2008-11-04 09:10:44 | PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SHEET A-1, DETAIL 2, DEMOLITION PLAN: IT APPEARS |
| FROM THIS LAYOUT THAT THIS WAS AN R-2, OCCUPANCY AND |
| FROM THE SUBMITTED PLANS THAT THIS OCCUPANCY IS BEING |
| CHANGED TO A BUSSINESS. PLEASE CLARIFY AND CHANGE THE |
| PERMIT APPLICATION. PER (W.P.B. AS AMENDED) SECTION 105 |
| PERMITS. |
| |
| 2. SHEET A-1, A-2 FLOOR PLAN AND SHEET A-3 DETAIL 11, |
| ROOM 218 IS A BATHROOM NOT AN EXISTING UTILITY ROOM. |
| PLEASE CORRECT THIS ON THE RESUBMITTAL. PER (W.P.B. AS |
| AMENDED) SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 3. DUE TO THE CHANGE OF OCCUPANCY THE FOLLOWING |
| PLUMBING FIXTURES IN THE FOLLOWING ROOM NUMBERS NEED TO |
| BE ACCESSIBLE PER THE FBC-2004 CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE. ROOM 215, WATER CLOSET, LAVATORY |
| AND BATHTUB. ROOM 217, SINK. ROOM 218, WATER CLOSET AND |
| LAVATORY. |
| |
| *THE FOLLOWING ARE THE CODE SECTIONS FOR SAID |
| ACCESSIBLE PLUMBING FIXTURES. |
| |
| **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH |
| THE FOLLOWING INFORMATION) |
| 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. |
| 11-4.16.3 HEIGHT. 17" TO 19". |
| 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C |
| 36" LONG. |
| 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" |
| HIGH. |
| 11-4.16.6 DISPENSERS. SEE FIGURE 29(B). |
| |
| **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL |
| REQUIRED WITH THE FOLLOWING INFORMATION) |
| 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR |
| COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE |
| FIGURE 31) |
| 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND |
| A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE |
| 32) |
| 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO |
| PROTECT AGAINST CONTACT. |
| 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND |
| ELECTRONICALLY CONTROLLED ARE EXAMPLES. |
| 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F. |
| |
| ** 11-4.20 BATHTUBS (ELEVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION) |
| 11-4.20.2 FLOOR SPACE. (SEE FIGURE 33) |
| 11-4.20.3 SEAT. REQUIRED. (SEE FIGURE 33 & 34) |
| 11-4.20.4 GRAB BARS. REQUIRED. (SEE FIGURE 33 & 34) |
| 11-4.20.5 CONTROLS. (SEE FIGURE 34) |
| 11-4.20.6 SHOWER UNIT. SHOWER SPRAY UNIT WITH A HOSE |
| MINIMUM 60" LONG USED BOTH AS A FIXED OR HAND HELD |
| SHALL BE PROVIDED. |
| |
| **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE |
| FOLLOWING INFORMATION) |
| 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR |
| COUNTER. |
| 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE, |
| AND 19" DEEP. |
| 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. |
| 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR |
| SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK |
| (NO CABINET DOORS, OPEN FRONT). |
| 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO |
| PROTECT AGAINST CONTACT. |
| 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR |
| ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS. |
| NOTE: SHEET A-3 DETAIL 2, KITCHEN 217, NEEDS TO BE |
| REVISED ACCORDINGLY. |
| |
| 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR |
| SPACE |
| 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE |
| SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR |
| SPACE (PER 11-4.2.3) |
| |
| 4. SHEET A-1, OVERALL TENANT FLOOR PLAN DOES NOT |
| INDICATE THE REQUIRED DRINKING FOUNTAIN FOR A BUSSINESS |
| OCCUPANCY PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM |
| NUMBER OF REQUIRED PLUMBING FIXTURES. PLEASE KNOW THAT |
| THE REQUIRED DRINKING FOUNTAIN SHALL BE ACCESSIBLE PER |
| THE FOLLOWING FBC-2004 CHAPTER 11, FLORIDA |
| ACCESSIBILITY CODE SECTIONS. |
| |
| **11-4.15 DRINKING FOUNTAINS (ELEVATION DETAIL REQUIRED |
| WITH THE FOLLOWING INFORMATION) |
| 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET |
| MAXIMUM. |
| 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN |
| TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT |
| OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN |
| ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN |
| 3" OF THE FRONT OF FOUNTAIN. |
| 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE |
| MOUNTED NEAR FRONT EDGE. |
| 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR |
| SPACE. |
| 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS |
| PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS |
| CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR |
| BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED |
| ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |