Plan Review Details - Permit 08100531
Plan Review Stops For Permit 08100531
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By mjacobs Date 2009-04-08 Time 12:20 Rev Time 0.00
Received By mjacobs Date 2009-04-08 Time 12:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-04-08 Cont ID  
Sent By mjacobs Date 2009-03-09 Time 09:17 Rev Time 0.00
Received By mjacobs Date 2009-03-09 Time 07:44 Sent To  
Notes
2009-03-09 09:17:22BUILDING PLAN REVIEW
 PERMIT: 08100531
 ADD: 1118 25TH STREET #7
 CONT: COMPLETE PROPERTY MANAGEMENT INC.
 TEL: (561)626-2778
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3/9/09
 REVIEW: 2NDT
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) OK
 4) OK
  
 5) MEZZANINE DELETED FROM DRAWINGS.
  
 6) THE DRAWINGS NEED TO CLEARLY INDICATE THE TYPE OF
 BUILDING PER CHAPTER 6 AND TABLE 503 AND THE USE AND
 OCCUPANCY PER CHAPTER 3. THE PLANS SHOW AN OCCUPANT
 LOAD OF 25 PERSONS. NOTE: THE OFFICE AREAS AND THE
 WAREHOUSE/STORAGE AREA SHALL BE CALCULATED ACCORDING
 THE DESIGN OCCUPANT LOAD PER TABLE 1004.1.2. IS
 OCCUPANCY TYPE S1 / F1 AND BUSINESS AS INDICATED?
  
 7) MEZZANINE DELETED FROM DRAWINGS.
 8) MEZZANINE DELETED FROM DRAWINGS.
  
 9) PROVIDE AN EXISTING FLOOR PLAN OF THE EXISTING AREA
 AND A PROPOSED FLOOR PLAN.
  
 10) MEZZANINE DELETED FROM DRAWINGS.
 11) MEZZANINE DELETED FROM DRAWINGS.
  
 12) DETAIL #3 IS MISSING FROM THE PLANS. SUBMIT A
 DETAIL CEILING FRAMING DRAWING SHOWING ALL MATERIALS
 AND FASTENERS ALONG WITH THE TYPE OF STUDS AND SPACING.
  
 13) MEZZANINE DELETED FROM DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-11-03 Cont ID  
Sent By mjacobs Date 2008-11-03 Time 10:49 Rev Time 0.00
Received By mjacobs Date 2008-11-03 Time 10:49 Sent To  
Notes
2008-10-31 17:00:10BUILDING PLAN REVIEW
 PERMIT: 08100531
 ADD: 1118 25TH STREET #7
 CONT: COMPLETE PROPERTY MANAGEMENT INC.
 TEL: (561)626-2778
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-31-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 4) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE INDICATED ON THE DRAWINGS.
  
 5) THE INFORMATION FOR THE BUILDING IS NOT LEGIBLE
 106.1.1. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE & EXTENT OF
 THE WORK PROPOSED & SHOW IN DETAIL THAT IT WILL CONFORM
 TO THE PROVISIONS OF THIS CODE AND RELEVANT LAWS,
 ORDINANCES, AND RULES AND REGULATIONS AS DETERMINED BY
 THE BUILDING OFFICIAL. INDICATE THE SQUARE FOOTAGE OF
 THE SPACE AND THE AREA OF THE MEZZANINE.
  
 6) THE DRAWINGS NEED TO CLEARLY INDICATE THE TYPE OF
 BUILDING PER CHAPTER 6 AND TABLE 503 AND THE USE AND
 OCCUPANCY PER CHAPTER 3.
  
