Plan Review Details - Permit 08100604
Plan Review Stops For Permit 08100604
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-01-06 Cont ID  
Sent By rmcdouga Date 2009-01-06 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2009-01-06 Time 07:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-10 Cont ID  
Sent By rmcdouga Date 2008-11-10 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-11-10 Time 16:50 Sent To  
Notes
2008-11-10 16:50:232004 FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) THE CONSTRUCTION TYPE AND CODE EDITION SPECIFIED ON
 THE COVERSHEET ARE INCORRECT. SPECIFY THE 2004 FBC
 SECTION 602.5 AND TYPE V-B CONSTRUCTION.
  
 2) THE SCOPE OF WORK ON SHEET 1.1 SPECIFIES REPLACING 2
 WINDOWS AND ON SHEET 1.2 THREE WINDOWS ARE TO BE
 REPLACED. PLEASE CORRECT.
  
 3) THE BATHROOM WINDOW IS INCORRECTLY SPECIFIED AS AN
 EGRESS WINDOW ON THE WINDOW SCHEDULE ON SHEET 1.2.
 PLEASE CORRECT.
  
 4) THE NOA (03-0717.03) SPECIFIED FOR WINDOWS 2 AND 3
 IN THE WINDOW SCHEDULE IS EXPIRED. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 10:18 Rev Time 0.00
Received By btrobaug Date 2008-12-19 Time 10:04 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-05 Cont ID  
Sent By btrobaug Date 2008-11-05 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2008-11-05 Time 10:07 Sent To P
Notes
2008-11-05 10:23:02 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA RESIDENTIAL BUILDING CODE, 2007
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE SERVICE ON SHEET 4.1 IS SHOWN AS AN EXISTING BUT
 MUST BE CORRECTED AS IT IS A LIFE SAFETY ISSUE. THERE
 IS A GROUNDING ELECTRODE CONDUCTOR AT THE METER AND A
 GROUNDING ELECTRODE SYSTEM SHOWN AT THE PANEL WITH A
 DISCONNECT IN BETWEEN THE TWO IN VIOLATION OF
 250.24(A)(5) LOAD-SIDE GROUNDING CONNECTIONS A
 GROUNDING CONNECTION SHALL NOT BE MADE TO ANY GROUNDED
 CONDUCTOR ON THE LOAD SIDE OF THE SERVICE DISCONNECTING
 MEANS EXCEPT AS OTHERWISE PERMITTED IN THIS ARTICLE.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225, 240 AND 230 CAN BE
 REVIEWED.
  
 3} INDICATE HOW THE EQUIPMENT GROUND IS RAN AND WHERE
 IT ORIGINATES, ON THE SERVICE RISER DIAGRAM SEE COMMENT
 #1
  
 4} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE NOTE #2 TO REFLECT THIS
 CHANGE.
  
 5} ELECTRICAL NOTE #3 IS INCORRECT REGARDING GFCI
 PROTECTION AT THE SINK***210.8(A) DWELLING UNITS ALL
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (6) KITCHENS ? WHERE THE RECEPTACLES ARE
 INSTALLED TO SERVE THE COUNTERTOP SURFACES. PLEASE
 CORRECT.
  
 6} ELECTRICAL NOTE #4 REGARDING THE CIRCUITING FOR
 SMOKE ALARMS IS NOT A VIOLATION BUT IT SHOULD BE NOTED
 THAT THE CIRCUIT MUST COMPLY WITH 210.12 AND BE AFCI
 PROTECTED. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 7} BEDROOM #3 MUST COMPLY WITH 210.12, NOTE SAME ON THE
 PLANS.
  
 8} IF THE CONDENSING UNIT IS BEING REPLACED TO MATCH
 THE AHU, LOCATE SAME ON PLANS, ALSO SHOW COMPLIANCE
 WITH THE REQUIRED DISCONNECT PER 440.14, RECEPTACLE PER
 210.63.
  
 9} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE. 61G15-23.002 SEAL, SIGNATURE AND
 DATE SHALL BE AFFIXED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-15 Cont ID  
Sent By adarroug Date 2008-12-15 Time 16:22 Rev Time 0.00
Received By adarroug Date 2008-12-15 Time 16:22 Sent To E
Notes
2008-12-15 16:23:05TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-10 Cont ID  
Sent By rmcdouga Date 2008-11-10 Time 16:50 Rev Time 0.00
Received By rmcdouga Date 2008-10-29 Time 14:15 Sent To  
Notes
2008-10-29 14:24:17TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 13:00 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 13:00 Sent To AD
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-30 Cont ID  
Sent By tgordon Date 2008-10-30 Time 09:37 Rev Time 0.40
Received By tgordon Date 2008-10-30 Time 09:37 Sent To E
Notes
2008-10-30 09:57:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW ON A/C PLAN 3.1 HOW THE AIR HANDLER IS TO BE
 SERVICED WHEN THERE IS NO DOOR TO THE AREA. SEE 2004
 FBC/R M1305.1 AND M1601.3.3.
  
 2) PLAN 3.1 STATES REMOVE AND REPLACE EXISTING DUCTS IN
 ALL HOUSE. PLEASE SHOW THE DUCT DESIGN WITH ALL SIZES
 SUPPLY AND RETURN ALSO THE CFM'S, PER 2004 FBC /R
 M1601.1 AND FBC 13-610.1.ABC.1 AND WPB AMEND. 106.3.5.4
 (10). SEE 2004 FBC/R M1602.4 REGARDING RETURN AIR
 REQUIREMENTS.
  
 3) SHOW ON PLAN AN EQUIPMENT SCHEDULE FOR EQUIPMENT
 BEING REPLACED AIR HANDLER (AND CONDENSER UNIT IF BEING
 REPLACED), PER 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-11-05 Cont ID  
Sent By mperson Date 2008-11-05 Time 14:15 Rev Time 0.15
Received By mperson Date 2008-11-05 Time 14:15 Sent To B
Notes
2008-11-05 14:19:46NOTE: THERE IS NO PROPOSED PLUMBING WORK BEING
 INDICATED ON SUBMITTED PLANS OR A PLUMBING PERMIT BEING
 APPLIED FOR AT THIS TIME. *MRPERSON.