 |
Plan Review Details - Permit 08110110
Plan Review Stops For Permit 08110110 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-01-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2009-01-23 |
Time |
16:35 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2009-01-22 |
Time |
09:41 |
Sent To |
|
|
Notes |
2009-01-23 16:36:26 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1-10. ADDRESSED. | | | | 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE | | REQUIRED WIDTH. PROVIDE DIMENSIONS TO SHOW COMPLIANCE. | | | | COMMENT NOT ADDRESSED. RESPONSE LETTER STATES THAT IT | | IS STRUCTURALLY INFEASIBLE TO MODIFY THE EXISTING | | STRUCTURE TO PROVIDE THE PROPER WIDTH, AND THIS IS AN | | EXISTING CONDITION. NOTE THAT THIS APPEARS TO BE A | | CHANGE OF OCCUPANCY WITH AN INCREASE IN OCCUPANT LOAD | | AND THE CORRIDOR WIDTH IS BEING DECREASED DUE TO | | INSTALLATION OF HANDRAILS. THEREFORE, THE STATEMENT | | THAT ???THIS IS AN EXISTING CONDITION AND WE HAVE NOT | | MADE IT WORSE??? IS NOT CORRECT. ALL MODIFICATIONS MUST | | COMPLY WITH THE CODE, FBC1001.1, EVEN WHEN THE LEVEL OF | | SAFETY/CODE COMPLIANCE IS KEPT THE SAME UNLESS | | PROVISIONS MADE FOR THAT SITUATION IN THE CODE (OR | | PROPOSED THROUGH ALTERNATE MATERIALS AND METHODS). SOME | | WAYS WHICH THIS COULD BE ADDRESSED WOULD BE TO RECESS | | THE DOORS, CHANGE THE DOOR LOCATION (IF AFFECTED BY THE | | COLUMN), CHANGE THE PROPOSED RAILING LOCATION, INSWING | | DOOR. SUGGESTIONS FOR RESOLUTION SHOULD BE THOROUGHLY | | INVESTIGATED BY DOR AS FULL RESEARCH INTO EACH OF THESE | | HYPOTHETICAL OPTIONS HAS NOT BEEN DONE. | | | | SCOPE CANNOT BE DETERMINED BECAUSE SHEETS A1 AND A3 ARE | | NOT CONSISTENT REGARDING THE DOOR SWING AT ROOMS 110 | | AND 109. LIFE SAFETY PLAN SHOWS THESE DOORS AS THE SAME | | SWING AS THE DEMO PLAN. DEPENDING ON WHICH CHANGE IS | | MADE, A DOOR IS POSSIBLY AFFECTED BY THE COLUMN OR | | OTHER DOOR SWING. AT THIS POINT, IT CANNOT BE | | DETERMINED WHAT NEEDS TO BE REVIEWED AS THE EXISTING | | DOOR SWING AND PROPOSED DOOR SWING ARE NOT CLEAR. | | | | REGARDING CHANGING THE DOOR SWING WITHOUT COMPLYING | | WITH THE CODE, ANY REQUEST TO PROPOSE AN ALTERNATIVE TO | | THE CODE IS TO BE DONE THROUGH ALTERNATE MATERIALS AND | | METHODS AND MUST BE MADE THROUGH A WRITTEN, USUALLY BY | | LETTER STATING THE CODE SECTION CITED IN THE COMMENT | | LIST, AND THE ARGUMENT IN FAVOR OF AN ALTERNATE METHOD. | | IF THE CODE ALLOWS FOR AN EXCEPTION, THIS EXCEPTION | | SHOULD BE INCORPORATED INTO THE PLAN. | | | | 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE | | 11-25, PULL SIDE. | | | | RESPONSE LETTER STATES THAT THE AREA IS 5FT 8IN X 14FT. | | IT IS NOT CLEAR WHAT DIMENSION YOU REFER TO AS THESE | | DIMENSIONS ARE NOT NOTED ON THE PLAN. THE WALKWAY AREA | | APPEARS TO BE 4FT 7IN DUE TO THE HANDRAIL, BUT AT THE | | COLUMN IT IS NARROWER. PLEASE PROVIDE THAT DIMENSION. | | NOTE THE REQUIREMENT OF 54IN IF THE DOOR HAS A CLOSER | | FOR A SIDE APPROACH. AS THE ACTUAL DIMENSION IS LESS | | THAN 