 7) THE CLEAR HEIGHT ABOVE AND BELOW THE MEZZANINE FLOOR
 CONSTRUCTION SHALL NOT BE LESS THAN 7 FEET. FBC 505.1
 SHOWS COMPLIANCE. THE AGGREGATE AREA OF THE MEZZANINE
 WITHIN A ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF
 THE ROOM OR SPACE IN WHICH THEY ARE LOCATED. FBC 502.2
  
 8) PLEASE INDICATE THE OCCUPANT LOAD OF THE MEZZANINE
 AND THE ENTIRE SPACE ON THE DRAWINGS PER 505.4 TABLE
 1004.1.2 AND TABLE 1607.1
  
 9) PROVIDE AN EXISTING FLOOR PLAN OF THE EXISTING AREA
 AND A PROPOSED FLOOR PLAN WITH ALL ELEVATION OF THE NEW
 AREA INCLUDING THE FRONT AND SIDES ELEVATIONS.
  
 10) 110.4.2 STORAGE & FACTORY- INDUS-TRIAL OCCUPANCIES.
 IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT, PROPRIETOR OR
 OCCUPANT OF GROUP S AND GROUP F OCCUPANCIES, OR ANY
 OCCUPANCY WHERE EXCESSIVE FLOOR LOADING IS LIKELY TO
 OCCUR, TO EMPLOY A COMPETENT ARCHITECT OR ENGINEER IN
 COMPUTING THE SAFE FLOOR LOAD CAPACITY. ALL SUCH
 COMPUTATIONS SHALL BE ACCOMPANIED BY AN AFFIDAVIT FROM
 THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN
 POUNDS PER SQ FT. THE COMPUTATIONS & AFFIDAVIT SHALL BE
 FILED AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 11) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART
 OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS
 PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE
 BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON
 PLATES OF APPROVED DESIGN WHICH SHALL BE SUPPLIED &
 SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A
 CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT BE REMOVED OR
 DEFACED, & IF LOST, REMOVED THE OWNER OF THE BUILDING
 SHALL REPLACE THEM. PLEASE SEE FBC 1603.3 FOR MORE
 INFORMATION.
  
 12) DETAIL #3 FAILS TO INDICATE THE ATTACHMENT DETAIL
 FOR THE FLOOR JOISTS. STATE THE TYPE OF CONNECTIONS FOR
 THE FLOOR JOISTS TO THE LEDGER AND THE OUTER WALL.
 INDICATE THE GRADE AND SPECIES OF THE FLOOR JOISTS ON
 THE PLANS PER FBC 2308.8. THE PLANS FAIL TO SHOW
 COLUMNS AND WALLS SUPPORTING THE MEZZANINE. THE
 CONNECTION DETAIL FOR THE GUARDRAIL IS ALSO REQUIRED.
  
 13) IS THE STAIRWAY BEING ENCLOSED? IF SO, THIS WILL
 MAKE THE MEZZANINE AN ENCLOSED AREA. PLEASE SHOW
 CLEARLY IF THE WALL AROUND THE STAIRS GOES TO THE DECK
 ABOVE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 11:17 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 11:17 Sent To  
Notes
2009-05-15 11:18:26DISREGARD PROVISO FROM PREVIOUS REVIEW. LPD LOCATED ON
 A-1.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-10 Cont ID  
Sent By dpalmer Date 2009-04-10 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2009-04-10 Time 16:54 Sent To  
Notes
2009-04-10 16:54:50** PROVISO **
  
 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS STILL NEED
 TO BE COMPLETED. 13-415.2

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-03-11 Cont ID  
Sent By dpalmer Date 2009-03-11 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2009-03-11 Time 10:44 Sent To  
Notes
2009-03-11 10:44:31** DENIED 2ND RESUB **
  
 *** PLEASE KNOW THAT SEVERAL NOTES FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING. THERE ARE ALSO SEVERAL
 NEW NOTES AS SOME INFORMATION WHICH IS ONLY NOW
 SUBMITTED DOES NOT MEET MINIMUM CODE COMPLIANCE. NOTES
 BELOW WILL BE MARKED FOR NEW COMMENTS. NOTES BELOW WILL
 ALSO BE MARKED FOR PREVIOUS REVIEW COMMENTS.
  
