Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By rmcdouga Date 2008-10-24 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2008-10-24 Time 10:49 Sent To  
Notes
2008-10-24 10:52:02ROOFING SUB-CONTRACTOR CHANGED BACK TO ROOFING SYSTEM
 THAT WAS SUBMITTED WITH MASTER PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By rmcdouga Date 2008-10-23 Time 15:46 Rev Time 0.00
Received By rmcdouga Date 2008-10-23 Time 15:45 Sent To  
Notes
2008-10-23 15:45:522004 FBC W/2007 REVISIONS
 INSTALL FLAT ROOF SYSTEM
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117
 CALCULATIONS FROM AN ARCHITECT, ENGINEER OR REGISTERED
 ROOF CONSULTANT FOR ENHANCED FASTENING AT PERIMETER AND
 CORNER AREAS. SEE LIMITATION #7 ON PAGE 39 OF THE
 CERTAINTEED MODIFIED ROOFING SYSTEM NOA NO. 08-0227.09.
 SEE FBC TABLE R301.2(2) FOR UPLIFT PRESSURES IN EXPOSUE
 B. CORNERS HAVE PRESSURES OF -89.0 PSF.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]