60INCHES, FRONT APPROACH CANNOT BE USED WHERE | | THERE IS A HANDRAIL. WHEN ALTERING THE DOOR, THE DOOR | | ALTERATION IS TO COMPLY WITH FBC REQUIREMENTS, BOTH CH | | 10 AND CH 11. | | | | GATE 116 DOES NOT COMPLY WITH MANEUVERING CLEARANCE | | REQUIREMENT OF 18IN ON THE PULL SIDE, 12 IN ON THE PUSH | | SIDE. IT IS NOT CLEAR IF DOOR 112 COMPLIES WITH THE | | 12IN REQUIREMENT. | | | | 13-14. ADDRESSED. | | | | 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE | | PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIRED | | FBC TABLE 1016.1. | | | | RESPONSE LETTER STATES FIRE RESISTANCE NOT REQUIRED FOR | | THE CORRIDOR AS IT IS OPEN. IF THIS IS A TYPE IIIA | | BUILDING, SHOULDN???T THE COLUMNS BE 1 HOUR, EXTERIOR | | BEARING WALLS 2 HOUR, ETC. PER FBC TABLE 601? PLEASE | | NOTE FIRE RATINGS ON THE PLAN TO AVOID FIELD CONFLICTS. | | | | 16-21. ADDRESSED. | | | | NEW COMMENTS: | | | | 22. THE OCCUPANT LOAD OF CLASSROOMS 108, 109, AND 110 | | (WHICH ALL EXIT THROUGH THE RAMP SINCE THE OPEN | | BREEZEWAY HAS NOW BEEN BLOCKED) EXCEEDS 50, SO TWO | | EXITS ARE REQUIRED FBC1018.1. | | | | 23. ALTHOUGH THE GATE IN THE BREEZEWAY HAS BEEN NOTED | | ???NOT AN EXIT???, IT IS STILL IN THE EXIT CORRIDOR AND | | MUST COMPLY WITH THE REQUIREMENTS OF THE CODE. IF THE | | GATE IS PERMANENTLY LOCKED, IT CREATES A DEAD END WHICH | | EXCEEDS 20FEET FBC1016.3. | | | | 24. FBC1003.5.2, WHEN A CHANGE IN ELEVATION OF 12INCHES | | OR LESS OCCURS IN AN EXIT ACCESS CORRIDOR, A RAMP SHALL | | BE PROVIDED. THE STEP IS IN THE EXIT ACCESS CORRIDOR, | | TWO EXITS ARE REQUIRED SO THE OCCUPANTS OF ROOMS 108, | | 109, AND 110 NEED THIS AS A SECOND EXIT. EVEN IF THIS | | IS MARKED AS NOT AN EXIT, THIS IS STILL LOCATED IN THE | | EXIT ACCESS CORRIDOR. | | | | 25. THE EXTERIOR DOORS ARE BEING ALTERED, PLEASE | | PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC EB 507.3, | | FAC9B72. | | | | 26. IS THIS A CHANGE OF USE/OCCUPANCY? PLEASE SEE FBC | | EB CHAPTER 8. SOME CODE REQUIREMENTS CANNOT BE | | DETERMINED WITHOUT THIS INFORMATION. | | | | 27. WHAT IS THE AREA IN THE OPEN COURTYARD? PART OF IT | | IS LABELED STORAGE, IS THIS CROSS SHAPED AREA A PART OF | | THE EXISTING CLASSROOM BUILDING BEING RENOVATED? WHAT | | ARE THE LINES WITH THE ARC? | | | | 28. ANOTHER REVIEWER HAS MADE NOTES THAT THIS AREA WILL | | BE USED FOR ADULT DAY CARE, SEE FBC313.2.3. PLEASE NOTE | | THAT OCCUPANT LOAD FBC1004 IS BASED ON ANTICIPATED | | NUMBER OF PEOPLE BASED ON ACTIVITY, AND OCCUPANCY | | CLASSIFICATION FBC CHAPTER 3 IS BASED ON CLASSIFICATION | | AS TO USE. IT IS POSSIBLE TO HAVE AN ASSEMBLY TYPE OF | | OCCUPANT LOAD IN ANOTHER OCCUPANCY CLASSIFICATION. | | | | 29. SEE ALSO FBC1033.6. IT CANNOT BE DETERMINED AT THIS | | POINT IF THE DOORS WOULD BE CONSIDERED DIRECTLY TO THE | | OUTSIDE; DO THE WINDOWS COMPLY WITH THE REQUIREMENT? IT | | SEEMS THAT AT THIS POINT REQUIREMENTS ARE NOT CLEAR | | BECAUSE OCCUPANCY DECLARED IS IN QUESTION. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-11-26 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-11-26 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-11-26 |
