Plan Review Details - Permit 08110110
Plan Review Stops For Permit 08110110
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-23 Cont ID  
Sent By shill Date 2009-01-23 Time 16:35 Rev Time 0.00
Received By shill Date 2009-01-22 Time 09:41 Sent To  
Notes
2009-01-23 16:36:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1-10. ADDRESSED.
  
 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE
 REQUIRED WIDTH. PROVIDE DIMENSIONS TO SHOW COMPLIANCE.
  
 COMMENT NOT ADDRESSED. RESPONSE LETTER STATES THAT IT
 IS STRUCTURALLY INFEASIBLE TO MODIFY THE EXISTING
 STRUCTURE TO PROVIDE THE PROPER WIDTH, AND THIS IS AN
 EXISTING CONDITION. NOTE THAT THIS APPEARS TO BE A
 CHANGE OF OCCUPANCY WITH AN INCREASE IN OCCUPANT LOAD
 AND THE CORRIDOR WIDTH IS BEING DECREASED DUE TO
 INSTALLATION OF HANDRAILS. THEREFORE, THE STATEMENT
 THAT ???THIS IS AN EXISTING CONDITION AND WE HAVE NOT
 MADE IT WORSE??? IS NOT CORRECT. ALL MODIFICATIONS MUST
 COMPLY WITH THE CODE, FBC1001.1, EVEN WHEN THE LEVEL OF
 SAFETY/CODE COMPLIANCE IS KEPT THE SAME UNLESS
 PROVISIONS MADE FOR THAT SITUATION IN THE CODE (OR
 PROPOSED THROUGH ALTERNATE MATERIALS AND METHODS). SOME
 WAYS WHICH THIS COULD BE ADDRESSED WOULD BE TO RECESS
 THE DOORS, CHANGE THE DOOR LOCATION (IF AFFECTED BY THE
 COLUMN), CHANGE THE PROPOSED RAILING LOCATION, INSWING
 DOOR. SUGGESTIONS FOR RESOLUTION SHOULD BE THOROUGHLY
 INVESTIGATED BY DOR AS FULL RESEARCH INTO EACH OF THESE
 HYPOTHETICAL OPTIONS HAS NOT BEEN DONE.
  
 SCOPE CANNOT BE DETERMINED BECAUSE SHEETS A1 AND A3 ARE
 NOT CONSISTENT REGARDING THE DOOR SWING AT ROOMS 110
 AND 109. LIFE SAFETY PLAN SHOWS THESE DOORS AS THE SAME
 SWING AS THE DEMO PLAN. DEPENDING ON WHICH CHANGE IS
 MADE, A DOOR IS POSSIBLY AFFECTED BY THE COLUMN OR
 OTHER DOOR SWING. AT THIS POINT, IT CANNOT BE
 DETERMINED WHAT NEEDS TO BE REVIEWED AS THE EXISTING
 DOOR SWING AND PROPOSED DOOR SWING ARE NOT CLEAR.
  
 REGARDING CHANGING THE DOOR SWING WITHOUT COMPLYING
 WITH THE CODE, ANY REQUEST TO PROPOSE AN ALTERNATIVE TO
 THE CODE IS TO BE DONE THROUGH ALTERNATE MATERIALS AND
 METHODS AND MUST BE MADE THROUGH A WRITTEN, USUALLY BY
 LETTER STATING THE CODE SECTION CITED IN THE COMMENT
 LIST, AND THE ARGUMENT IN FAVOR OF AN ALTERNATE METHOD.
 IF THE CODE ALLOWS FOR AN EXCEPTION, THIS EXCEPTION
 SHOULD BE INCORPORATED INTO THE PLAN.
  
 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE
 11-25, PULL SIDE.
  