 1) NOTE: PREVIOUS REVIEW: PLEASE SUBMIT PLANS SHOWING
 MINIMUM CODE COMPLIANCE FOR LIGHTING CONTROLS FOR NEW
 PER FBC 13-415.1.ABC.1.1, .1.2. THE RESPONSE LETTER
 MENTIONS *NOTES* WERE ADDED TO PLANS. THE PLANS DO NOT
 CONTAIN ANY NOTES WITH RESPECT TO MINIMUM LIGHTING
 CONTROLS. IN EITHER CASE PLACING NOTES ON THE PLANS IN
 LIEU OF DETAILS IS NOT PERMITTED. PLEASE BE SURE TO ADD
 THE SPECIFIC TYPE OF CONTROLS, TIMES ETC.
  
 2) NOTE: PREVIOUS REVIEW: PLEASE SEE 13-415.2,
 13-415.2.ABC.1.1 AND .1.2. THE PREVIOUS REVIEW
 REQUESTED TO SHOW LIGHTING PERFORMANCE CALCULATIONS PER
 THE SECTIONS GIVEN. THE RESPONSE MENTIONS THESE ITEMS
 ARE SHOWN ON PLANS HOWEVER THERE ARE NO LIGHTING
 PERFORMANCE CALCULATIONS PER THE SECTIONS GIVEN SHOWN
 ON PLANS.
  
 3) NOTE: NEW COMMENT: PLEASE SEE NEW RISER WHICH NOW
 SHOWS THE MAIN SERVICE WITH A 100AMP FEED TO A 100AMP
 PANEL YET THE PANEL SCHEDULE INDICATES A 200AMP PANEL.
 THESE DO NOT CORRELATE.
 PLEASE ALSO SEE THE LOAD CALCULATIONS FOR THIS UNIT IS
 NOT CODE COMPLIANT. THE RECEPTACLE LOAD FOR EXAMPLE
 INDICATE SONLY FOUR(4) TOTAL RECEPTACLES AT 180VA EACH.
 HOWEVER PLEASE TAKE A LOOK AT THE PLANS THERE IS A
 SUBSTANTIAL AMOUNT OF MORE RECEPTACLES THAN FOUR.
 220.12,220.14,220.44 ETC.
  
 4) NOTE: NEW COMMENT: PLEASE SEE THE TOTAL LOAD
 CALCULATIONS AS EACH BAY INDICATES THE SAME EXACT LOADS
 WHICH IS NOT POSSIBLE. SEVERAL OF THESE UNITS HAVE BEEN
 BUILT OUT WITH A SUBSTANTIAL AMOUNT OF MORE LOAD THAN
 WHAT IS SHOWN.
 PLEASE ALSO SEE THE TOTAL OF THE LOAD CALCULATIONS
 WHICH INDICATES THE LOAD AT 440AMPS ON A 600AMP
 SERVICE. HOWEVER THE RISER CLEARLY INDICATES THIS MAIN
 SERVICE AS 600AMP EQUIPMENT WITH 400AMP FUSES. THIS
 WOULD TAKE THE LOAD OVER THE RATING OF THE OVER CURRENT
 PROTECTION PROVIDED. THIS IS NOT ONLY NOT PERMITTED IT
 IS UNSAFE AND DOES NOT MEET:
 220,230.70,230.71,230.76,230.79, 240.4, 310.16,110.14,
 ETC. THERE TOO MANY SECTIONS TO NOTE. THE LOAD MAY NOT
 EXCEED THE SERVICE RATING.
  
 5) NOTE: NEW COMMENT: PLEASE SEE THE OCCUPANCY
 CLASSIFICATION IS NOW LISTED AS *F*. WHAT WILL BE
 MANUFACTURED IN THIS LOCATION? THERE ARE CONCERNS OVER
 THE TYPE OF MANUFACTURING AND PRODUCTS OF STORAGE ETC
 WITH RESPECT TO ELECTRICAL PERTAINING TO POSSIBLE CLASS
 AND DIVISION LOCATIONS.
 PLEASE BE SURE TO SEE NEC 500 (ALL) FOR POSSIBLE CODE
 REQUIREMENTS.
  