Time |
10:31 |
Sent To |
|
|
Notes |
2008-11-26 13:12:45 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. PROVIDE A DEMO PLAN WHICH SHOULD INCLUDE EXISTING | | FLOOR PLAN. SCOPE IS NOT CLEAR. IT IS NOT CLEAR WHICH | | WALLS ARE EXISTING, WHICH ARE NEW. | | | | 2. PLEASE NOTE THAT THE FLOOR PLAN SHOWN ON A1 DOES NOT | | IDENTIFY DOORS, ROOMS, OR CORRIDORS. FOR INSTANCE, | | THERE ARE FIVE DIFFERENT ROOMS LABELED "EXISTING | | CLASSROOM". THERE ARE MANY DOORS BUT THEY ARE NOT | | LABELED, AND AS THE ROOMS AND CORRIDORS ARE NOT LABELED | | IT IS DIFFICULT FOR ME TO IDENTIFY WHICH DOOR, ROOM, OR | | CORRIDOR IS REFERRED TO IN THE COMMENT. ROOM | | DESIGNATION NUMBERS, OR A DOOR SCHEDULE, WOULD BE | | HELPFUL. | | | | 3. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING | | HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY | | CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. | | | | 4. DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. | | | | 5. GOVERNING CODE SHOULD INCLUDE 2007 | | REVISIONS/SUPPLEMENTS (EFFECTIVE JULY 1, 2007). | | | | 6. SHOW CORRIDOR WIDTHS. FBC11-4.8.6, FBC10. | | | | 7. DECLARE SQUARE FOOT AREA AND OCCUPANT LOAD FOR EACH | | ROOM. FBC10. | | | | 8. A DOOR IS SHOWN AS SWINGING AGAINST THE DIRECTION OF | | TRAVEL. SEE COMMENT 7; CLARIFY REQUIREMENTS FBC1008.1. | | 9. A 1" SLOPE IS SHOWN IN THE CORRIDOR. SPECIFY THE | | WIDTH, FBC10, FBC11. | | | | 10. A 4" ELEVATION CHANGE IS SHOWN AT A DOOR. SEE | | FBC1003.5.2, FBC1104.3.8. | | | | 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE | | REQUIRED WIDTH. PROVIDE DIMESIONS TO SHOW COMPLIANCE. | | | | 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE | | 11-25, PULL SIDE. | | | | 13. A2, DETAIL LABELED AS "GUARDRAIL". NOTE THAT A | | GUARDRAIL IS REQUIRED TO BE 42", BUT THIS IS SHOWN AS | | 36". IS A GUARDRAIL REQUIRED? FBC1012.1. IS THIS A | | HANDRAIL RATHER THAN A GUARDRAIL? | | | | 14. A TYPICAL INTERIOR PARTITION DETAIL WAS PROVIDED. | | HOWEVER, IT IS NOT CLEAR WHAT THIS IS FOR; EXISTING OR | | PROPOSED? ALSO (WALL LEGEND) NOTE THAT THE GRAPHIC FOR | | THE BLOCK WALL DOES NOT MATCH THE GRAPHIC USED FOR THE | | EXTERIOR WALL, AND THE GRAPHIC FOR THE FRAME WALL DOES | | NOT APPEAR ON THE FLOOR PLAN. SEE OTHER COMMENTS | | REGARDING SCOPE OF WORK. | | | | 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE | | PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIED | | FBC TABLE 1016.1. | | | | 16. WHAT DO THE DASHED LINES REPRESENT? THEY APPEAR IN | | TWO DIFFERENT EXISTING CLASSROOMS. | | | | 17. A3, LIFE SAFETY PLAN, THE PATH OF TRAVEL SHOULD BE | | MEASURED ALONG THE PATH OF ANTICIPATED TRAVEL. IT IS | | SHOWN GOING THROUGH THE CENTER OF THE ROOM, WHERE A | | CLASSROOM WOULD NORMALLY HAVE CHAIRS AND DESKS. PATH OF | | TRAVEL SHOULD BE SHOWN ALONG THE PERIMETER OF THE ROOM. | | | | 18. PROVIDE MORE INFORMATION REGARDING THE EXIT | | DISCHARGE. THE