Plan Review Details - Permit 08100611
Plan Review Stops For Permit 08100611
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-02-03 Cont ID  
Sent By mjacobs Date 2009-02-03 Time 13:47 Rev Time 0.00
Received By mjacobs Date 2009-02-03 Time 13:47 Sent To PC
Notes
2009-02-03 13:47:372/3/09 REVISION #2 TO SHEET A-1, CHANGE WALL TYPE (B)
 TO WALL TYPE (C)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-12 Cont ID  
Sent By mjacobs Date 2009-01-12 Time 16:29 Rev Time 0.00
Received By mjacobs Date 2009-01-12 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By mjacobs Date 2008-11-04 Time 07:14 Rev Time 0.00
Received By mjacobs Date 2008-11-04 Time 07:14 Sent To  
Notes
2008-11-04 07:14:12BUILDING PLAN REVIEW
 PERMIT: 08100611
 ADD: 1450 CENTRE PARK BLVD
 CONT: FISHER CONTRACTING CORP
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-03-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5) NOW THE SPACE IS BEING ALTERED, SHOW THE LAYOUT OF
 THE SPRINKLER HEADS IN RELATION TO THE NEW ROOMS AND
 WALLS ADDED TO THE SPACE. THIS INFORMATION CAN BE SHOWN
 ON THE NEW REFLECTED CEILING PLANS. FBC 106.3.5.1.1(5)
 AND FS 553. 79(2).
  
 6) IT SEEMS AS IF ADDITIONAL SQUARE FOOTAGE IS ADDED TO
 A SPACE. IF THIS IS CORRECT, INDICATE THE NEW TOTAL
 SQUARE FOOTAGE OF SUITE #200 ALONG WITH THE OCCUPANT
 LOAD PER TABLE 1004.1.2.
  
 7) SHEET A-1 SHOWS TWO OR THREE DIFFERENT WALL TYPES
 FOR THE FILE/STORAGE ROOM, WHERE DOES WALL TYPE ?B? AND
 WALL TYPE ?C? ENDS FOR THE FILE ROOM? CLARIFY.
 8) SUBMIT A LIFE SAFETY PLAN SHOWING MEANS OF EGRESS,
 EXIT ACCESS, EXIT AND EXIT DISCHARGE. FBC
 106.3.5.1.1(7).
  
 9) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-19 Cont ID  
Sent By btrobaug Date 2009-02-19 Time 13:40 Rev Time 0.00
Received By btrobaug Date 2009-02-19 Time 13:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-01-08 Cont ID  
Sent By btrobaug Date 2009-01-08 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2009-01-08 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 09:59 Sent To  
Notes
2008-11-04 09:59:16 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE TITLE BLOCK IS INDICATING
 APPLIED DESIGN INITIATIVE LLC WHICH IS REQUIRED TO BE
 LICENSED IN THE STATE O FLORIDA PER FLORIDA STATUTES
 481.219. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 WHICH REQUIRES LICENSE NUMBER TO BE LISTED
 ON TITLE BLOCKS. IF THE WORK IS SOLELY THROUGH THE
 RESPONSIBLE ARCHITECT AS LISTED PLEASE EITHER INCLUDE
 LICENSING OR REMOVE FROM TITLE BLOCKS.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADE
 WHICH INDICATE THIS INFORMATION.
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES AS ADOPTED
 BY FS 553.73 ARE LISTED ON PLANS ACCORDINGLY. FOR
 EXAMPLE COVER SHEET INDICATES NFPA-70 ( NATIONAL
 ELECTRICAL CODE) AS THE 2002 EDITION. THIS CODE HAS NOT
 BEEN IN EFFECT IN THE STATE OF FLORIDA SINCE DECEMBER
 8TH, 2006.
 PLANS SHOULD NOTE AS FOLLOWS.
 2004 FBC W/ 2007 REVISIONS.
 2003 NFPA-101
 2002 NFPA-72
 2005 NFPA-70.
  
 ** SOME OF THESE ARE SHOWN ON ELECTRICAL PLANS HOWEVER
 COORDINATION WITH OTHER PLANS IS NEEDED.
  
 3) NOTE: PLEASE LIST THE MAXIMUM TIMES ON OCCUPANCY
 SENSORS/OVER RIDES AS NOTED ON SYMBOL LEGEND.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-01-15 Cont ID  
Sent By mwennerg Date 2009-01-15 Time 15:20 Rev Time 0.00
Received By mwennerg Date 2009-01-15 Time 15:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-06 Cont ID  
Sent By mwennerg Date 2008-11-06 Time 15:00 Rev Time 0.00
Received By mwennerg Date 2008-11-06 Time 15:00 Sent To P
Notes
2008-11-06 15:05:55***DENIED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM REMODEL.
  
