFORMATION ON E3 IS SHOWN.
  
 4) NOTE: PLEASE SEE FBC 11-4.27.4 AS THE TIMER TYPE
 DEVICES AS SHOWN ARE NOT PERMITTED TO BE THE TYPE WHICH
 WOULD REQUIRE TWISTING ACTION ETC. PLEASE SEE SECTION
 GIVEN AS ALL CONTROLS FOR LIGHTING ETC NEED TO MEET ADA
 REQUIREMENTS.
 PLEASE ADJUST NOTES AND SPECIFICS FOR DEVICES.
  
 5) NOTE: PLEASE PROVIDE WALL/FLOOR PENETRATION DETAILS
 FOR LISTED WALL ASSEMBLIES. 300.21. PLEASE SEE
 COMMENTARY IN NEC HANDBOOK WHICH WILL REFERENCE
 ACCEPTABLE STANDARDS.
 IF THE SAME DETAILS ON A4 ARE TO BE USED PLEASE MAKE
 NOTE ON ELECTRICAL PLANS REFERENCING TO THIS SHEET.
  
 6) NOTE: PLEASE CLARIFY THE SECTION ON E3 SHOWN AS
 *DEMAND LOAD* WHICH SHOWS EXISTING FEEDERS AS 4-
 500MCM. WHAT FEEDERS ARE THESE AS THE NEW FEEDERS ON
 RISER FROM GUTTER ARE NOT THE SAME.
  
 7) NOTE: PLEASE NOTE A *FLOATING NEUTRAL KIT* REQUIRED
 AT THE TENANT METER. 250.6,250.24 ETC.
  
 8) NOTE: PLEASE SHOW ANY NEW OR EXISTING FIRE ALARM
 DEVICES. PLEASE BE SURE TO SEE FBC 11-4.28.1,.2 AND .3
 FOR MINIMUM LEVELS FOR ADA COMPLIANCE.
 (IF APPLICABLE IN THIS BUILDING).
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-03-04 Cont ID  
Sent By mwennerg Date 2009-03-04 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2009-03-04 Time 13:29 Sent To  
Notes
2009-03-04 13:30:49***PROVISO***
  
 SWING OF THE DOOR TO THE DATA ROOM WAS CORRECTED ON
 A-SHEETS ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-02-18 Cont ID  
Sent By mwennerg Date 2009-02-18 Time 12:36 Rev Time 0.00
Received By mwennerg Date 2009-02-18 Time 12:36 Sent To  
Notes
2009-02-18 12:37:46***DENIED***
  
  
 1) THE DOOR TO DATA ROOM 113 SEEMS TO EXTEND GREATER
 THAN 1/2 THE WIDTH OF THE CORRIDOR. SEE NFPA 101,
 SEC.7.2.1.4.4.
  
  
 PLANS WILL REMAIN IN FAILED STATUS UNTIL SUBMITTED AND
 APPROVED FOR PERMIT REVIEW.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-11 Cont ID  
Sent By mwennerg Date 2008-12-11 Time 13:55 Rev Time 0.00
Received By mwennerg Date 2008-12-11 Time 13:55 Sent To  
Notes
2008-12-11 14:04:35PLANS APPEAR TO BE CODE COMPLIANT HOWEVER PLEASE SEE
 THE FOLLOWING:
  
 1) TITLE SHEET INDICATES THAT PROJECT IS PROTECTED BY
 AN AUTOMATIC FIRE SPRINKLER SYSTEM. WHEN PLANS ARE
 SUBMITTED FOR PERMIT REVIEW, PLEASE SHOW THE FIRE
 SPRINKLER LAYOUT. THIS CAN BE ILLUSTRATED ON THE
 REFLECTED CEILING PLAN. IN ADDITION, SEPARATE SHOP
 DRAWINGS AND PERMIT WILL BE REQUIRED FOR FIRE SPRINKLER
 REMODEL.
  
 2) THE DOOR TO DATA ROOM 113 SEEMS TO EXTEND GREATER
 THAN 1/2 THE WIDTH OF THE CORRIDOR. SEE NFPA 101,
 SEC.7.2.1.4.4.
  
