Plan Review Details - Permit 08110113
Plan Review Stops For Permit 08110113
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By jwitmer Date 2008-12-02 Time 08:56 Rev Time 0.88
Received By jwitmer Date 2008-12-02 Time 08:56 Sent To  
Notes
2008-12-02 09:00:13BUILDING PLAN REVIEW
 PERMIT: 08110113
 ADD: 4801 DRREHER TRAIL N
 CONT BELLA CONSTRUCTION ? JEFF BERKOFF
 TEL: (561)722-6402
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION:REVIEWED
  
 1) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO
 MEET THE PROVISIONS OF THE TECHNICAL CODE.
  
 2) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 3) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED.
 FLOOD ZONE A7 BASE FLOOD 12'-6".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-13 Cont ID  
Sent By jwitmer Date 2008-11-13 Time 13:36 Rev Time 2.22
Received By jwitmer Date 2008-11-13 Time 13:36 Sent To  
Notes
2008-11-13 13:41:22BUILDING PLAN REVIEW
 PERMIT: 08110113
 ADD: 4801 DRREHER TRAIL N
 CONT:"PLAN REVIEW/ MAJOR WORKING DRAWING REVIEW"
 TEL: (561)319-7831
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) THE PERMIT APPLICATION READS UNDER DESCRIPTION OF
 WORK A 10,000 SQUARE FOOT SLAB. IS THIS TO BE FOR A
 SLAB OR A MONOLITHIC FOUNDATION?
  
 1C) UNDER THE HEADING ON THE PERMIT APPLICATION
 "DESCRIBE PROJECT IN DETAIL" PLEASE INDICATE IF THE
 STRUCTURE THAT WILL BE ERECTED ON THE MONOLITHIC
 FOUNDATION IF THIS STRUCTURE WILL BE TEMPORARY
 (LESS THAN 180DAYS) OR PERMANANT.
  
 3103.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL APPLY TO
 STRUCTURES ERECTED FOR A PERIOD OF LESS THAN 180 DAYS.
 TENTS AND OTHER MEMBRANE STRUCTURES ERECTED FOR A
 PERIOD OF LESS THAN 180 DAYS SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE. THOSE ERECTED FOR A
 LONGER PERIOD OF TIME SHALL COMPLY WITH APPLICABLE
 SECTIONS OF THIS CODE. SECTION 3105.5 RIGID AWNINGS AND
 CANOPY SHUTTERS HAVE DESIGN PRESSURES FOR THERE FRAMES
 BASED ON A BASIC WIND SPEED OF 90 MPH, TENTS DO NOT
 HAVE THIS DERATING OF WIND VALUES. PLEASE REVIEW
 FOUNDATION CALCULATION FOR 140 MPH/ 3 SECOND GUST.
  
 1D) SHEET S-1 UNDER WIND LOADS INDICATES THAT THE
 STRUCTURE IS DESIGNED FOR 90 MPH WIND SPEED, OUR
 JURISDICTION IS LOCATED WITHIN A 140 MPH WIND ZONE, 3
 SECOND GUST, PLEASE SEE FIGURE 1609.
 THIS WILL EFFECT THE STRUCTURAL MONOLITHIC FOUNDATION
 IF IT IS DESIGNED TO ONLY 90 MPH, PLEASE REVISE TO 140
 MPH WIND ZONE.
  
 1E) PLEASE PROVIDE THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
  
 1F) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601 , ASSUMED PROPERTY LINE BETWEEN BUILDINGS,
 TABLE 602 & TABLE 704.8.
  
 1G) THE OCCUPANT LOAD, SEE 1004.
  
 1H) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
  
 1I) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO
 MEET THE PROVISIONS OF THE TECHNICAL CODE.
  