 2) PLEASE SHOW FIRE SPRINKLER LAYOUT PF ALTERED AREAS.
 ADDITIONALLY, SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 3) ILLUSTRATE THE LOCATIONS OF REQUIRED 2A-10B,C RATED
 FIRE EXTINGUISHERS.
  
 4) JOB SITE TO BE CLEANED OF EXCESS DEBRIS DAILY OR
 MORE FREQUENTLY TO ENSURE SAFE OPERATION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 10:41 Rev Time 0.00
Received By adarroug Date 2009-02-17 Time 10:41 Sent To  
Notes
2009-02-17 10:42:14TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 08:39 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 08:39 Sent To B
Notes
2009-01-30 08:39:42TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 13:59 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 13:59 Sent To  
Notes
2009-01-06 14:00:12TO "BOB"#18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-07 Cont ID  
Sent By mperson Date 2008-11-07 Time 09:54 Rev Time 0.00
Received By mperson Date 2008-10-30 Time 10:19 Sent To PC
Notes
2008-10-30 12:27:31TO "BOB"#10

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-04 Cont ID  
Sent By rregueir Date 2009-03-04 Time 10:16 Rev Time 0.00
Received By rregueir Date 2009-03-04 Time 10:16 Sent To PC
Notes
2009-03-04 10:17:09PAGE M-1 REVISION #2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 14:21 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 14:21 Sent To PC
Notes
2009-01-24 14:21:42PLANS PREVIOUSLY REVIEWED AND STAMPED BY TOM GORDON
 HAVE BEEN RESTAMPED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-30 Cont ID  
Sent By tgordon Date 2008-10-30 Time 16:20 Rev Time 0.40
Received By tgordon Date 2008-10-30 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2009-01-09 Cont ID  
Sent By kstevens Date 2009-01-09 Time 16:20 Rev Time 0.00
Received By kstevens Date 2009-01-09 Time 16:20 Sent To  
Notes
2009-01-09 16:20:34NO PLUMBING WORK SHOWN OR INDICATED ON PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-07 Cont ID  
Sent By mperson Date 2008-11-07 Time 08:57 Rev Time 1.00
Received By mperson Date 2008-11-07 Time 08:57 Sent To I
Notes
2008-11-07 09:50:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. COVER SHEET IS INDICATING THE WRONG CODE CYCLE.
 PLEASE DECLARE THE CORRECT GOVERNING CODE (FBC-2004
 WITH 2007 REVISIONS). PER (W.P.B. AS AMENDED) SECTION
 106.5 RETENTION OF CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. SHEET L-3 SPECIFICATIONS, FOOD SERVICE NOTES (2)
 SCOPE OF WORK STATES THAT A WATER LINE WILL BE
 FURNISHED AND INSTALLED FOR A NEW REFRIGERATOR WITH ICE
 MAKER, FILTERED WATER COOLER, AND COFFEE MAKER HOWEVER
 THERE IS NO CLEAR LOCATION OF THESE ITEMS ON ANY PLAN
 SHEETS. PLEASE CLEARLY INDICATE THE LOCATION OF THESE
 ITEMS AND PROVIDE THE FOLLOWING PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.1.3, PLUMBING (3)(10)(13): AN ISOMETRIC
 POTABLE WATER RISER DIAGRAM IS REQUIRED FOR THE
 PROPOSED WORK FOR BOTH THE HOT AND COLD WATER
 INDICATING THE PIPE SIZES, VALVE LOCATIONS, LOCATION OF
 THE WATER SUPPLY LINE WITH BACKFLOW PREVENTER **608,
 THERMAL EXPANSION CONTROL FOR THE WATER HEATER (IF
 APPLICABLE) **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 4. PLEASE CLARIFY ON THE RESUBMITTAL IF THERE IS AN
 EXISTING DRINKING FOUNTAIN LOCATED IN THE COMMON AREA
 THAT IS ADA COMPLIANT OR IS THE WATER COOLER INDICATED
 ON SHEET L-3 THIS REQUIRED DRINKING FOUNTAIN PER
 FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES A DRINKING FOUNTAIN IS
 REQUIRED FOR A BUSSINESS OCCUPANCY (1 PER 100). PLEASE
 KNOW THAT IF THE WATER COOLER IS IN FACT THE REQUIRED
 DRINKING FOUNTAIN THE FOLLOWING IS REQUIRED PER THE
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]