  
 PLANS WILL REMAIN IN FAILED STATUS UNTIL SUBMITTED AND
 APPROVED FOR PERMIT REVIEW.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-02 Cont ID  
Sent By adarroug Date 2009-03-02 Time 16:29 Rev Time 0.00
Received By adarroug Date 2009-03-02 Time 16:29 Sent To  
Notes
2009-03-02 16:34:27TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 16:20 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 16:20 Sent To  
Notes
2009-01-21 16:22:48TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 10:23 Rev Time 0.00
Received By kstevens Date 2008-11-14 Time 13:59 Sent To  
Notes
2008-11-14 14:00:31TO "COMM" BD#57

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-20 Cont ID  
Sent By rregueir Date 2009-02-20 Time 09:43 Rev Time 0.00
Received By rregueir Date 2009-02-20 Time 09:43 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-12-06 Cont ID  
Sent By rregueir Date 2008-12-06 Time 12:52 Rev Time 0.00
Received By rregueir Date 2008-12-06 Time 12:36 Sent To  
Notes
2008-12-06 12:52:03REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: P/F
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN REVIEWED FOR COMPLIANCE AND PASSED.
 HOWEVER, PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN
 REVIEW. NO PERMIT APPLICATION HAS BEEN SUBMITTED. PLANS
 WILL REMIAN IN FAILED STATUS PENDING SUBMISSION OF
 PERMIT APPLICATION.
  
 NOTE: ENERGY CALCULATIONS WERE NOT REVIEWED FOR CODE
 COMPLIANCE. IT IS NOT CLEAR AT THIS TIME WHETHER THIS
 WORK QUALIFIES AS A "RENOVATION" AS DEFINED IN FBCB
 13-202. IF THIS PROJECT IS NOT A RENOVATION UNDER THIS
 DEFINITION, SEE FBCB 13-101.6 BELOW FOR MINIMUM
 REQUIREMENTS. ENOUGH INFORMATION HAS BEEN PROVIDED ON
 PLANS TO DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS
 OF FBCB 13-101.6. THEREFORE, NO ENERGY OR COOLING LOAD
 CALCULATIONS ARE REQUIRED.
  
 13-101.6 BUILDING SYSTEMS.
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS WHERE NEW PRODUCTS ARE INSTALLED OR
 REPLACED IN EXISTING BUILDINGS, AND FOR WHICH A PERMIT
 MUST BE OBTAINED. SUCH SYSTEMS SHALL MEET THE MINIMUM
 EFFICIENCIES ALLOWED FOR THAT SYSTEM ON FORM 400C FOR
 COMMERCIAL BUILDINGS AND ON FORM 600C FOR RESIDENTIAL
 BUILDINGS.
 1. HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS;
 2. SERVICE WATER OR POOL HEATING SYSTEMS;
 3. ELECTRICAL SYSTEMS AND MOTORS;
 4. LIGHTING SYSTEMS.
 EXCEPTIONS:
 1. WHERE PART OF A FUNCTIONAL UNIT IS REPAIRED OR
 REPLACED. FOR EXAMPLE, REPLACEMENT OF AN ENTIRE HVAC
 SYSTEM IS NOT REQUIRED BECAUSE A NEW COMPRESSOR OR
 OTHER PART DOES NOT MEET CODE WHEN INSTALLED WITH AN
 OLDER SYSTEM.
 2. WHERE EXISTING COMPONENTS ARE UTILIZED WITH A
 REPLACEMENT SYSTEM, SUCH AS AIR DISTRIBUTION SYSTEM
 DUCTS OR ELECTRICAL WIRING FOR LIGHTS, SUCH COMPONENTS
 OR CONTROLS NEED NOT MEET CODE IF MEETING CODE WOULD
 REQUIRE THAT COMPONENT?S REPLACEMENT.
 3. REPLACEMENT EQUIPMENT THAT WOULD REQUIRE EXTENSIVE
 REVISIONS TO OTHER SYSTEMS, EQUIPMENT OR ELEMENTS OF A
 BUILDING WHERE SUCH REPLACEMENT IS A LIKE-FOR-LIKE
 REPLACEMENT, SUCH AS THROUGH-THE-WALL CONDENSING UNITS
 AND PTACS, CHILLERS, AND COOLING TOWERS IN CONFINED
 SPACES.
 4. HVAC EQUIPMENT SIZING CALCULATIONS ARE NOT REQUIRED
 FOR SYSTEMS INSTALLED IN EXISTING BUILDINGS NOT MEETING
 THE DEFINITION OF RENOVATION IN SECTION 202.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-02 Cont ID  
Sent By kstevens Date 2009-03-02 Time 18:08 Rev Time 0.00
Received By kstevens Date 2009-03-02 Time 18:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-02-20 Cont ID  
Sent By kstevens Date 2009-02-20 Time 10:26 Rev Time 0.00
Received By kstevens Date 2009-02-20 Time 10:26 Sent To  
Notes
2009-02-20 10:29:41DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY:
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT A.5 SHOW COMPLIANCE WITH SECTION 11-4.24.3 KNEE
 CLEARANCE (27" REQD), AND 11-4.24.6 EXPOSED PIPES &
 SURFACES.
 ****RESPONSE NOTED, BUT SECTION 1-4.24.6 NOT ADDRESSED.
  