 4) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUIULDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED.
 FLOOD ZONE A7 BASE FLOOD 12'-6".
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2008-12-08 Cont ID  
Sent By btrobaug Date 2008-12-08 Time 14:12 Rev Time 0.00
Received By btrobaug Date 2008-12-08 Time 14:12 Sent To PC
Notes
2008-12-08 14:15:50 
  
  
 ELECTRICAL GROUNDING ON PERMIT #08120118./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-12-02 Cont ID  
Sent By dpalmer Date 2008-12-02 Time 14:11 Rev Time 0.00
Received By dpalmer Date 2008-12-02 Time 14:11 Sent To  
Notes
2008-12-02 14:31:00**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW.
 FOUNDATION GROUNDING ELECTRODE SYSTEM IS REQUIRED AS
 THERE WILL BE ELECTRICAL EQUIPMENT, LIGHTING ETC INSIDE
 THE TENT STRUCTURE.
 250.50, 250.66

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-17 Cont ID  
Sent By dpalmer Date 2008-11-17 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2008-11-17 Time 11:38 Sent To  
Notes
2008-11-17 11:39:15 
  
  
 ** FAILED REVIEW **
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR * PLAN
 REVIEW* AND HAVE NOT BEEN SUBMITTED FOR PERMIT
 APPLICATION.
 AS THE PLANS SUBMITTED ARE FOR REVIEW OF SLAB ONLY
 PLEASE BE AWARE OF COMMENTS BELOW AND FROM OTHER
 TRADES. THE FUTURE WILL NEED PLANS SHOWING ALL
 ELECTRICAL AND LIGHTING AS NOTED BELOW.
  
 2) NOTE: PLEASE SUBMIT A PLANS SHOWING THE LIFE SAFETY
 REQUIREMENTS FOR LIGHTING FOR EGRESS UNDER NORMAL AND
 EMERGENCY CONDITIONS. PLEASE SEE NFPA-101 2003 , 7.8
 AND 7.9.
 PLEASE SEE NEC 700.12F FOR CIRCUITING.
 **
  
 3) NOTE: PLEASE SUBMIT A DETAIL FOR GROUNDING ELECTRODE
 SYSTEM AS REQUIRED PER 250.50 FOR ELECTRICAL SERVICE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-12-04 Cont ID  
Sent By mgonzale Date 2008-12-04 Time 13:48 Rev Time 1.00
Received By mgonzale Date 2008-12-04 Time 13:48 Sent To ENG
Notes
2008-12-04 13:50:40ENGINEERING REVIEW - PASSED
  
 CONTRACTOR HAS PROVIDED ANSWERS TO THE PREVIOUS
 COMMENTS.
 HE HAS INCLUDED PERTINENT INFORMATION AND SUBMITTED TO
 ENGINEERING SERVICES.
  
 CALL:
 MANNY GONZALEZ
 PROJECT COORDINATOR
 AT 561 494-1040
 TO SCHEDULE A PRECONSTRUCTION MEETING.
 THANKS
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-12-03 Cont ID  
Sent By mgonzale Date 2008-12-03 Time 13:23 Rev Time 1.00
Received By mgonzale Date 2008-12-03 Time   Sent To ENG
Notes
2008-12-03 13:23:10ENGINEERING REVIEW - FAILED 12/03/08
  
 PLEASE RESUBMIT WITH THE FOLLOWING:
  
 TEMPORARY 10000SF STRUCTURE WITH SLAB MAY IMPACT
 PROPERTY PERVIOUS AND IMPERVIOUS CALCULATIONS.
 PLEASE CONFIRM THAT A SFWMD PERMIT MODIFICATION IS NOT
 REQUIRED. THE TENT IS TEMP STRUCTURE (180 DAYS MAX.)
 HOWEVER THE SLAB/FOOTINGS WILL REMAIN.
  
 TYPE OF CONCRETE AND IT'S PERMEABILITY. THE USE OF
 VARIOUS PERVIOUS PAVEMENT ALTERNATIVES ARE AVAILABLE TO
 DECREASE THE VOLUME OF RUNOFF AND REDUCE THE VOLUME OF
 POLLUTANTS BY ALLOWING INITIAL INFILTRATION AT THE
 RUNOFF SOURCE. PERVIOUS CONCRETE OR CONCRETE PAVER
 BLOCKS CAN BE CONSIDERED FOR THE PROJECT AS AN
 ALTERNATE PAVING MATERIAL.
  