LIFE SAFETY PLAN MEASURES TO THE RAMP | | BASE. IS THIS THE OUTSIDE? A DOOR IS SHOWN ADJACENT TO | | THE RAMP IN THE HALLWAY. COVERED WALKWAYS SHOULD BE | | INCLUDED IN PATH OF TRAVEL. FBC1002. PLAN SHOULD SHOW | | WHERE THE OCCUPANT WILL LEAVE THE BUILDING (INCLUDING | | COVERED WALKWAYS). | | | | 20. DOES THE BUILDING HAVE A FIRE ALARM? SEE | | FBC11-4.28. NOTE THAT A VISUAL SIGNAL IS REQUIRED IN | | THE RESTROOMS; NONE SHOWN. | | | | 21. THE PROPOSED CHANGE OF DOOR SWING APPEARS TO | | INTERFERE WITH THE DOOR SWING OF THE ADJACENT DOOR, | | FBC1008. PLEASE REVISE. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-01-16 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-01-16 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-01-16 |
Time |
11:29 |
Sent To |
|
|
Notes |
2009-01-16 11:30:53 | ** DENIED PLANS** | | | | | | | | | | 1) NOTE: THE OCCUPANCY CLASSIFICATION IS STILL IN | | QUESTION. IT IS THE UNDERSTANDING OF THIS OFFICE THAT | | THIS WILL BE USED AS AN ADULT DAY CARE USE, NOT | | EDUCATION A-3). | | USE FOR POSSIBLE ALZHEIMER PATIENTS IS NOT EDUCATION | | SEE FBC CHAPTER 3 (GROUP *D*) CHAPTER 4, LS 101 CHAPTER | | 16. | | PLEASE PROVIDE LETTER FROM OWNER AND DESIGNER WHICH | | COORDINATES WITH THE PLANS STATING THE INTENDED USE. | | ONCE THIS HAS BEEN FINALIZED REVIEW STATUS WILL BE | | REVISED. | | LETTERS FROM OWNER AND DESIGNER NEED TO BE ORIGINAL AND | | NOTARIZED CORRECTLY. | | | | FBC EXISTING: 801.2 PARTIAL CHANGE OF OCCUPANCY GROUP. | | WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A | | NEW OCCUPANCY GROUP, SECTION 812 SHALL APPLY. | | 13-101.3,808.3,808.1. | | | | | | AS THE INTENDED USE IS NOT YET DETERMINED FOR FINAL | | REVIEW OF PLANS, SOME CHANGES MAY OR MAY NOT BE NEEDED. | | | | | | | | | | | | | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-11-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-11-25 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-11-25 |
Time |
11:27 |
Sent To |
|
|
Notes |
2008-11-25 11:28:00 | | | | | | | | | | | ** FAILED REVIEW ** | | | | | | | | 1) NOTE: A CALLED WAS PLACED TO RON GILMAN WHO IS THE | | ELECTRICAL ENGINEER OF RECORD FOR PROJECT. THE NEW | | ELECTRICAL PANEL AND EXISTING DISCONNECTS NEED TO BE | | VERIFIED IF THEY CONTAIN A LOCKING TYPE COVER FOR THE | | OCCUPANCY ALONG WITH A LOCKING COVER FOR THE | | DISCONNECT. | | THERE MAY BE SOME OTHER OPTIONS SUCH AS A SHORT WALL | | WITH A LOCKING DOOR OF SOME TYPE GIVING THE CLEARANCE | | REQUIREMENTS PER 110.26, 240.24 | | ENGINEER WAS GOING TO LOOK INTO OPTIONS AND CONTACT THE | | ARCHITECT. | | | | 2) NOTE: NEED EQUIPMENT GROUNDING CONDUCTOR FROM | | DISCONNECT TO NEW PANEL. | | 250.110,250.122 | | | | 3) NOTE: PLEASE SEE 422.30, 422.31 AS THE WATER HEATER | | REQUIRES A DISCONNECT. THE PLANS SHOW A RECEPTACLE | | WHICH IS NOT PERMITTED. | | | | 4) NOTE: OCCUPANCY FOR INTENDED USE WILL NEED TO BE ON | | PLANS PER FBC CHAPTER 3, 303.1 | | | | 5) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS WHICH CALL | | FOR TWO NEW ELECTRICAL PANELS. PLEASE COORDINATE. | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2009-01-27 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2009-01-27 |