 RESPONSE LETTER STATES THAT THE AREA IS 5FT 8IN X 14FT.
 IT IS NOT CLEAR WHAT DIMENSION YOU REFER TO AS THESE
 DIMENSIONS ARE NOT NOTED ON THE PLAN. THE WALKWAY AREA
 APPEARS TO BE 4FT 7IN DUE TO THE HANDRAIL, BUT AT THE
 COLUMN IT IS NARROWER. PLEASE PROVIDE THAT DIMENSION.
 NOTE THE REQUIREMENT OF 54IN IF THE DOOR HAS A CLOSER
 FOR A SIDE APPROACH. AS THE ACTUAL DIMENSION IS LESS
 THAN 60INCHES, FRONT APPROACH CANNOT BE USED WHERE
 THERE IS A HANDRAIL. WHEN ALTERING THE DOOR, THE DOOR
 ALTERATION IS TO COMPLY WITH FBC REQUIREMENTS, BOTH CH
 10 AND CH 11.
  
 GATE 116 DOES NOT COMPLY WITH MANEUVERING CLEARANCE
 REQUIREMENT OF 18IN ON THE PULL SIDE, 12 IN ON THE PUSH
 SIDE. IT IS NOT CLEAR IF DOOR 112 COMPLIES WITH THE
 12IN REQUIREMENT.
  
 13-14. ADDRESSED.
  
 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE
 PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIRED
 FBC TABLE 1016.1.
  
 RESPONSE LETTER STATES FIRE RESISTANCE NOT REQUIRED FOR
 THE CORRIDOR AS IT IS OPEN. IF THIS IS A TYPE IIIA
 BUILDING, SHOULDN???T THE COLUMNS BE 1 HOUR, EXTERIOR
 BEARING WALLS 2 HOUR, ETC. PER FBC TABLE 601? PLEASE
 NOTE FIRE RATINGS ON THE PLAN TO AVOID FIELD CONFLICTS.
  
 16-21. ADDRESSED.
  
 NEW COMMENTS:
  
 22. THE OCCUPANT LOAD OF CLASSROOMS 108, 109, AND 110
 (WHICH ALL EXIT THROUGH THE RAMP SINCE THE OPEN
 BREEZEWAY HAS NOW BEEN BLOCKED) EXCEEDS 50, SO TWO
 EXITS ARE REQUIRED FBC1018.1.
  
 23. ALTHOUGH THE GATE IN THE BREEZEWAY HAS BEEN NOTED
 ???NOT AN EXIT???, IT IS STILL IN THE EXIT CORRIDOR AND
 MUST COMPLY WITH THE REQUIREMENTS OF THE CODE. IF THE
 GATE IS PERMANENTLY LOCKED, IT CREATES A DEAD END WHICH
 EXCEEDS 20FEET FBC1016.3.
  
 24. FBC1003.5.2, WHEN A CHANGE IN ELEVATION OF 12INCHES
 OR LESS OCCURS IN AN EXIT ACCESS CORRIDOR, A RAMP SHALL
 BE PROVIDED. THE STEP IS IN THE EXIT ACCESS CORRIDOR,
 TWO EXITS ARE REQUIRED SO THE OCCUPANTS OF ROOMS 108,
 109, AND 110 NEED THIS AS A SECOND EXIT. EVEN IF THIS
 IS MARKED AS NOT AN EXIT, THIS IS STILL LOCATED IN THE
 EXIT ACCESS CORRIDOR.
  
 25. THE EXTERIOR DOORS ARE BEING ALTERED, PLEASE
 PROVIDE PRODUCT APPROVAL FOR THE DOORS, FBC EB 507.3,
 FAC9B72.
  
 26. IS THIS A CHANGE OF USE/OCCUPANCY? PLEASE SEE FBC
 EB CHAPTER 8. SOME CODE REQUIREMENTS CANNOT BE
 DETERMINED WITHOUT THIS INFORMATION.
  
 27. WHAT IS THE AREA IN THE OPEN COURTYARD? PART OF IT
 IS LABELED STORAGE, IS THIS CROSS SHAPED AREA A PART OF
 THE EXISTING CLASSROOM BUILDING BEING RENOVATED? WHAT
 ARE THE LINES WITH THE ARC?
  
 28. ANOTHER REVIEWER HAS MADE NOTES THAT THIS AREA WILL
 BE USED FOR ADULT DAY CARE, SEE FBC313.2.3. PLEASE NOTE
 THAT OCCUPANT LOAD FBC1004 IS BASED ON ANTICIPATED
 NUMBER OF PEOPLE BASED ON ACTIVITY, AND OCCUPANCY
 CLASSIFICATION FBC CHAPTER 3 IS BASED ON CLASSIFICATION
 AS TO USE. IT IS POSSIBLE TO HAVE AN ASSEMBLY TYPE OF
 OCCUPANT LOAD IN ANOTHER OCCUPANCY CLASSIFICATION.
  
 29. SEE ALSO FBC1033.6. IT CANNOT BE DETERMINED AT THIS
 POINT IF THE DOORS WOULD BE CONSIDERED DIRECTLY TO THE
 OUTSIDE; DO THE WINDOWS COMPLY WITH THE REQUIREMENT? IT
 SEEMS THAT AT THIS POINT REQUIREMENTS ARE NOT CLEAR
 BECAUSE OCCUPANCY DECLARED IS IN QUESTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-26 Cont ID  
Sent By shill Date 2008-11-26 Time 10:31 Rev Time 0.00
Received By shill Date 2008-11-26 Time 10:31 Sent To  
Notes
2008-11-26 13:12:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE A DEMO PLAN WHICH SHOULD INCLUDE EXISTING
 FLOOR PLAN. SCOPE IS NOT CLEAR. IT IS NOT CLEAR WHICH
 WALLS ARE EXISTING, WHICH ARE NEW.
  
 2. PLEASE NOTE THAT THE FLOOR PLAN SHOWN ON A1 DOES NOT
 IDENTIFY DOORS, ROOMS, OR CORRIDORS. FOR INSTANCE,
 THERE ARE FIVE DIFFERENT ROOMS LABELED "EXISTING
 CLASSROOM". THERE ARE MANY DOORS BUT THEY ARE NOT
 LABELED, AND AS THE ROOMS AND CORRIDORS ARE NOT LABELED
 IT IS DIFFICULT FOR ME TO IDENTIFY WHICH DOOR, ROOM, OR
 CORRIDOR IS REFERRED TO IN THE COMMENT. ROOM
 DESIGNATION NUMBERS, OR A DOOR SCHEDULE, WOULD BE
 HELPFUL.
  
 3. PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 4. DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 5. GOVERNING CODE SHOULD INCLUDE 2007
 REVISIONS/SUPPLEMENTS (EFFECTIVE JULY 1, 2007).
  
 6. SHOW CORRIDOR WIDTHS. FBC11-4.8.6, FBC10.
  
 7. DECLARE SQUARE FOOT AREA AND OCCUPANT LOAD FOR EACH
 ROOM. FBC10.
  
 8. A DOOR IS SHOWN AS SWINGING AGAINST THE DIRECTION OF
 TRAVEL. SEE COMMENT 7; CLARIFY REQUIREMENTS FBC1008.1.
 9. A 1" SLOPE IS SHOWN IN THE CORRIDOR. SPECIFY THE
 WIDTH, FBC10, FBC11.
  
 10. A 4" ELEVATION CHANGE IS SHOWN AT A DOOR. SEE
 FBC1003.5.2, FBC1104.3.8.
  
 11. FBC1008.1, THE DOOR CANNOT BLOCK MORE THAN HALF THE
 REQUIRED WIDTH. PROVIDE DIMESIONS TO SHOW COMPLIANCE.
  
 12. SHOW MANEUVERING CLEARANCE FOR DOORS, FBC FIGURE
 11-25, PULL SIDE.
  
 13. A2, DETAIL LABELED AS "GUARDRAIL". NOTE THAT A
 GUARDRAIL IS REQUIRED TO BE 42", BUT THIS IS SHOWN AS
 36". IS A GUARDRAIL REQUIRED? FBC1012.1. IS THIS A
 HANDRAIL RATHER THAN A GUARDRAIL?
  