 WATER SURFACE CALCULATIONS. PERVIOUS IMPERVIOUS CALC.
 BMP'S MUST BE IN PLACE IF FILL IS BROUGHT IN OR ANY
 SOIL IS DISTURBED.
 WHERE WILL STORM RUN-OFF GO? WET DETENTION OR DRY
 DETENTION AREAS IDENTIFIED.
 WATER QUALITY CRITERIA THAT YOU WILL FOLLOW.
 STATE ANY OFF-SITE DISCHARGE.
  
  
 COMMENTS CONCERNING POLLUTION CONTROL:
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18), CHAPTER 90 UTILITIES,
 ARTICLE V. STORMWATER POLLUTION PREVENTION
 SEC. 90-203. PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS.
 (A) GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES
  PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 DIRECTLY OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR
 DUMP INTO
  ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM
 SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER
  THAN THAT COMPOSED ENTIRELY OF STORMWATER.
 PER; CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18), CHAPTER 90
 UTILITIES, ARTICLE V. STORMWATER POLLUTION PREVENTION,
 SEC. 90-203. PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS. (A) GENERAL PROHIBITION. EXCEPT AS
 PROVIDED IN SECTION 90-205, AND EXCEPT PURSUANT TO A
 VALID NPDES PERMIT, IT SHALL BE UNLAWFUL FOR ANY PERSON
 TO DIRECTLY OR INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR
 DUMP INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL
 SEPARATE STORM SEWER SYSTEM WITHIN THE CITY, ANY
 SUBSTANCE OTHER THAN THAT COMPOSED ENTIRELY OF
 STORMWATER. SUPPLY A POLLUTION CONTROL PLAN WITH A
 MINIMUM OF THE FOLLOWING INFORMATION;
 A) SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO
 BE DISTURBED. SHOW WHERE SILT SCREENS WILL BE INSTALLED
 B) FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN
 GRATES WITH ROCK BAGS AT ANY CURBED INLET ON-SITE TO
 STOP SOLIDS FROM ENTERING THE SYSTEM. SHOW THE
 PROTECTION OF ALL ON-SITE CATCH BASINS, SHOW PROTECTION
 OF ALL OFF-SITE CATCH BASINS, INCLUDE DETAILS AS TO THE
 TYPE OF PROTECTION USED ON AND OFF-SITE FOR THE CATCH
 BASINS, SUCH AS FILTER FABRIC IS REQUIRED UNDER THE
 CATCH BASIN GRATES WITH ROCK BAGS AT ANY CURBED INLET
 TO STOP SOLIDS FROM ENTER THE SYSTEM.
 C) ADD TURBIDITY BARRIER AT THE OUTFALLS AND ALONG THE
 FULL WIDTH OF THE PROJECT, SHOW WHERE SILT SCREENS WILL
 BE INSTALLED, HOW THEY WILL BE TIED DOWN AND
 MAINTAINED.
 D) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS.
 E) DETAIL HOW AND WHEN ANY CLEAN-UP WILL BE PREFORMED.
  
 GENERAL SFWMD RETENTION/DETENTION REQUIREMENTS
 1. VOLUME IS CALCULATED AS:
 WET DETENTION VOLUME SHALL BE PROVIDED FOR THE FIRST
 INCH OF RUNOFF FROM THE DEVELOPED PROJECT, OR THE TOTAL
 RUNOFF OF 2.5-INCHES TIMES THE PERCENTAGE OF
 IMPERVIOUSNESS, WHICHEVER IS GREATER, B) DRY DETENTION
 VOLUME SHALL BE PROVIDED EQUAL TO 75% OF THE ABOVE
 AMOUNTS COMPUTED FOR WET DETENTION.
  