Time |
09:15 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2009-01-27 |
Time |
09:09 |
Sent To |
|
|
Notes |
2009-01-27 09:15:27 | 1) IT APPEARS THAT RESPONSES HAVE BEEN PROVIDED TO | | PREVIOUS COMMENTS MADE BY THE FIRE RESCUE DEPARTMENT. | | | | 2) NOTE # 3 BELOW DOOR SCHEDULE INDICATES ON PAGE A-1 | | THAT "EXISTING GATES DESIGNATED TO BE PART OF AN EGRESS | | SYSTEM SHALL REMAIN UNLOCKED OR AUTOMATICALLY UNLOCK IN | | CASE OF FIRE DURING HOURS OF OPERATION". HOW DOES THIS | | AUTOMATIC UNLOCKING OCCUR. | | | | 3) ON PAGE A-3 IT HAS BEEN DECLARED THAT OCCUPANT | | ACTIVITIES WILL INLCUDE "ADULT EDUCATION AND RELIGIOUS | | ACCESSORY USE". SOME INFORMATION SUGGESTS THAT THESE | | FACILITIES MAY BE USED FOR AN ADULT DAY CARE AND IS NOT | | DECLEARED ON THE PLANS. THIS INFORMATION IF TRUE NEEDS | | TO BE DECLARED ON THE PLANS. THE MINIMUM BUILDING AND | | FIRE CODE REQURIEMENTS SHALL BE MET FOR THE SPECIFIC | | OCCUPANCY TYPE AND USE. THE BUILDING AND ELECTRICAL | | PLAN REVIEWERS HAVE BOT DENIED THESE REVISED PLANS. | | PLEASE REVISE PLANS ACCORDINGLY AND ENSURE THAT ALL | | INFORMATION HAS BEEN PROVIDED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-12-04 |
|
|
Cont ID |
|
Sent By |
mcarsill |
Date |
2008-12-04 |
Time |
07:41 |
Rev Time |
0.00 |
Received By |
mcarsill |
Date |
2008-12-04 |
Time |
07:34 |
Sent To |
|
|
Notes |
2008-12-04 07:41:10 | MEMORIAL PRESBYTERION CHURCH | | 1300 SOUTH OLIVE AVENUE | | | | 1. PLEASE DECLARE USED OF THESE CLASSROOMS. WHAT TYPES | | OF ACTIVITIES, AGE OF STUDENTS, AND THE DURATION OF | | TIME THESE STUDENTS WILL RECEIVE INSTRUCTION. | | | | 2. PLEASE ILLUSTRATE ON THE PLANS THE LOCATIONS OF ANY | | FIRE SAFETY EQUIPMENT CONTAINED IN THE BUILDING. THIS | | EQUIPMENT WOULD INCLUDE ILLUMINATED EXIT SIGNS, | | EMERGENCY LIGHTING FIXTURES, PORTABLE FIRE | | EXTINGUISHERS, FIRE SPRINKLER SYSTEMS, OR FIRE ALARM | | EQUIPMENT. | | | | 3. PLEASE INDICATE EXISTING INTERIOR FINISH | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | 4. PLEASE INDICATE EXIT DISCHARGE LOCATIONS. | | | | 5. PLEASE PROVIDE AN EXPECTED OCCUPANT LOADS FOR THE | | OCCUPANT LOADS FOR THE EDUCATIONAL PORTIONS OF THE | | BUILDING. | | | | 6. INFORMATION NEEDED FOR ANY EXISTING OR NEW DOOR | | HARDWARE TO INLCUDE COURTYARD GATES. PLEASE FURTHER | | ADVISE WHAT TYPE OF LOCKING ARRANGEMENTS EXIST FOR THE | | CLOSET DOORS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2009-01-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2009-01-07 |
Time |
16:44 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2009-01-07 |
Time |
16:44 |
Sent To |
|
|
Notes |
2009-01-07 16:44:45 | TO "COMM" BD#7 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-12-04 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-12-04 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-11-07 |
Time |
10:42 |