 6) NOTE: PLEASE BE AWARE OF FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THERE
 ARE SECTIONS WHICH HAVE BEEN REPEATED A SECOND TIME.
  
 ** THERE ARE STILL SEVERAL UNANSWERED ITEMS OR
 CORRECTIONS WHICH NEED TO BE MADE WHICH MAY CREATE NEW
 COMMENTS.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 08:36 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 08:36 Sent To  
Notes
2008-11-04 08:37:05 
  
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE INCLUDE NEW OR EXISTING HORNS, STROBES,
 HORN/STROBE DEVICES MEETING FBC 11-4.28.1, .2 AND .3.
 PLEASE LIST THE HEIGHTS AND LEVELS.
  
 2) NOTE: PLEASE INCLUDE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1,.1.2.
 THESE WOULD BE FOR NEW AREAS ONLY AND MAY BE SHOWN ON
 PLANS FOR TABLE 13-415.2.B
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND.
 ** NEW BEING INSTALLED
  
 3) NOTE: PLEASE INCLUDE LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2 AND .1.3. ** NEW BEING INSTALLED
 ONLY REQUIRED
  
 4) NOTE: THE RISER AS SHOWN ON PLANS IS NOT SHOWN AS IT
 EXISTS. IF EXISTING THEN PLEASE INDICATE OTHERWISE THE
 REVIEW WILL BE DONE FOR NEW EQUIPMENT UNDER CURRENT
 CODES.
 230,220,240 ETC
  
 5) NOTE: PLEASE SEE THE CODE SECTION REFLECTED PER
 700.12E IS NOW DIFFERENT UNDER THE CURRENT 2005 NEC.
 THE NEW CODE SECTION IS 700.12F. IF THIS HAD BEEN THE
 ONLY COMMENT IT WOULD HAVE BEEN REDLINED. PLEASE
 CORRECT AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE PLANS NEED TO STATE THE
 FOLLOWING CODES AS A DESIGN STANDARD AT A MINIMUM.
 THESE ARE FOR THIS REVIEWER ONLY. PLEASE BE AWARE OF
 ANY COMMENTS FORM OTHER TRADES WHICH MAY HAVE ANY
 COMMENTS
  
 2004 FBC W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
  
 7) NOTE: PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR
 SCOPE OF WORK. AS NO PANEL SCHEDULE WAS SHOWN WITH
 CIRCUITING LOADS ETC REVIEW OF THESE ITEMS COULD NOT BE
 DONE. PLEASE INCLUDE THE NEW AND EXISTING LOADS ON
 PANEL.
 220, 408.4, 215.3, 230.42 ETC
 FBC 106.1.1, .1.2 FOR ADDITIONAL INFORMATION, CLARITY
 AND COORDINATION.
  
 8) NOTE: PLEASE SUBMIT LIGHTING LEVELS FOR STAIRS UNDER
 NORMAL AND EMERGENCY CONDITIONS. PLEASE SEE NFPA-101
 7.8.1.3, 7.9.1.2, .2.2.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-10 Cont ID  
Sent By mwennerg Date 2009-04-10 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2009-04-10 Time 10:36 Sent To  
Notes
2009-04-10 10:49:27***PROVISO***
  
 THE RESPONSE LETTER INDICATES THAT THE REAR EXIT DOES
 NOT REQUIRE PASSING THROUGH AN OFFICE. THE PLANS DO
 SHOW EXITING THROUGH OFFICE #3. PROVIDED THAT THIS
 SPACE MEETS THE DEFINITION AND REQUIREMENTS FOR A
 SINGLE EXIT, THE EXIT SIGN INSIDE OFFICE #3 MUST BE
 REMOVED. IF A SECOND EXIT IS REQUIRED, IT WOULD HAVE TO
 BE RELOCATED OUTSIDE OF THE OFFICE AREA MAKING IT
 ACCESSIBLE AND OBVIOUS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-03-16 Cont ID  
Sent By mawillia Date 2009-03-16 Time 13:03 Rev Time 0.00
Received By mawillia Date 2009-03-16 Time 12:30 Sent To  
Notes
2009-03-16 13:02:26*****DENIED*****
  
  
  
 05. WHAT EQUIPMENT AND/OR PROCESSES WILL BE USED AT THE
 NEW MEZZANINE LEVEL? YOUR RESPONSE WAS THAT THE SPACE
 IS FOR VIDEO GAME STORAGE AND SOME REPAIR; HOWEVER
 RESPONSE TO PREVIOUS ITEMS 6 THRU 9 INDICATES THAT THE
 STAIRS TO THE MEZZANINE ARE TO BE REMOVED THE DRAWINGS
 AND WILL BE REMOVED FROM THE IMPROVEMENT. WHERE WILL
 THE STORAGE OF THESE ITEMS BE LOCATED.
  
 10. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 AND FIRE EXTINGUISHER(S) FOR THE NEW FLOOR PLAN. COULD
 NOT LOCATE THE LOCATION OF THE FIRE EXTINGUISHER(S)
  
 NEW COMMENT:
  
 AA. IT APPEARS THAT EGRESSING AT THE REAR EXIT HAS TO
 DONE THROUGH AN OFFICE. PLEASE EXPLAIN AS PER NFPA 101,
 2003 EDITION HOW THIS ARRANGEMENT IS ACCEPTABLE.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-11-03 Cont ID  
Sent By mawillia Date 2008-11-03 Time 14:43 Rev Time 0.00
Received By mawillia Date 2008-11-03 Time 13:21 Sent To  
Notes
2008-11-03 14:35:49*****DENIED*****
  
  
 01. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02. THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 03. PLEASE LIST THE FOLLOWING INFORMATION FOR THIS
 OCCUPANCY: * OCCUPANT LOAD AND EGRESS CAPACITIES * IS
 THERE A FIRE ALARM SYSTEM? * IS THERE A FIRE SPRINKLER
 SYSTEM?
  
 04. PROVIDE AN EXISTING FLOOR LAYOUT OF THE TENANT
 SPACE.
  
 05. WHAT EQUIPMENT AND/OR PROCESSES WILL BE USED AT THE
 NEW MEZZANINE LEVEL?
  
 06. STAIRS SHALL COMPLY WITH 7.2.2 OF NFPA 101 - 2003
 EDITION.
  
 07. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE NEW
 HANDRAILS.
  
 08. THE STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES AND
 SHALL BE CONTINUOUSLY GRASPABLE ALONG THEIR ENTIRE
 LENGHT.
  
 09. EXPLAIN THE STAIR'S 14 RISERS @ 7-5/8" AND ITS 13
 TREADS @ 10" AS LISTED IN THE STAIR DETAIL.
  
 10. SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY LIGHTS,
 AND FIRE EXTINGUISHER(S) FOR THE NEW FLOOR PLAN.
  
 11. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS FOR THE NEW OFFICES IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 09:39 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 09:39 Sent To  
Notes
2009-04-06 09:39:29TO "B16"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 09:11 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 09:11 Sent To  
Notes
2009-03-04 09:12:02TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-04 Cont ID  
Sent By tgordon Date 2008-11-04 Time 16:07 Rev Time 0.00
Received By tgordon Date 2008-10-24 Time 14:20 Sent To  
Notes
2008-10-24 14:25:16TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-11-04 Cont ID  
Sent By tgordon Date 2008-11-04 Time 16:06 Rev Time 0.15
Received By tgordon Date 2008-11-04 Time 16:06 Sent To  
Notes
2008-11-04 16:07:47THREE PORTABLE A/C UNITS BEING INSTALLED MECHANICAL
 PERMIT NOT REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-06 Cont ID  
Sent By kstevens Date 2009-04-06 Time 11:58 Rev Time 0.00
Received By kstevens Date 2009-04-06 Time 11:58 Sent To  
Notes
2009-04-06 13:33:05 
  