 A) COMMERCIAL OR INDUSTRIAL ZONED PROJECTS SHALL
 PROVIDE AT LEAST ONE HALF INCH OF DRY DETENTION OR
 RETENTION PRETREATMENT AS PART OF THE REQUIRED
 RETENTION/DETENTION, UNLESS REASONABLE ASSURANCES CAN
 BE OFFERED THAT HAZARDOUS MATERIALS WILL NOT ENTER THE
 PROJECT?S SURFACE WATER MANAGEMENT SYSTEM. B) PROJECTS
 HAVING GREATER THAN 40% IMPERVIOUS AREA AND WHICH
 DISCHARGE DIRECTLY IN TO SPECIFIC RECEIVING WATERS AS
 OUTLINED IN SECTION 5.2.2, VOLUME IV, SHALL PROVIDE AT
 LEAST ONE HALF INCH OF DRY DETENTION OR RETENTION
 PRETREATMENT AS PART OF THE REQUIRED
 RETENTION/DETENTION. C) WATER SURFACE AND ROOFED AREAS
 CAN BE DEDUCTED FROM SITE AREAS ONLY FOR WATER QUALITY
 PERVIOUS/IMPERVIOUS CALCULATIONS. THE WATER SURFACE
 AREA MEETING DIMENSIONAL CRITERIA MAY ALSO BE
 SUBTRACTED FROM THE TOTAL SITE AREA WHEN MAKING FINAL
 WATER QUALITY TREATMENT VOLUME CALCULATIONS. D) IN
 CASES OF WIDENING EXISTING URBAN PUBLIC HIGHWAY
 PROJECTS, THE DISTRICT SHALL REDUCE THE WATER QUALITY
 REQUIREMENTS, IF THE APPLICANT PROVIDES DOCUMENTATION
 WHICH DEMONSTRATES THAT ALL REASONABLE DESIGN
 ALTERNATIVES HAVE BEEN CONSIDERED, AND WHICH PROVIDES
 EVIDENCE THAT THE ALTERNATIVES ARE ALL
 COST-PROHIBITIVE. E) PROJECTS WITHIN CONES OF
 DEPRESSION ? RETENTION/DETENTION AREA LOCATIONS SHALL
 NOT REDUCE HYDRAULIC RECHARGE DISTANCES TO PUBLIC WATER
 SUPPLY WELLS IN EXCESS OF 2%, NOR SHALL WET
 RETENTION/DETENTION AREAS BE CLOSER TO PUBLIC WATER
 SUPPLY WELLS THAN 300 FEET.
  
 IMPERVIOUS AREAS:
 RUNOFF SHALL BE DISCHARGED FROM IMPERVIOUS SURFACES
 THROUGH RETENTION AREAS, DETENTION DEVICES, FILTERING
 AND CLEANSING DEVICES, OR SUBJECT TO SOME OTHER TYPE OF
 BEST MANAGEMENT PRACTICE (BMP) PRIOR TO DISCHARGE FROM
 THE PROJECT SITE. PROJECTS WHICH INCLUDE SUBSTANTIAL
 PAVED AREAS, SUCH AS, SHOPPING CENTERS, LARGE HIGHWAY
 INTERSECTIONS WITH FREQUENT STOPPED TRAFFIC, AND HIGH
 DENSITY DEVELOPMENTS, PROVISIONS SHALL BE MADE FOR THE
 REMOVAL OF OIL, GREASE, AND SEDIMENT FROM STORMWATER
 DISCHARGES.
 _______________________________________________________
 __________________________________
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18), CHAPTER 94 ZONING AND LAND
 DEVELOPMENT REGULATIONS
 ARTICLE XIV. LANDSCAPING, LAND CLEARING, AND TREE
 PROTECTION
 SEC. 94-450. VACANT LOT AND CONSTRUCTION SITE
 MAINTENANCE.
 (A) INTENT. THE INTENT OF THIS SECTION IS TO MINIMIZE
 THE DETRIMENTAL HEALTH, SAFETY, GENERAL WELFARE AND
  IMPACTS OF VACANT
  LOTS AND CONSTRUCTION ACTIVITIES ON THE RESIDENTS OF
 THE CITY OF WEST PALM BEACH; TO ENSURE THAT EACH VACANT
 LOT AND
  CONSTRUCTION SITE IS MAINTAINED, AND EACH CONSTRUCTION
 ACTIVITY IS CONDUCTED IN SUCH A MANNER SO AS TO AVOID
  UNNECESSARY INCONVENIENCE AND ANNOYANCE TO THE GENERAL
 PUBLIC AND THE OCCUPANTS OF THE NEIGHBORING PROPERTIES;
  AND TO REQUIRE MAINTENANCE PRACTICES THAT WILL REDUCE
 THE AMOUNT OF SEDIMENT AND OTHER POLLUTANTS LEAVING
  CONSTRUCTION SITES DURING LAND DEVELOPMENT OR LAND
 DISTURBING CONSTRUCTION ACTIVITIES.
 _______________________________________________________
 __________________________________
  
 - NO POLLUTION CONTROL PLAN SUBMITTED OR SUBMITTED WITH
 OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
 -SUPPLY A POLLUTION CONTROL PLAN WITH A MINIMUM OF THE
 FOLLOWING INFORMATION;
 A) SILT FENCE NEEDS TO BE INSTALLED AROUND ANY AREAS TO
 BE DISTURBED. SHOW WHERE SILT SCREENS WILL BE INSTALLED
 B) FILTER FABRIC IS REQUIRED UNDER THE CATCH BASIN
 GRATES WITH ROCK BAGS AT ANY CURBED INLET ON-SITE TO
 STOP SOLIDS FROM ENTERING THE SYSTEM. SHOW THE
 PROTECTION OF ALL ON-SITE CATCH BASINS, SHOW PROTECTION
 OF ALL OFF-SITE CATCH BASINS, INCLUDE DETAILS AS TO THE
 TYPE OF PROTECTION USED ON AND OFF-SITE FOR THE CATCH
 BASINS, SUCH AS FILTER FABRIC IS REQUIRED UNDER THE
 CATCH BASIN GRATES WITH ROCK BAGS AT ANY CURBED INLET
 TO STOP SOLIDS FROM ENTER THE SYSTEM.
 C) ADD TURBIDITY BARRIER AT THE OUTFALLS AND ALONG THE
 FULL WIDTH OF THE PROJECT, SHOW WHERE SILT SCREENS WILL
 BE INSTALLED, HOW THEY WILL BE TIED DOWN AND
 MAINTAINED.
 D) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS
 E) DETAIL HOW AND WHEN ANY CLEAN-UP WILL BE PREFORMED.
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING STORMWATER SYSTEM:
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18).
 SECTION 109.3.10 , IMPACT OF CONSTRUCTION , OF THE CITY
 CODE REQUIRES A PROFESSIONAL ENGINEER TO PREPARE A
 DRAINAGE PLAN AND CERTIFY THE WORK. MAY BE UNDER THE
 BUILDING CODE, LOOK IT UP WHEN YOU GET A CHANCE.
 _______________________________________________________
 __________________________________
 - NO STORMWATER SYSTEM PLAN SUBMITTED OR SUBMITTED WITH
 OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING WATER SYSTEM: ANY NEW CITY WATER
 SERVICE? IRRIGATION? ETC.
 _______________________________________________________
 __________________________________
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 _______________________________________________________
 ___________________________________
  
 - NO WATER SYSTEM PLAN SUBMITTED OR SUBMITTED WITH OUT
 ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
 _______________________________________________________
 __________________________________
  
