Plan Review Details - Permit 08100660
Plan Review Stops For Permit 08100660 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-02-04 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2009-02-04 |
Time |
12:41 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2009-02-04 |
Time |
10:15 |
Sent To |
PC |
|
Notes |
2009-02-04 10:30:08 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007 | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ADDRESS ON THE PLAN DOES NOT MATCH THE ADDRESS | | ON THE APPLICATION, CORRELATE SAME. 106.1 FBC | | | | 2} THE PLAN SUBMITTED DOES NOT SEEM TO BE THE SAME PLAN | | AS WAS SUBMITTED 11/14/08 AS THE COMMENTS MADE DO NOT | | RELATE TO THIS PLAN.SEE COMMENT #1. | | | | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON A SITE OR | | FLOOR PLAN, METER ENCLOSURE, DISCONNECTS AND PANELS, SO | | THAT COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE | | REVIEWED. A DISCONNECT MAY BE REQUIRED PER | | 230.70(A)(1). | | | | 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.*** THIS | | COMMENT IS MADE BECAUSE THE NEW PANEL WITH WOULD BE | | SUBJECT TO LINE FAULT CURRENT AS THE FIRST MEANS OF | | DISCONNECT. | | | | 5} PROVIDE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | EQUIPMENT TO BE INSTALLED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561/805-6718 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-11-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-11-18 |
Time |
08:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-11-18 |
Time |
08:42 |
Sent To |
PC |
|
Notes |
2008-11-18 08:43:03 | | | | | | | ** FAILED REVIEW ** | | | | | | 1) NOTE: PLEASE INDICATE THE LOCATION OF THE PANEL. | | 110.26,240.24, 408.36 | | | | 2) NOTE: PLANS SUBMITTED CONTAIN A TITLE BLOCK FROM AN | | ENGINEERING FIRM. PLANS MUST BE SIGNED, DATED AND | | SEALED FORM THAT ENGINEERING FIRM PER FS 471.025, FAC | | 61G15-23.002. | | | | 3) NOTE: MISSING EQUIPMENT GROUNDING AFTER THE FIRST | | MEANS OF DISCONNECT PER 250.110,250.122. | | | | 4) NOTE: NEEDS TO HAVE TWO GROUND RODS. 250.50, 250.56 | | | | 5) NOTE: RISER INDICATES AN OVER HEAD SERVICE HOWEVER | | THE NOTE ON RISER MENTIONS TO BASE OF POLE WHICH WOULD | | LEND TO AN UNDERGROUND SERVICE. | | PLEASE COORDINATE WHICH ONE IT WILL BE AND REVISE AS | | NEEDED. | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
|