 3. SHT P.1 THE SANITARY AND TRAP ARE NOT SHOWN AT THE
 SINK IN ROOM 121. PLEASE CLARIFY SECTIONS 106.1.1,
 701.1 & 1002.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PIPING
 AND TRAP STILL NOT SHOWN AT THE SINK. THE PIPING AND
 TRAP ARE SHOWN OUTSIDE THE CABINET.
  
 4. OK
 5. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-18 Cont ID  
Sent By kstevens Date 2008-12-18 Time 09:56 Rev Time 0.00
Received By kstevens Date 2008-12-17 Time 16:57 Sent To  
Notes
2008-12-18 10:19:51DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 PLAN REVIEW ONLY:
  
 1. SHT A.3 SHOW COMPLIANCE WITH SECTION 11-4.16.5 FLUSH
 CONTROLS.
  
 2. SHT A.5 SHOW COMPLIANCE WITH SECTION 11-4.24.3 KNEE
 CLEARANCE (27" REQD), AND 11-4.24.6 EXPOSED PIPES &
 SURFACES.
  
 3. SHT P.1 THE SANITARY AND TRAP ARE NOT SHOWN AT THE
 SINK IN ROOM 121. PLEASE CLARIFY SECTIONS 106.1.1,
 701.1 & 1002.1.
  
 4. SHTS T.1 & LS.1 PLEASE INDICATE 2007 REVISIONS WITH
 THE FBC-2004 IN THE CODE SUMMARY.
  
 5. SHT P.3 PLEASE INDICATE THE REQUIRED INSULATION FOR
 THE HOT WATER PIPING WITH A NOTE ON THE WATER RISER
 DIAGRAM AS INDICATED IN THE INPUT DATA REPORT SHT 9 FOR
 THE PIPING. CHAPTER 13.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status N Date 2009-01-27 Cont ID  
Sent By eschneid Date 2009-01-27 Time 14:32 Rev Time 0.25
Received By eschneid Date 2009-01-27 Time 14:32 Sent To  
Notes
2009-01-27 14:33:31INTERIOR WORK ONLY.
  
 IF WORK EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, THEN
 A LANDSCAPE PLAN IS REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-19 Cont ID  
Sent By eschneid Date 2008-11-19 Time 11:53 Rev Time 0.00
Received By eschneid Date 2008-11-19 Time 11:19 Sent To  
Notes
2008-11-19 11:56:19PLEASE NOTE THAT IF THE FINAL PERMIT VALUE EXCEEDS 50%
 OF THE ASSESSED VALUE OF THE BUILDING, THEN A LANDSCAPE
 PLAN SHOWING COMPLIANCE WITH THE LANDSCAPE CODE IS
 REQUIRED.
  
 OTHERWISE, COMPLIES WITH ZONING REQ.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.