 COMMENTS CONCERNING SANITARY SYSTEM: ANY NEW CITY
 SEWER?
 _______________________________________________________
 _________________________________
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 _______________________________________________________
 __________________________________
 - NO SANITARY SYSTEM PLAN SUBMITTED OR SUBMITTED WITH
 OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING LIGHTING:
 _______________________________________________________
 __________________________________
 - NO LIGHTING PLAN SUBMITTED OR SUBMITTED WITH OUT
 ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING IRRIGATION:
 _______________________________________________________
 __________________________________
 - IRRIGATION PLAN SUBMITTED OR SUBMITTED WITH OUT
 ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING LANDSCAPING:
 _______________________________________________________
 __________________________________
 - NO LANDSCAPING PLAN SUBMITTED OR SUBMITTED WITH OUT
 ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING SURVEY ISSUES:
 PER; CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18), CHAPTER 78
 STREETS, SIDEWALKS AND PUBLIC PLACES, ARTICLE I. IN
 GENERAL, SECTION 78-9. CITY DATUM OR PLANE OF
 REFERENCE.
 (A) THE CITY DATUM OR OFFICIAL CITY BASE OR PLANE OF
 REFERENCE FOR ELEVATIONS IN THE CITY IS HEREBY FIXED AS
 THE NATIONAL GEODETIC VERTICAL DATUM OF 1929 (NGVD-29),
 AS ESTABLISHED BY THE UNITED STATES COAST AND GEODETIC
 SURVEY.
 (B) ALL OFFICIAL ELEVATIONS, INCLUDING BUT NOT
 RESTRICTED TO SIDEWALK, STREET AND SEWER GRADES,
 HEREAFTER ESTABLISHED IN THE CITY SHALL BE DESCRIBED
 WITH REFERENCE TO THEIR ELEVATIONS, AS COMPARED WITH
 THE OFFICIAL CITY DATUM IN FEET AND DECIMALS OF A FOOT.
 NO GRADE OR OFFICIAL ELEVATION SHALL BE ESTABLISHED
 OTHER THAN IN THE MANNER PRESCRIBED IN THIS SECTION.
 PLEASE USE THIS DATUM AND CALL IT OUT ON THE PLAN
 SHEETS AS A NOTE.
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING SIDEWALKS AND DRIVEWAY APPROACHES
 _______________________________________________________
 __________________________________
 -DRIVEWAY APPROACH AND OR SIDEWALK PLAN NEEDS TO BE
 APPROVED BY THE ROW PERMIT REVIEWER AT THE TRAFFIC
 ENGINEERING OFFICE PRIOR TO BEING SUBMITTED TO
 CONSTRUCTION SERVICES.
 - NO SIDEWALK OR DRIVEWAY APPROACH PLAN SUBMITTED OR
 SUBMITTED WITH OUT ENGINEERING SERVICES DEPARTMENT
 APPROVED STAMP. PRIOR TO SUBMITTING ROW PERMIT ASK THE
 RECEPTIONIST TO FAX IT TO YOU OR STOP BY AND PICK UP A
 COPY.
 CONTACT THE RIGHT-OF-WAY REVIEWER, WINDEL PALMER,
 PROJECT COORDINATOR, THE TRAFFIC ENGINEERS OFFICE AT:
 1000 ? 45TH STREET, SUITE 15
 WEST PALM BEACH, FL 33407
 TELEPHONE: (561)494-1041
 FAX: (561) 494-1069
  
 FORM CAN BE DOWNLOADED VIA WEB:
 HTTP://WWW.CITYOFWPB.ORG/ENGINEERING/ENG_INFO.HTM#RIGHT
 OFWAY
  
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING STREETS, SIGNAGE, ADA,:
 _______________________________________________________
 __________________________________
 - NO STREET, CURB, ADA PLAN SUBMITTED OR SUBMITTED WITH
 OUT ENGINEERING SERVICES DEPARTMENT APPROVED STAMP.
 _______________________________________________________
 __________________________________
 COMMENTS CONCERNING DUMPSTERS AND ENCLOSURES:
 _______________________________________________________
 __________________________________
 - ENCLOSURE DETAIL NOT SUBMITTED OR SUBMITTED WITH
 NON-STANDARD DETAIL OR WITH OUT ENGINEERING SERVICES
 DEPARTMENT APPROVED STAMP.
 DETAIL MUST MATCH WHAT IS TO BE PERMITTED. IF THE CITY
 DETAIL IS USED THEN A WOOD ENCLOSURE WILL NEED TO BE
 BUILT. IF CHAIN LINK OR A CONCRETE WALL ARE TO BE USED
 THEN SUBMIT A DETAIL FOR ONE OF THEM.
 _______________________________________________________
 __________________________________
  
 THANK YOU FOR YOUR PROMPT ASSISTANCE.
  
