Plan Review Details - Permit 08100423
Plan Review Stops For Permit 08100423
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-09 Cont ID  
Sent By mjacobs Date 2008-12-09 Time 07:43 Rev Time 0.00
Received By mjacobs Date 2008-12-09 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-25 Cont ID  
Sent By mjacobs Date 2008-11-25 Time 15:38 Rev Time 0.00
Received By mjacobs Date 2008-11-25 Time 15:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By mjacobs Date 2008-10-23 Time 15:52 Rev Time 0.00
Received By mjacobs Date 2008-10-23 Time 15:52 Sent To  
Notes
2008-10-23 15:52:0910-23-08
 BUILDING PLAN REVIEW
 PERMIT: 08100423
 ADD: 3109 45TH STREET #100
 CONT: VILLA FRANCA DESIGN
 TEL: (561)575-2288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. SHOW THIS
 INFORMATION ON THE DRAWINGS.
  
 4) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL OF ALTERATION ON THE
 PLANS.
  
 5) SHEET A1 SHOWS TWO OPENINGS BEING CLOSED OFF AT
 STORAGE ROOM #26 AND FUTURE EXAM ROOM #8: WILL THE
 EXISTING DOOR REMAIN IN THE STORAGE ROOM? PROVIDE A
 DETAIL DRAWING SHOWING WHAT MATERIAL WILL BE USED TO
 CLOSE THE OPENINGS, HOW THE TOP AND BOTTOM SECTION OF
 THE OPENINGS WILL BE ATTACHED TO THE EXISTING STRUCTURE
 AND HOW THE RATING OF THE EXISTING WALLS WILL BE
 MAINTAINED. A HEADER DETAIL IS REQUIRED FOR THE NEW
 OPENING IN THE 18 INCH CONCRETE WALL. THE HEADER SHALL
 CONSIST OF LINTEL OR SOME OTHER TYPE OF STRUCTURAL
 CONSTRUCTION TO HOLD THE EXISTING CONCRETE IN PLACE.
 FBC 2104.1.6 THE MINIMUM LENGTH OF END SUPPORT FOR
 LINTELS SHALL BE 4 INCHES. ADDITIONAL INFORMATION IS
 REQUIRED 106.1.2
  
 6) NOW THE SPACE IS ALTERED FIRE SPRINKLER PLANS ARE
 REQUIRED TO SHOW THE NEW LAYOUT OF THE FIRE SPRINKLER
 HEADS IN COMPARISON THE NEW ROOMS. THE NEW SPRINKLER
 HEAD LOCATIONS MAY BE SHOWN ON THE CEILING PLANS ON
 SHEET A3. FBC* 106.3.5.1.1(5) FS 553.79(2)
  
 7) THE SOFFIT AND COVE LIGHT DETAILS ON SHEET A3 FAILS
 TO INDICATE HOW THE TOP TRACK OR METAL STUDS WILL BE
 ATTACHED TO THE STRUCTURE ABOVE AND WHAT TYPE OF
 FASTENERS WILL BE USED.
  
 8) SHEET A4; THE ROOM FINISH SCHEDULE FAILS TO SHOW THE
 FINISHED OF THE WALLS. TABLE 803.5 MINIMUM INTERIOR
 FINISH CLASSIFICATION; PROVIDE INFORMATION BASED ON
 INTERIOR FINISH REQUIREMENTS BASED ON OCCUPANCY. PLEASE
 INDICATE THE FLAME SPREAD PER THIS TABLE.
  
 9) FBC 1210.2 WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, T A HEIGHT OF 4 FEET. STATE THE WALL FINISHES
 FOR THE BATHROOMS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-02-18 Cont ID  
Sent By btrobaug Date 2009-02-18 Time 12:06 Rev Time 0.00
Received By btrobaug Date 2009-02-18 Time 12:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-12-01 Cont ID  
Sent By btrobaug Date 2008-12-01 Time 16:03 Rev Time 0.00
Received By btrobaug Date 2008-12-01 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-29 Cont ID  
Sent By btrobaug Date 2008-10-29 Time 14:49 Rev Time 0.00
Received By btrobaug Date 2008-10-28 Time 14:57 Sent To  
Notes
2008-10-29 14:49:17 
  
  
  
 APPLICATION #08100423 ELECTRICAL PLAN REVIEW
 3109 45TH STREET 10/28/08
 WEST PALM BEACH, FL.
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1 FOR AUTOMATIC CONTROL REQUIREMENTS AND
 FOR LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 2} INDICATE COMPLIANCE WITH 517.13 ON THE PLANS. THIS
 CAN BE DONE IN NOTE FORM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-12-10 Cont ID  
Sent By mawillia Date 2008-12-10 Time 11:03 Rev Time 0.00
Received By mawillia Date 2008-12-10 Time 10:54 Sent To  
Notes
2008-12-10 11:03:00*****APPROVED*****
  
  
 PLAN SHEETS A1, A4, E1 & E2 WERE PREVIOUSLY STAMPED,
 INITIALED, AND DATED ON 12/02/2008; SHEET A4 WAS
 RE-STAMPED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-12-02 Cont ID  
Sent By mawillia Date 2008-12-02 Time 16:40 Rev Time 0.00
Received By mawillia Date 2008-12-02 Time 16:16 Sent To I
Notes
2008-12-02 16:35:53*****APPROVED*****
  
  
 PLAN SHEETS A1, A4, E1 & E2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 09:56 Rev Time 0.00
Received By mwennerg Date 2008-10-31 Time 09:56 Sent To  
Notes
2008-10-31 10:04:02***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS TO BE
 MOUNTED AT LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE.
  
 3) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 4) SHEET E-2 INDICATES A FIRE ALARM SYSTEM TO INCLUDE A
 CONTROL PANEL. IF FIRE ALARM SUPERVISES AN AUTOMATIC
 FIRE SPRINKLER SYSTEM, IT SHALL BE UL CERTFICATED PRIOR
 TO FINAL INSPECTION.
  
 5) PLEASE INDICATE THE MAXIMUM TRAVEL DISTANCE ON THE
 SAFETY FLOOR PLAN.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2009-05-12 Time   Rev Time 0.00
Received By lmartine Date 2009-05-12 Time 16:58 Sent To M
Notes
2009-05-12 16:58:11GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-04-22 Cont ID  
Sent By dpalmer Date 2009-04-22 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2009-04-22 Time 11:53 Sent To M
Notes
2009-04-22 11:53:38TO RR DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-26 Cont ID  
Sent By adarroug Date 2009-03-26 Time 16:19 Rev Time 0.00
Received By adarroug Date 2009-03-26 Time 16:19 Sent To  
Notes
2009-03-26 16:20:17TO "B5"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-17 Cont ID  
Sent By adarroug Date 2009-02-17 Time 11:00 Rev Time 0.00
Received By adarroug Date 2009-02-17 Time 11:00 Sent To E
Notes
2009-02-17 11:01:07TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-04 Cont ID  
Sent By adarroug Date 2008-12-04 Time 10:59 Rev Time 0.00
Received By adarroug Date 2008-12-04 Time 10:59 Sent To  
Notes
2008-12-04 11:02:27TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-14 Cont ID  
Sent By adarroug Date 2008-11-14 Time 13:35 Rev Time 0.00
Received By adarroug Date 2008-11-14 Time 13:35 Sent To  
Notes
2008-11-14 13:39:02TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 10:06 Rev Time 0.00
Received By mwennerg Date 2008-10-21 Time 14:54 Sent To  
Notes
2008-10-21 14:58:01TO "BOB"#12

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-05-28 Cont ID  
Sent By rregueir Date 2009-05-28 Time 15:57 Rev Time 0.00
Received By rregueir Date 2009-05-28 Time 15:50 Sent To PC
Notes
2009-05-28 16:00:02PAGE M1 REV 3

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2009-05-04 Cont ID  
Sent By rregueir Date 2009-05-04 Time 09:59 Rev Time 0.00
Received By rregueir Date 2009-05-04 Time 09:32 Sent To PC
Notes
2009-05-04 09:59:17REVIEW #: REVISION DELTA 3
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISION HISTORY INDICATES THAT THIS IS REVISION DELTA
 3. HOWEVER, NO DELTA 3 COULD BE FOUND ON PLANS. THERE
 IS NO INDICATION ONPLANS WHAT CHANGES WERE MADE
 SPECIFIC TO THIS REVISION. PLEASE CLEARLY IDENTIFY THE
 LOCATION OF THE CHANGES FROM THE PREVIOUSLY STAMPED
 PLANS AND RESUBMIT. SEE FBC-B 106.1.3 AS AMENDED BY THE
 CITY OF WEST PALM BEACH.
 NOTE: IT WOULD BE HELPFUL, IN ORDER TO FACILITATE A
 TIMELY REVIEW, TO REMOVE THE CLOUDS FROM PREVIOUS
 REVISIONS AND ONLY CLOUD THE AREAS BEING CHANGED
 SPECIFIC TO DELTA 3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-04-02 Cont ID  
Sent By rregueir Date 2009-04-02 Time 11:33 Rev Time 0.00
Received By rregueir Date 2009-04-02 Time 11:19 Sent To  
Notes
2009-04-02 11:33:14REVISED M-1 AND M-2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 17:29 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-28 Cont ID  
Sent By tgordon Date 2008-10-28 Time 08:14 Rev Time 0.45
Received By tgordon Date 2008-10-28 Time 08:14 Sent To  
Notes
2008-10-28 08:27:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLAN A3 SHOWS BATT INSULATION LYING ON THE
 ACOUSTICAL CEILING, PER 2004 FBC 13-404.1.ABC.1 ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS. PLEASE CORRECT.
  
 2) PLEASE SUBMIT A COPY OF THE ASHRAE 62 (2004 OR 2007)
 SECTION THAT DEMONSTRATES THE EQUATION USED FOR THE
 OUTDOOR AIR CALCULATIONS FOR THE WAITING ROOM. SEE 2004
 FBC/M 403.4 AND ASHRAE 62.1-2004 SECTION 6.2.6.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-04-06 Cont ID  
Sent By kstevens Date 2009-04-06 Time 09:37 Rev Time 0.00
Received By kstevens Date 2009-04-06 Time 09:37 Sent To  
Notes
2009-04-06 09:39:26REVISIONS OK -- SHT P-1 & P-2. (SHT P-3 SHOWS NO
 CHANGES/REVISIONS - NO STAMPS REQUIRED)

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-12-15 Cont ID  
Sent By kstevens Date 2008-12-15 Time 12:13 Rev Time 0.00
Received By kstevens Date 2008-12-15 Time 12:13 Sent To  
Notes
2008-12-15 12:14:14PROVISO: -- FORWARD APPROACH REQUIRED PER 11-4.24.5.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-11-25 Cont ID  
Sent By kstevens Date 2008-11-25 Time 13:30 Rev Time 0.00
Received By kstevens Date 2008-12-09 Time 07:42 Sent To  
Notes
2008-11-25 13:50:49DENIED
 REFERENCE:
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 4. SHT A2 INTERIOR ELEVATION DETAIL (9) @ LOUNGE:
 PLEASE CORRECT/ADD THE FOLLOWING REQUIRED INFORMATION
 PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBLILITY
 CODE SECTION TO THE DETAIL FOR THE ACCESSIBLE SINK.
  
 *SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH,
 30" WIDE AND 19" DEEP. (OPEN FRONT REQUIRED, REMOVE
 CABINET DOORS @ SINK).
 ****NO RESPONSE, COMMENT NOT ADDRESSED. (SCALES OUT
 JUST OVER 25" AND NO MINIMUM CLEARANCE (27") INDICATED.
  
 5. SHEET A4 DETAILS: PLEASE ADD THE FOLLOWING REQUIRED
 INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTION FOR THE FOLLOWING ACCESSIBLE
 PLUMBING FIXTURES.
  
 SECTION 11-4.15 CLEARANCES. KNEE 27" HIGH.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ********NEW COMMENTS********
  
 1B. SHT A1 SHOW CLEAR FLOOR SPACE FOR THE LOUNGE SINK
 PER SECTION 11-4.24.5 ON THE FLOOR PLAN.
  
 2B. SHT A4 CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAIN
 IS SHOWN AS A PARALLEL APPROACH. PER SECTION 11-4.15.
 SUCH UNITS SHALL HAVE A MINIMUM 30"X48" CLEAR FLOOR
 SPACE TO ALLOW A PERSON IN A WHEELCHAIR TO APPROACH THE
 UNIT FACING FORWARD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-30 Cont ID  
Sent By mperson Date 2008-10-30 Time 13:14 Rev Time 1.30
Received By mperson Date 2008-10-30 Time 13:14 Sent To  
Notes
2008-10-30 13:28:41PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION 106.5
 RECORD RETENTION.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS".
  
 2. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 3. THE ADDRESS IS INCOMPLETE ON ALL PLAN SHEETS. THE
 SUITE NUMBER 110 IS MISSING FROM THE ADDRESS. PLEASE
 CORRECT PER FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS
 AND SECTION 106.5 RECORD RETENTION.
  
 4. SHEET A2 INTERIOR ELEVATION DETAIL (9) @ LOUNGE:
 PLEASE CORRECT/ADD THE FOLLOWING REQUIRED INFORMATION
 PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION TO THE DETAIL FOR THE ACCESSIBLE SINK.
  
 *SECTION 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER. (DETAIL INCORRECTLY INDICATES 3'-0")
  
 *SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH,
 30" WIDE, AND 19" DEEP. (OPEN FRONT REQUIRED, REMOVE
 CABINET DOORS @ SINK)
  
 *SECTION 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
  
 5. SHEET A4 DETAILS: PLEASE ADD THE FOLLOWING REQUIRED
 INFORMATION PER THE FBC-2004 CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE SECTIONS FOR THE FOLLOWING
 ACCESSIBLE PLUMBING FIXTURES.
  
 *DRINKING FOUNTAIN SECTION 11-4.15.
  
 SECTION 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR
 SIDE MOUNTED NEAR FRONT EDGE.
  
 SECTION 11-4.15.5 CLEARANCES. KNEE 27" HIGH.
  
 *WATER CLOSET SECTION 11-4.16.
  
 SECTION 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE
 MAX. 44" HIGH.
  
 6. SHEET P-1 DETAIL (2) SANITARY PLUMBING ISOMETRIC
 DIAGRAM: PLEASE CORRECT THE FOLLOWING PER THE FBC-2004
 PLUMBING CODE SECTIONS.
  
 A} W.C. #2 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A1.
 PLEASE KNOW THAT THERE ARE TWO LAVATORIES BEING
 INDICATED IN THE ISOMETRIC, HOWEVER THE FLOOR PLAN IS
 ONLY INDICATING ONE LAVATORY. PLEASE CORRECT PER
 SECTION 401.1 AND 701.1 SCOPE.
  
 B} EXAM ROOM #4 AND #5 CLEARLY INDICATE THE FIXTURE
 TYPE ON THE ISOMETRIC. PER SECTION 401.1 AND 701.1
 SCOPE.
  
 C} PLEASE KNOW THAT THE LABORATORY SINK PLUMBING ON
 BOTH THE SANITARY PLUMBING PLAN AND THE SANITARY
 PLUMBING ISOMETRIC DIAGRAM IS BEING INDICATED IN THE
 WRONG LOCATION AND DOES NOT REFLECT THE FLOOR PLAN OF
 SHEET A1. PLEASE CORRECT PER SECTION 701.1 SCOPE.
  
 7. SHEET P-2 DETAIL (2) WATER PLUMBING ISOMETRIC
 DIAGRAM: PLEASE CLEARLY INDICATE THE REQUIRED FULL-OPEN
 VALVE LOCATED ON THE WATER SUPPLY PIPE TO THE WATER
 HEATER. PER FBC-2004 PLUMBING SECTION 606.1 LOCATION OF
 FULL-OPEN VALVES (7).
  
 8. THE WATER HEATER AND HOT WATER PIPE INSULATION ARE
 MISSING FROM THE ENERGY CALCULATIONS. PER FBC-2004
 CHAPTER 13, TABLE 13-411.1.ABC.2 MINIMUM PIPE
 INSULATION AND TABLE 13-412.1.ABC.3 PERFORMANCE
 REQUIREMENTS FOR WATER HEATING EQUIPMENT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2009-04-03 Cont ID  
Sent By eschneid Date 2009-04-03 Time 08:50 Rev Time 0.25
Received By eschneid Date 2009-04-03 Time 08:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-30 Cont ID  
Sent By eschneid Date 2008-10-30 Time 16:53 Rev Time 0.00
Received By eschneid Date 2008-10-30 Time 16:53 Sent To  
Notes
2008-10-30 17:02:48BUILDING VALUE @ $554,461 ACCORDING TO PAPA. NOTE THAT
 ALL IMPROVEMENTS PERMIT VALUE WITHIN ONE YEAR TO THIS
 BUILDING (BOTH BAYS) MAY NOT EXCEED $277,230 OR A
 LANDSCAPE PLAN MEETING ALL CODE STANDARDS IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.