 14. A TYPICAL INTERIOR PARTITION DETAIL WAS PROVIDED.
 HOWEVER, IT IS NOT CLEAR WHAT THIS IS FOR; EXISTING OR
 PROPOSED? ALSO (WALL LEGEND) NOTE THAT THE GRAPHIC FOR
 THE BLOCK WALL DOES NOT MATCH THE GRAPHIC USED FOR THE
 EXTERIOR WALL, AND THE GRAPHIC FOR THE FRAME WALL DOES
 NOT APPEAR ON THE FLOOR PLAN. SEE OTHER COMMENTS
 REGARDING SCOPE OF WORK.
  
 15. NOTE ANY REQUIRED FIRE RESISTANCE RATINGS ON THE
 PLAN. FOR INSTANCE, CORRIDOR PROTECTION MAY BE REQUIED
 FBC TABLE 1016.1.
  
 16. WHAT DO THE DASHED LINES REPRESENT? THEY APPEAR IN
 TWO DIFFERENT EXISTING CLASSROOMS.
  
 17. A3, LIFE SAFETY PLAN, THE PATH OF TRAVEL SHOULD BE
 MEASURED ALONG THE PATH OF ANTICIPATED TRAVEL. IT IS
 SHOWN GOING THROUGH THE CENTER OF THE ROOM, WHERE A
 CLASSROOM WOULD NORMALLY HAVE CHAIRS AND DESKS. PATH OF
 TRAVEL SHOULD BE SHOWN ALONG THE PERIMETER OF THE ROOM.
  
 18. PROVIDE MORE INFORMATION REGARDING THE EXIT
 DISCHARGE. THE LIFE SAFETY PLAN MEASURES TO THE RAMP
 BASE. IS THIS THE OUTSIDE? A DOOR IS SHOWN ADJACENT TO
 THE RAMP IN THE HALLWAY. COVERED WALKWAYS SHOULD BE
 INCLUDED IN PATH OF TRAVEL. FBC1002. PLAN SHOULD SHOW
 WHERE THE OCCUPANT WILL LEAVE THE BUILDING (INCLUDING
 COVERED WALKWAYS).
  
 20. DOES THE BUILDING HAVE A FIRE ALARM? SEE
 FBC11-4.28. NOTE THAT A VISUAL SIGNAL IS REQUIRED IN
 THE RESTROOMS; NONE SHOWN.
  
 21. THE PROPOSED CHANGE OF DOOR SWING APPEARS TO
 INTERFERE WITH THE DOOR SWING OF THE ADJACENT DOOR,
 FBC1008. PLEASE REVISE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-16 Cont ID  
Sent By dpalmer Date 2009-01-16 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2009-01-16 Time 11:29 Sent To  
Notes
2009-01-16 11:30:53** DENIED PLANS**
  
  
  
  
 1) NOTE: THE OCCUPANCY CLASSIFICATION IS STILL IN
 QUESTION. IT IS THE UNDERSTANDING OF THIS OFFICE THAT
 THIS WILL BE USED AS AN ADULT DAY CARE USE, NOT
 EDUCATION A-3).
 USE FOR POSSIBLE ALZHEIMER PATIENTS IS NOT EDUCATION
 SEE FBC CHAPTER 3 (GROUP *D*) CHAPTER 4, LS 101 CHAPTER
 16.
 PLEASE PROVIDE LETTER FROM OWNER AND DESIGNER WHICH
 COORDINATES WITH THE PLANS STATING THE INTENDED USE.
 ONCE THIS HAS BEEN FINALIZED REVIEW STATUS WILL BE
 REVISED.
 LETTERS FROM OWNER AND DESIGNER NEED TO BE ORIGINAL AND
 NOTARIZED CORRECTLY.
  
 FBC EXISTING: 801.2 PARTIAL CHANGE OF OCCUPANCY GROUP.
 WHERE A PORTION OF AN EXISTING BUILDING IS CHANGED TO A
 NEW OCCUPANCY GROUP, SECTION 812 SHALL APPLY.
 13-101.3,808.3,808.1.
  
  
 AS THE INTENDED USE IS NOT YET DETERMINED FOR FINAL
 REVIEW OF PLANS, SOME CHANGES MAY OR MAY NOT BE NEEDED.
  
  
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-25 Cont ID  
Sent By dpalmer Date 2008-11-25 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2008-11-25 Time 11:27 Sent To  
Notes
2008-11-25 11:28:00 
  
  
  
  
 ** FAILED REVIEW **
  
  
  
 1) NOTE: A CALLED WAS PLACED TO RON GILMAN WHO IS THE
 ELECTRICAL ENGINEER OF RECORD FOR PROJECT. THE NEW
 ELECTRICAL PANEL AND EXISTING DISCONNECTS NEED TO BE
 VERIFIED IF THEY CONTAIN A LOCKING TYPE COVER FOR THE
 OCCUPANCY ALONG WITH A LOCKING COVER FOR THE
 DISCONNECT.
 THERE MAY BE SOME OTHER OPTIONS SUCH AS A SHORT WALL
 WITH A LOCKING DOOR OF SOME TYPE GIVING THE CLEARANCE
 REQUIREMENTS PER 110.26, 240.24
 ENGINEER WAS GOING TO LOOK INTO OPTIONS AND CONTACT THE
 ARCHITECT.
  
 2) NOTE: NEED EQUIPMENT GROUNDING CONDUCTOR FROM
 DISCONNECT TO NEW PANEL.
 250.110,250.122
  
 3) NOTE: PLEASE SEE 422.30, 422.31 AS THE WATER HEATER
 REQUIRES A DISCONNECT. THE PLANS SHOW A RECEPTACLE
 WHICH IS NOT PERMITTED.
  
 4) NOTE: OCCUPANCY FOR INTENDED USE WILL NEED TO BE ON
 PLANS PER FBC CHAPTER 3, 303.1
  
 5) NOTE: PLEASE SEE THE ARCHITECTURAL PLANS WHICH CALL
 FOR TWO NEW ELECTRICAL PANELS. PLEASE COORDINATE.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-01-27 Cont ID  
Sent By mcarsill Date 2009-01-27 Time 09:15 Rev Time 0.00
Received By mcarsill Date 2009-01-27 Time 09:09 Sent To  
Notes
2009-01-27 09:15:271) IT APPEARS THAT RESPONSES HAVE BEEN PROVIDED TO
 PREVIOUS COMMENTS MADE BY THE FIRE RESCUE DEPARTMENT.
  
 2) NOTE # 3 BELOW DOOR SCHEDULE INDICATES ON PAGE A-1
 THAT "EXISTING GATES DESIGNATED TO BE PART OF AN EGRESS
 SYSTEM SHALL REMAIN UNLOCKED OR AUTOMATICALLY UNLOCK IN
 CASE OF FIRE DURING HOURS OF OPERATION". HOW DOES THIS
 AUTOMATIC UNLOCKING OCCUR.
  
 3) ON PAGE A-3 IT HAS BEEN DECLARED THAT OCCUPANT
 ACTIVITIES WILL INLCUDE "ADULT EDUCATION AND RELIGIOUS
 ACCESSORY USE". SOME INFORMATION SUGGESTS THAT THESE
 FACILITIES MAY BE USED FOR AN ADULT DAY CARE AND IS NOT
 DECLEARED ON THE PLANS. THIS INFORMATION IF TRUE NEEDS
 TO BE DECLARED ON THE PLANS. THE MINIMUM BUILDING AND
 FIRE CODE REQURIEMENTS SHALL BE MET FOR THE SPECIFIC
 OCCUPANCY TYPE AND USE. THE BUILDING AND ELECTRICAL
 PLAN REVIEWERS HAVE BOT DENIED THESE REVISED PLANS.
 PLEASE REVISE PLANS ACCORDINGLY AND ENSURE THAT ALL
 INFORMATION HAS BEEN PROVIDED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-12-04 Cont ID  
Sent By mcarsill Date 2008-12-04 Time 07:41 Rev Time 0.00
Received By mcarsill Date 2008-12-04 Time 07:34 Sent To  
Notes
2008-12-04 07:41:10MEMORIAL PRESBYTERION CHURCH
 1300 SOUTH OLIVE AVENUE
  
 1. PLEASE DECLARE USED OF THESE CLASSROOMS. WHAT TYPES
 OF ACTIVITIES, AGE OF STUDENTS, AND THE DURATION OF
 TIME THESE STUDENTS WILL RECEIVE INSTRUCTION.
  
 2. PLEASE ILLUSTRATE ON THE PLANS THE LOCATIONS OF ANY
 FIRE SAFETY EQUIPMENT CONTAINED IN THE BUILDING. THIS
 EQUIPMENT WOULD INCLUDE ILLUMINATED EXIT SIGNS,
 EMERGENCY LIGHTING FIXTURES, PORTABLE FIRE
 EXTINGUISHERS, FIRE SPRINKLER SYSTEMS, OR FIRE ALARM
 EQUIPMENT.
  
 3. PLEASE INDICATE EXISTING INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 4. PLEASE INDICATE EXIT DISCHARGE LOCATIONS.
  
 5. PLEASE PROVIDE AN EXPECTED OCCUPANT LOADS FOR THE
 OCCUPANT LOADS FOR THE EDUCATIONAL PORTIONS OF THE
 BUILDING.
  
 6. INFORMATION NEEDED FOR ANY EXISTING OR NEW DOOR
 HARDWARE TO INLCUDE COURTYARD GATES. PLEASE FURTHER
 ADVISE WHAT TYPE OF LOCKING ARRANGEMENTS EXIST FOR THE
 CLOSET DOORS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-07 Cont ID  
Sent By adarroug Date 2009-01-07 Time 16:44 Rev Time 0.00
Received By adarroug Date 2009-01-07 Time 16:44 Sent To  
Notes
2009-01-07 16:44:45TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-04 Cont ID  
Sent By mawillia Date 2008-12-04 Time 10:54 Rev Time 0.00
Received By mawillia Date 2008-11-07 Time 10:42 Sent To  
Notes
2008-11-07 11:01:21TO "COMM" BD#22

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 16:43 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 16:38 Sent To PC
Notes
2009-02-15 16:43:02BASED ON THE RECONFIGURED SPACE AND PROPOSED USE
 (CLASSIFICATION AS ADULT DAY CARE) AND BASED ON THE
 REQUIREMENTS OF FBC-EB 609.1 AND FBC-EB 809.1,
 ALTERATIONS OR ADDITIONS TO THE EXISTING MECHANICAL
 SYSTEMS ARE NOT REQUIRED FOR CODE COMPLIANCE. UNLESS
 SPECIFIC MECHANICAL WORK IS BEING PERFORMED AS PART OF
 THE ALTERATION, NO MECHANICAL PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 16:18 Rev Time 0.25
Received By tgordon Date 2008-11-07 Time 16:18 Sent To  
Notes
2008-11-07 16:18:47NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-30 Cont ID  
Sent By kstevens Date 2009-01-30 Time 15:48 Rev Time 0.00
Received By kstevens Date 2009-01-30 Time 15:48 Sent To  
Notes
2009-01-30 15:58:02DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1, OK
 2. OK
 3. OK
  
 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE
 WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN
 THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE
 THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL
 LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN
 CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2
 & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH
 REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED
 DRINKING FOUNTAINS?
 ****RESPONSE NOTED, BUT COMMENT CONCERNING MINIMUM
 FACILITIES HAS NOT BEEN ADDRESSED. PER THE SQUARE
 FOOTAGE INDICATED, (5556SF)), AND THE 15 NET PER SF THE
 MINIMUM FACILITIES ARE 2 WATER CLOSETS FOR MALE AND 3
 WATER CLOSETS FOR FEMALE, 2 DRINKING FOUNTAINS, AND A
 SERVICE SINK. PLEASE INDICTE THE LOCATION OF ALL
 REQUIRED FIXTURES. TABLES 1004.1.2 & 403.1.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 *********NEW COMMENT**********
  