Sent To |
|
|
Notes |
2008-11-07 11:01:21 | TO "COMM" BD#22 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
N |
Date |
2009-02-15 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-02-15 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-02-15 |
Time |
16:38 |
Sent To |
PC |
|
Notes |
2009-02-15 16:43:02 | BASED ON THE RECONFIGURED SPACE AND PROPOSED USE | | (CLASSIFICATION AS ADULT DAY CARE) AND BASED ON THE | | REQUIREMENTS OF FBC-EB 609.1 AND FBC-EB 809.1, | | ALTERATIONS OR ADDITIONS TO THE EXISTING MECHANICAL | | SYSTEMS ARE NOT REQUIRED FOR CODE COMPLIANCE. UNLESS | | SPECIFIC MECHANICAL WORK IS BEING PERFORMED AS PART OF | | THE ALTERATION, NO MECHANICAL PERMIT IS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2008-11-07 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-11-07 |
Time |
16:18 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2008-11-07 |
Time |
16:18 |
Sent To |
|
|
Notes |
2008-11-07 16:18:47 | NO MECHANICAL PLANS SUBMITTED, AND NO | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | THIS TIME. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2009-01-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-30 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-30 |
Time |
15:48 |
Sent To |
|
|
Notes |
2009-01-30 15:58:02 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 EXISTING BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1, OK | | 2. OK | | 3. OK | | | | 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE | | WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN | | THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE | | THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL | | LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN | | CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2 | | & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH | | REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED | | DRINKING FOUNTAINS? | | ****RESPONSE NOTED, BUT COMMENT CONCERNING MINIMUM | | FACILITIES HAS NOT BEEN ADDRESSED. PER THE SQUARE | | FOOTAGE INDICATED, (5556SF)), AND THE 15 NET PER SF THE | | MINIMUM FACILITIES ARE 2 WATER CLOSETS FOR MALE AND 3 | | WATER CLOSETS FOR FEMALE, 2 DRINKING FOUNTAINS, AND A | | SERVICE SINK. PLEASE INDICTE THE LOCATION OF ALL | | REQUIRED FIXTURES. TABLES 1004.1.2 & 403.1. | | | | 5. OK | | 6. OK | | 7. OK | | 8. OK | | | | *********NEW COMMENT********** | | | | 1B. ROOM 110 INDICATES A NEW SINK. PER SECTION 11-4.24 | | THE SINK SHALL BE ACCESSIBLE. PLEASE SUBMIT A | | DETAIL/ELEVATION FOR THE SINK SHOWING COMPLIANCE WITH | | SECTION 11-4.24 AND ALL SUBSECTIONS. (FORWARD APPROACH | | REQUIRED, CABINET DOORS NOT APPROVED IN CLEAR FLOOR | | SPACE). | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-12-02 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-12-02 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-12-02 |
Time |
15:43 |
Sent To |
|
|
Notes |