 MANNY GONZALEZ
 PROJECT COORDINATOR
 CITY OF WPB ENGINEERING SERVICES
 (561) 494-1085
 AT CS EXT 561-805-6713
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-03 Cont ID  
Sent By mawillia Date 2008-12-03 Time 11:58 Rev Time 0.00
Received By mawillia Date 2008-12-03 Time 11:48 Sent To  
Notes
2008-12-03 11:52:15*****APPROVED****
  
 PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-18 Cont ID  
Sent By mawillia Date 2008-11-18 Time 12:14 Rev Time 0.00
Received By mawillia Date 2008-11-18 Time 11:50 Sent To  
Notes
2008-11-18 12:13:02*****PROVISO*****
  
  
 THE APPROPIATE PLAN SHEET(S), IF ANY, TO BE
 FIRE-STAMPED UNDER THE PERMIT APPLICATION PROCESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-01 Cont ID  
Sent By adarroug Date 2008-12-01 Time 16:17 Rev Time 0.00
Received By adarroug Date 2008-12-01 Time 16:10 Sent To  
Notes
2008-12-01 16:17:52TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-08 Cont ID  
Sent By btrobaug Date 2008-12-08 Time 14:18 Rev Time 0.00
Received By btrobaug Date 2008-11-07 Time 11:40 Sent To PC
Notes
2008-11-07 11:40:57TO "COMM" BD#11--EXPEDITED--

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-03 Cont ID  
Sent By jroach Date 2008-12-03 Time 13:32 Rev Time 0.00
Received By jroach Date 2008-12-03 Time 13:32 Sent To  
Notes
2008-12-03 13:37:35ZONING PLAN REVIEW
 PERMIT: 08110113
 ADD: 4801 DREHER TRAIL NORTH
 CONT: BELLA CONSTRUCTION CORP.
 TEL: (561) 722-6402
  
 PROVISO:
  
 THIS APPROVAL IS ONLY FOR THE SLAB FOR THE INSTALLATION
 OF A TEMPORARY TENT!
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-01 Cont ID  
Sent By jroach Date 2008-12-01 Time 18:15 Rev Time 0.00
Received By jroach Date 2008-12-01 Time 18:15 Sent To  
Notes
2008-12-01 18:18:34ZONING PLAN REVIEW
 PERMIT: 08110113
 ADD: 4801 DREHER TRAIL NORTH
 CONT: BELLA CONSTRUCTION CORP.
 TEL: (561) 722-6402
  
 REVIEW STATUS: FAILED
  
 THE FOLLOWING ARE REPEAT COMMENTS FROM PREVIOUS PLAN
 REVIEWS:
  
 1) PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY OF THE AREA.
  
 2) PLEASE PROVIDE THE SETBACK DIMENSIONS FROM ALL
 PROPERTY LINES TO THE PROPOSED SLAB/TENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-11-21 Cont ID  
Sent By jroach Date 2008-11-21 Time 16:13 Rev Time 0.00
Received By jroach Date 2008-11-21 Time 16:13 Sent To  
Notes
2008-11-21 16:15:45***FAILED***
  
 1) PLEASE PROVIDE MORE INFORMATION REGARDING THE
 PROPOSED TENT...WILL THIS BE TEMPORARY OR PERMANENT? IF
 THIS IS A PERMANENT TENT, ADDITIONAL COMMENTS MAY BE
 GENERATED THAT COULD SIGNIFICANTLY ALTER THE PERMITTING
 PROCESS AND SCOPE OF WORK. PLEASE CONTACT ME REGARDING
 THIS FOR FURTHER DISCUSSION.
  
 2) PLEASE PROVIDE TWO (2) COPIES OF A CURRENT AND
 ACCURATE SURVEY OF THE AREA.
  
 3) PLEASE PROVIDE THE SETBACK DIMENSIONS FROM ALL
 PROPERTY LINES TO THE PROPOSED SLAB/TENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.