 1B. ROOM 110 INDICATES A NEW SINK. PER SECTION 11-4.24
 THE SINK SHALL BE ACCESSIBLE. PLEASE SUBMIT A
 DETAIL/ELEVATION FOR THE SINK SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS. (FORWARD APPROACH
 REQUIRED, CABINET DOORS NOT APPROVED IN CLEAR FLOOR
 SPACE).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-12-02 Cont ID  
Sent By kstevens Date 2008-12-02 Time 15:43 Rev Time 0.00
Received By kstevens Date 2008-12-02 Time 15:43 Sent To  
Notes
2008-12-02 16:56:07DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1, ALL SHEETS SEALED BY THE ARCHITECT OF RECORD ARE
 REQUIRED TO HAVE THE SIGNATURE OF THE DESIGN
 PROFESSIONAL. IT APPEARS THAT INITIALS HAVE BEEN USED
 IN PLACE OF THE SIGNATURE. IF THE INITIALS ARE INDEED
 THE LEGAL SIGNATURE OF THE DESIGN PROFESSIONAL, THEN A
 SIGNED, SEALED, NOTORIZED LETTER INDICATING THE LEGAL
 SIGNATURE OF THE ARCHITECT SHALL BE SUBMITTED FOR OUR
 RECORDS. FAC 61G1-16.003, 61G1-16.004(5) & FS 481.2055.
  
 2. SUBMIT AN EXISTING FLOOR PLAN SO THE EXTENT OF THE
 WORK INDICATED CAN BE VERIFIED. SECTION 106.1.2.
  
 3. SHT A-1 SHOW THE ROOM NUMBERS THAT CORRESPOND TO THE
 ROOMS INDICATED ON THE APPLICATION FOR PERMIT. SECTIONS
 106.1.1 & 106.1.2.
  
 4. SHT A-1 TOILET ROOMS SHOW IMAGES OF W/C'S IN THE
 WOMEN'S AND MEN'S TOILET ROOMS AND AN IMAGE OF A LAV IN
 THE MEN'S TOILET SUPERIMPOSED OVER THE W/C AND LAV. ARE
 THE FIXTURES BEING DELETED OR MOVED FROM THERE ORIGINAL
 LOCATION? PLEASE CLARIFY. IF FIXTURES ARE DELETED THEN
 CALCULATION FOR MINIMUM FACILITIES PER TABLES 1004.1.2
 & 403.1 ARE REQUIRED TO INDICATE COMPLIANCE WITH
 REQUIRED FIXTURES. SECTION 106.1.1. ARE THERE REQUIRED
 DRINKING FOUNTAINS?
  
 5. SHT A-1 INDICATES CODE REQUIREMENTS WITH 2006
 REVISIONS. CODE SHALL ALSO INCLUDE THE 2007 REVISIONS
 AS WELL AS THE 2005 REVISIONS. SECTION 106.1.1.
  
 6. INDICATE THE LEVEL OF ALTERATION AS REQUIRE IN
 SECTION 301 OF THE EXISTING BUILDING CODE.
  
 7. SHT A-1 INDICATES 4 ABANDONED GAS BASE BOARD HEATERS
 AND A NEW 30 GALLON GAS WATER HEATER. A SEPARATE GAS
 PERMIT IS REQUIRED THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 8. SHT P-1 THE SANITARY RISER DIAGRAM SHOWS AN EXISTING
 W/C & LAV BY THE CLASSROOM SINK THAT IS NOT SHOWN ON
 THE FLOOR PLAN. PLEASE CLARIFY. SHOW THE EXISTING
 TOILET ROOM ON THE FLOOR PLAN. SECTIONS 106.1.1,
 106.1.2 & 701.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved