Plan Review Details - Permit 08100526
Plan Review Stops For Permit 08100526
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 13:47 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 13:47 Sent To P
Notes
2008-11-07 13:48:11TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 13:31 Rev Time 0.00
Received By mperson Date 2008-10-24 Time 09:50 Sent To  
Notes
2008-10-24 09:50:23TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-10 Cont ID  
Sent By mperson Date 2008-11-10 Time 14:23 Rev Time 0.45
Received By mperson Date 2008-11-10 Time 14:23 Sent To PC
Notes
2008-11-10 14:30:17****************PROVISO****************
 INFORMATION ONLY REVISION NOT REQUIRED.
 PER FLORIDA STATUTES 489.105 (3)(M) THE BACKFLOW
 PREVENTER FOR THE POTABLE WATER SUPPLY TO THE
 IRRIGATION SYSTEM SHALL BE INSTALLED BY A LICENSED
 PLUMBING CONTRACTOR.
  
 MIKE PERSON
 BUILDING PLANS EXAMINER / PLUMBING
 THE CITY OF WEST PALM BEACH
 OFFICE: (561) 805-6730
 FAX: (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By mperson Date 2008-10-31 Time 13:12 Rev Time 0.45
Received By mperson Date 2008-10-31 Time 13:12 Sent To I
Notes
2008-10-31 13:31:07PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET IR-1 INDICATES "IRRIGATION TAP AT DEDICATED 3"
 METER", HOWEVER THERE IS NO INDICATION OF BACKFLOW
 PROTECTION FOR THE POTABLE WATER. PER FBC-2004 PLUMBING
 SECTION 608.16.5 CONNECTIONS TO LAWN IRRIGATION
 SYSTEMS. THE POTABLE WATER SUPPLY TO LAWN IRRIGATION
 SYSTEMS SHALL BE PROTECTED AGAINST BACKFLOW BY AN
 ATMOSPHERIC-TYPE VACUUM BREAKER, A PRESSURE-TYPE VACUUM
 BREAKER OR A REDUCED PRESSURE PRINCIPLE BACKFLOW
 PREVENTER. A VALVE SHALL NOT BE INSTALLED DOWNSTREAM
 FROM AN ATMOSPHERIC VACUUM BREAKER. WHERE CHEMICALS ARE
 INTRODUCED INTO THE SYSTEM, THE POTABLE WATER SUPPLY
 SHALL BE PROTECTED AGAINST BACKFLOW BY A REDUCED
 PRESSURE PRINCIPLE BACKFLOW PREVENTER. CLEARLY INDICATE
 HOW THE POTABLE WATER WILL BE PROTECTED ON THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]