 PASSED/PROVISO: A VENT IS REQUIRED FOR THE D.F. SECTION
 901.2.1. -- THE CLEAR FLOOR SPACE IS REQUIRED TO BE
 FORWARD APPROACH. SECTION 11-4.15.5(1). -- REVISION
 REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-12 Cont ID  
Sent By kstevens Date 2009-03-12 Time 15:52 Rev Time 0.00
Received By kstevens Date 2009-03-12 Time 15:52 Sent To  
Notes
2009-03-12 15:59:37PLUMBING PLAN REVIEW:
 DENIED:
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 ****FROM PREVIOUS REVIEW:
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW.
 ****NEW PLAN SHOW BOTH A STORAGE OCCUPANCY AND AN (F)
 OCCUPANCY. IT ALSO SHOWS 3 OFFICES WHICH INDICATE
 BUSINESS OCCUPANCY. PLEASE CLARIFY. IF THIS IS A MIXED
 OCCUPANCY, PLEASE INDICATE THE TOTAL OCCUPANCY OF EACH
 OCCUPANCY. TABLES 1004.1.2 & 403.1.
  
 2. PLEASE INDICATE ON THE RESUBMITTED PLANS THAT THE
 FACILITY HAS AN EXISTING DRINKING FOUNTAIN AND SERVICE
 SINK OR PROVIDE SAID FIXTURES ACCORDINGLY. PLEASE KNOW
 THAT THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER THE
 FBC???2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
 ****CONFLICTING INFORMATION IS INDICATED ON THE
 PLANS.THE FLOOR PLAN INDICATES AN EXISTING SERVICE SINK
 AND AN EXISTING DRINKING FOUNTAIN. THERE IS ALSO AN
 EXISTING WATER COOLER, (DRINKING FOUNTAIN) DETAIL. BUT
 ON THE SANITARY RISER DIAGRAM IT INDICATES A NEW
 DRINKING FOUNTAIN AND SHOWS NO SERVICE SINK. PLEASE
 CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-11-04 Cont ID  
Sent By mperson Date 2008-11-04 Time 09:51 Rev Time 0.30
Received By mperson Date 2008-11-04 Time 09:51 Sent To  
Notes
2008-11-04 10:06:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1
 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND
 I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 *NOTE: THIS APPEARS TO BE A STORAGE FACILITY. PLEASE
 KNOW THAT FOR A STORAGE FACILITY PER THE FBC-2004
 PLUMBING TABLE 403.1 MINIMUM NUMBERS OF REQUIRED
 PLUMBING FIXTURES FOR A S-1 OR S-2 OCCUPANCY ARE THE
 FOLLOWING.
  
 *WATER CLOSETS= 1 PER 100.
 *LAVATORIES= 1 PER 100.
 *DRINKING FOUNTAIN= 1 PER 1000.
 *OTHER= 1 SERVICE SINK.
  
 PLEASE INDICATE ON THE RESUBMITTED PLANS THAT THE
 FACILITY HAS AN EXISTING DRINKING FOUNTAIN AND SERVICE
 SINK OR PROVIDE SAID FIXTURES ACCORDINGLY. PLEASE KNOW
 THAT THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER THE
 FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS"
  
 END OF COMMENTS:
  
 *PLEASE CALL IS THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-29 Cont ID  
Sent By kdfreema Date 2008-10-29 Time 11:20 Rev Time 0.00
Received By kdfreema Date 2008-10-29 Time 11:20 Sent To  
Notes
***NONE***