2008-12-02 16:56:07 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 EXISTING BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1, ALL SHEETS SEALED BY THE ARCHITECT OF RECORD ARE | | REQUIRED TO HAVE THE SIGNATURE OF THE DESIGN | | PROFESSIONAL. IT APPEARS THAT INITIALS HAVE BEEN USED | | IN PLACE OF THE SIGNATURE. IF THE INITIALS ARE INDEED | | THE LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL, THEN A | | SIGNED, SEALED, NOTORIZED LETTER INDICATING THE LEGAL | | SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR | | RECORDS. FAC 61G1-16.003, 61G1-16.004(5) & FS 481.2055. | | | | 2. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE | | WORK INDICATED CAN BE VERIFIED. SECTION 106.1.2. | | | | 3. SHT A-1 SHOW THE ROOM NUMBERS THAT CORRESPOND TO THE | | ROOMS INDICATED ON THE APPLICATION FOR PERMIT. SECTIONS | | 106.1.1 & 106.1.2. | | | | 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE | | WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN | | THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE | | THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL | | LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN | | CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2 | | & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH | | REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED | | DRINKING FOUNTAINS? | | | | 5. SHT A-1 INDICATES CODE REQUIREMENTS WITH 2006 | | REVISIONS. CODE SHALL ALSO INCLUDE THE 2007 REVISIONS | | AS WELL AS THE 2005 REVISIONS. SECTION 106.1.1. | | | | 6. INDICATE THE LEVEL OF ALTERATION AS REQUIRE IN | | SECTION 301 OF THE EXISTING BUILDING CODE. | | | | 7. SHT A-1 INDICATES 4 ABANDONED GAS BASE BOARD HEATERS | | AND A NEW 30 GALLON GAS WATER HEATER. A SEPARATE GAS | | PERMIT IS REQUIRED THE FOLLOWING INFORMATION IS | | REQUIRED FOR THE PERMIT: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | D. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | E. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | F. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304. | | | | G. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | H. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | J. CLEARLY SHOW THE LOCATION AND CAP- | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | OR ASME), THE DISTANCE OF THE TANK FROM | | THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | INGS, AND THE LOCATION OF ANY BUILDING | | OPENINGS BELOW THE RELIEF VALVE OF THE | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | K. CLEARLY INDICATE ON THE PLAN IF THE | | LP TANK IS ABOVE OR BELOW GROUND, AND | | SHOW REQUIRED PROTECTION OF THE TANK AND | | APPURTENANCES PER NFPA 58. IF THE TANK | | IS BELOW GROUND THE CONTAINER SHALL BE | | SECURILY ANCHORED PER NFPA 58 SECTION | | 3-2.2.7(H). | | | | 8. SHT P-1 THE SANITARY RISER DIAGRAM SHOWS AN EXISTING | | W/C & LAV BY THE CLASSROOM SINK THAT IS NOT SHOWN ON | | THE FLOOR PLAN. PLEASE CLARIFY. SHOW THE EXISTING | | TOILET ROOM ON THE FLOOR PLAN. SECTIONS 106.1.1, | | 106.1.2 & 701.1. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |