Plan Review Details - Permit 08100688
Plan Review Stops For Permit 08100688
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jgomez Date 2008-11-04 Time 13:50 Rev Time 0.00
Received By jgomez Date 2008-11-04 Time 13:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By jgomez Date 2008-11-04 Time 08:57 Rev Time 0.00
Received By jgomez Date 2008-11-04 Time 08:57 Sent To PC
Notes
2008-11-04 09:01:18RESIDENTIAL (R3) SHUTTERS BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007
 REVISIONS.
  
 1- INSTALLATION SCHEDULE INDICATES THE MINIMUM EDGE
 DISTANCE TO BE 3". ANCHOR SCHEDULES ON SHEETS 13 AND 14
 ARE FOR 3 1/2" EDGE DISTANCE. NEED TO REDUCE ANCHOR
 SPACING AS REQUIRED BY EDGE DISTANCE VERSUS SPACING FOR
 ANCHORS TABLE ON SHEET 14. REVISE AS REQUIRED.
 ***NOTES: A) EDGE DISTANCE EXCLUDES STUCCO FINISH. B)
 COORDINATE PANEL SPAN COLUMN WITH EDGE DISTANCE COLUMN.
  
 2- TYPE OF TAPCON TO BE USED TO MATCH TYPE OF TAPCON
 SPECIFIED ON STORM SHUTTERS DRAWINGS SHEET 14.
  
 3- OPENING #4 CALLS FOR CONNECTION TYPE "E" AT BOTTOM.
 DRAWINGS SUBMITTED ARE HIGHLIGHTING CONNECTION TYPE "I"
 ON SHEET 7. CLARIFY WHICH IS THE ACTUAL CONNECTION TYPE
 THAT IS GOING TO BE USED TO AVOID CONFLICTS.
 ***NOTE: CHECK ANCHOR SPACING FOR CONNECTION TYPE "E".
 ALSO, COORDINATE SPACING WITH ITEM #1 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-04 Cont ID  
Sent By jgomez Date 2008-11-04 Time 10:25 Rev Time 0.00
Received By jgomez Date 2008-11-03 Time 11:24 Sent To  
Notes
2008-11-03 11:24:48TO "JGOMEZ" DESK/DHCD PROJECT