Plan Review Details - Permit 08110241
Plan Review Stops For Permit 08110241
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 15:36 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 15:36 Sent To  
Notes
2008-12-01 15:46:40PASSED PROVISO -- MAKEUP AIR REQUIREMENTS PER SECTION
 304.4.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By kstevens Date 2008-11-18 Time 13:33 Rev Time 0.00
Received By kstevens Date 2008-11-18 Time 13:33 Sent To  
Notes
2008-11-18 13:44:19DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3. (NOTE: THE PRINTED NAME AND DATE
 ARE NOT INDICATED.)
  
 3. PER FBC MECHANICAL, SECTION 303.9.4 PROTECTION FROM
 DAMAGE. APPLIANCES (WATER HATERE IN GARAGE) SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS. (CAN BE
 PROVISO'D).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  