Plan Review Details - Permit 08110006
Plan Review Stops For Permit 08110006
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-01-27 Cont ID  
Sent By shill Date 2009-01-27 Time 14:36 Rev Time 0.00
Received By shill Date 2009-01-27 Time 14:36 Sent To  
Notes
2009-01-27 14:36:58REVISION A5 DATED 1/20/9

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-22 Cont ID  
Sent By shill Date 2009-01-22 Time 09:08 Rev Time 0.00
Received By shill Date 2009-01-22 Time 09:08 Sent To  
Notes
2009-01-22 09:09:47REVISION #3 SHEETS A1, A2, A3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-14 Cont ID  
Sent By shill Date 2009-01-14 Time 09:45 Rev Time  
Received By shill Date 2009-01-13 Time 16:16 Sent To  
Notes
2009-01-14 10:26:10****CORRECTIONS****
 ****REVISED 1/16/9****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. A NOTE HAS BEEN ADDED TO THE UL ASSEMBLY, "OPTIONAL
 CONT. CAULKING". PLEASE SHOW HOW THE RATED WALLS WILL
 COMPLY WITH FBC708.4 OR FBC706.4 CONTINUITY. RATED
 WALLS NOT NOTED AS FIRE PARTITIONS OR FIRE BARRIERS.
  
 2. THE PURPOSE, CONSTRUCTION, AND LOCATION OF DETAIL 22
 IS NOT CLEAR BASED ON THE INFORMATION PROVIDED. IT IS
 MY UNDERSTANDING THAT THIS DETAIL IS TO ADDRESS THE
 REQUIREMENT FOR SUPPORTS AT 4' OC FOR FULL HEIGHT FIRE
 RATED WALLS WHICH ARE STRUCTURALLY UNSUPPORTED AT THE
 TOP OF THE WALL. THE PURPOSE OF THE DETAIL IS NOT
 CLEAR; IT NOTES CATS AT 4' OC. FIRE RATED WALLS SHOULD
 HAVE A HEAD OF WALL DETAIL SPECIFIED FOR FIRE
 RESISTANCE. STRUCTURAL SUPPORT DETAILS SHOULD BE NOTED
 AS SUCH AND MATERIALS USED AND FASTENING SHOULD BE
 STATED PLEASE REVISE, FBC*106, FBC708, FBC16.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 17:58 Rev Time 0.00
Received By shill Date 2008-11-19 Time 17:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 09:44 Sent To  
Notes
2009-01-29 09:45:16PLAN BROUGHT IN BY BRIAN, STAMPED. OK

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-01-16 Cont ID  
Sent By dpalmer Date 2009-01-16 Time 08:25 Rev Time 0.00
Received By dpalmer Date 2009-01-16 Time 08:25 Sent To PC
Notes
2009-01-16 08:25:36** DENIED PLANS**
  
  
 1) NOTE: PLEASE SEE ROOM #902. NEED LIGHTING CONTROLS
 PER 13-415.1.ABC.1, .1.2. THIS IS A SEPARATE SPACE.
 ONLY STANDARD SWITCHES ARE SHOWN. PLEASE REVISE.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-30 Cont ID  
Sent By dpalmer Date 2008-12-30 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2008-12-30 Time 16:52 Sent To  
Notes
2008-12-30 16:54:38** DENIED REVIEW **
  
  
 ** SHEET E3.1 AND 4.1 WERE OK.
 REDLINED: WIRING METHOD ALLOWED BY NEC 645 ARE NOT
 PERMITTED IN THE PHONE ROOM. CHAPTERS 1-4 APPLY ON
 WIRING.
  
 1) NOTE: PLEASE SEE ROOM 902 IS MISSING CONTROLS PER
 FBC 13-415.1.ABC.1.1, .1.2. THIS WAS NOT ON PREVIOUS
 REVIEWED PLANS. PLEASE SHOW CONTROLS PER SECTIONS FOR
 CONFERENCE ROOMS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By dpalmer Date 2008-12-02 Time 11:18 Rev Time 0.00
Received By dpalmer Date 2008-12-02 Time 11:18 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-10 Cont ID  
Sent By dpalmer Date 2008-11-10 Time 13:53 Rev Time 0.00
Received By dpalmer Date 2008-11-10 Time 13:53 Sent To  
Notes
2008-11-10 13:53:47 
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2,13-415.2.ABC.1.1,.1.2.
 PLEASE SEE THE LPC SUBMITTED DO NOT COORDINATE WITH
 PLANS AND FIXTURE LEGEND. PLEASE SEE THE FIXTURE LEGEND
 AND THE WATTAGES SHOWN. PLEASE SEE THE CALCULATIONS
 SUBMITTED ONLY INDICATE TWO FIXTURES.
  
 2) NOTE: PLEASE SEE 408.36, 240.21 AND 310.16 AS THE
 TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER CURRENT
 PROTECTION.
  
 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%.
 230.42,215.3 ETC.
 PLEASE SEE 422.13 FOR ANY STORAGE TYPE WATER HEATERS.
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-22 Cont ID  
Sent By mwennerg Date 2009-01-22 Time 13:38 Rev Time 0.00
Received By mwennerg Date 2009-01-22 Time 13:38 Sent To  
Notes
2009-01-22 13:39:34REVISION #3 DATED 12/19/09.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-11-14 Cont ID  
Sent By mwennerg Date 2008-11-14 Time 14:38 Rev Time 0.00
Received By mwennerg Date 2008-11-14 Time 14:38 Sent To  
Notes
2008-11-14 14:39:35SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-22 Cont ID  
Sent By adarroug Date 2009-01-22 Time 10:14 Rev Time 0.00
Received By adarroug Date 2009-01-22 Time 10:14 Sent To B
Notes
2009-01-22 10:14:54TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-07 Cont ID  
Sent By adarroug Date 2009-01-07 Time 14:58 Rev Time 0.00
Received By adarroug Date 2009-01-07 Time 14:58 Sent To E
Notes
2009-01-07 14:59:21TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-05 Cont ID  
Sent By adarroug Date 2009-01-05 Time 10:51 Rev Time 0.00
Received By adarroug Date 2009-01-05 Time 10:51 Sent To B
Notes
2009-01-05 10:51:44TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-29 Cont ID  
Sent By adarroug Date 2008-12-29 Time 09:16 Rev Time 0.00
Received By adarroug Date 2008-12-29 Time 09:16 Sent To  
Notes
2008-12-29 09:21:15TO "COMM" BD#57

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 10:45 Sent To E
Notes
2008-11-26 10:46:03TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-19 Cont ID  
Sent By shill Date 2008-11-19 Time 17:58 Rev Time 0.00
Received By shill Date 2008-11-04 Time 08:20 Sent To  
Notes
2008-11-04 08:27:19TO "COMM" BD#34

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 11:28 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 11:28 Sent To PC
Notes
2009-02-01 11:28:53REVISED M2.1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-11-05 Cont ID  
Sent By tgordon Date 2008-11-05 Time 16:38 Rev Time 1.30
Received By tgordon Date 2008-11-05 Time 16:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-01-29 Cont ID  
Sent By kstevens Date 2009-01-29 Time 15:54 Rev Time 0.00
Received By kstevens Date 2009-01-29 Time 15:54 Sent To  
Notes
2009-01-29 15:54:32REVISION OK -- SHT P2.1.

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-11-19 Cont ID  
Sent By kstevens Date 2008-11-19 Time 13:44 Rev Time 0.00
Received By kstevens Date 2008-11-19 Time 13:44 Sent To  
Notes
***NONE***