Plan Review Details - Permit 08100422
Plan Review Stops For Permit 08100422
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-12 Cont ID  
Sent By mjacobs Date 2008-11-12 Time 10:07 Rev Time 0.00
Received By mjacobs Date 2008-11-12 Time 10:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By mjacobs Date 2008-10-23 Time 10:15 Rev Time 0.00
Received By mjacobs Date 2008-10-23 Time 10:15 Sent To  
Notes
2008-10-23 10:14:59 
 10-23-08
 BUILDING PLAN REVIEW
 PERMIT: 08100422
 ADD: 3109 45TH STREET #100
 CONT: VILLA FRANCA DESIGN
 TEL: (561)575-2288
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. THIS INFORMATION
 SHALL BE SHOWN ON THE PLANS.
  
 4) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. SUBMIT AN EXISTING
 FLOOR PLAN OF THE AREA PRIOR TO THE BATHROOM
 INSTALLATION.
  
 5) THE DESCRIPTION ON THE APPLICATION STATES ?RELOCATE
 INTERIOR BATHROOMS? SHOW ON THE DRAWINGS WHERE THE
 EXISTING BATHROOMS ARE AND WHERE THEY WILL BE RELOCATED
 TO.
  
 6) SHEET A1 SHOWS THE BATHROOM DOORS SWINGING OUT AND
 SHEET M-P-1 SHOWS THEM SWINGING IN. THE FLOOR PLAN ON
 EACH SHEET SHALL MATCH EACH OTHER. NOTE: FBC 11-4.22.2
 ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH
 SECTION 11-4.13. DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
  
 7) THE FINISH SCHEDULE ON SHEET A1 FAILS TO INDICATE
 THE WALL FINISHES IN THE BATHROOMS. NOTE: FBC 1202.2
 WALLS WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET ABOVE THE FLOOR. PLEASE PROVIDE ADDITIONAL
 INFORMATION.
  
 8) 2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE. INDICATE THE LEVEL ON THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-20 Cont ID  
Sent By btrobaug Date 2008-11-20 Time 09:30 Rev Time 0.00
Received By btrobaug Date 2008-11-20 Time 09:30 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By btrobaug Date 2008-10-24 Time 11:07 Rev Time 0.00
Received By btrobaug Date 2008-10-24 Time 08:05 Sent To  
Notes
2008-10-24 08:24:56 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED, INCLUDING SUITE
 NUMBER.
  
 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS
 AMENDED.
  
 3} PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION. SHOW AREA OF DEMOLITION ON THE
 PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 14:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-10-30 Cont ID  
Sent By mwennerg Date 2008-10-30 Time 10:05 Rev Time 0.00
Received By mwennerg Date 2008-10-30 Time 10:05 Sent To  
Notes
2008-10-30 10:06:511) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 08:40 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 08:40 Sent To  
Notes
2008-11-07 08:44:52TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-05 Cont ID  
Sent By lmartine Date 2008-10-30 Time 16:07 Rev Time 0.00
Received By lmartine Date 2008-10-21 Time 14:45 Sent To  
Notes
2008-10-21 14:48:48TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 14:25 Rev Time 0.25
Received By tgordon Date 2008-11-07 Time 14:25 Sent To  
Notes
2008-11-07 14:28:27TWO BATHROOM EXHAUST FANS AND ONE JANITOR CLOSET
 EXHAUST FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-24 Cont ID  
Sent By tgordon Date 2008-10-24 Time 13:46 Rev Time 0.25
Received By tgordon Date 2008-10-24 Time 13:46 Sent To  
Notes
2008-11-07 14:25:08BATHROOM EXHAUST FANS ONLY.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-10 Cont ID  
Sent By mperson Date 2008-11-10 Time 10:20 Rev Time 0.30
Received By mperson Date 2008-11-10 Time 10:20 Sent To  
Notes
2008-11-10 10:36:03****************PROVISO****************
 INFORMATION ONLY REVISION NOT REQUIRED.
 **11-4.16 WATER CLOSETS
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-24 Cont ID  
Sent By mperson Date 2008-10-24 Time 16:01 Rev Time 1.00
Received By mperson Date 2008-10-24 Time 16:01 Sent To  
Notes
2008-10-24 16:49:39PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE INCLUDE THE COMPLETE ADDRESS ON ALL PLAN
 SHEETS INCLUDING THE SUITE NUMBER. PER FBC-2004 CHAPTER
 1, (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. DECLARE THE GOVERNING CODE. (FBC-2004 WITH 2007
 REVISIONS) PER FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED)
 SECTION 106.5 RETENTION OF COSTRUCTION DOCUMENTS.
  
 3. DECLARE THE LEVEL OF ALTERATION. PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 4. PERMIT APPLICATION STATES "RELOCATE INTERIOR
 BATHROOMS". PROVIDE AN EXISTING FLOOR PLAN LAYOUT
 CLEARLY INDICATING THE LOCATION OF THE EXISTING
 BATHROOMS BEFORE THEY WERE RELOCATED. PER FBC-2004
 CHAPTER 1, (W.P.B. AS AMENDED) SECTION 106.1.2
 ADDITIONAL DATA. ALSO INDICATE THE LOCATION OF THE
 REQUIRED DRINKING FOUNTAIN ON THE EXISTING FLOOR PLAN
 AND IF ONE IS NOT EXISTING PROVIDE ONE PER FBC-2004
 PLUMBING TABLE 403.1 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES FOR A BUSINESS OCCUPANCY 1 PER 100 IS
 REQUIRED AND IT SHALL BE ACCESSIBLE PER THE FBC-2004
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WATER IS WITHIN
 3" OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 5. SHEET A1 FLOOR PLAN: THE BATHROOM DOORS ARE SWINGING
 OUT, HOWEVER ON SHEET M-P-1 DETAILS #1, 2, AND 3 THE
 DOOR SWING IS BEING INDICATED AS IN. PLEASE KNOW THAT
 PER FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTION 11-4.22.2 DOORS (1) DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE OF ANY FIXTURE. PLEASE CORRELATE
 RESUBMITTED PLAN SHEETS TO CLEARLY INDICATE AN OUTWARD
 DOOR SWING.
  
 6. SHEET A-1 CLEARLY INDICATE THE CLEAR FLOOR SPACE FOR
 THE FOLLOWING FIXTURES COMPLIANT WITH THE FOLLOWING
 FBC-2004 CHAPTER CODE SECTIONS. *WATER CLOSET SECTION
 11-4.16.2 SEE FIGURE 28 AND *LAVATORY SECTION 11-4.19.3
 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND A MAXIMUM
 OF 19" UNDERNEATH THE LAVATORY.
  
 7. SHEET A2 PLUMBING FIXTURE ELEVATION DETAIL FOR THE
 WATER CLOSET: CLEARLY INDICATE THAT THE WATER CLOSET IS
 COMPLIANT WITH THE FOLLOWING FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTION 11-4.16.5 FLUSH
 CONTROLS. MOUNTED ON WIDE SIDE MAX. 44" HIGH.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-30 Cont ID  
Sent By eschneid Date 2008-10-30 Time 17:01 Rev Time 0.00
Received By eschneid Date 2008-10-30 Time 17:01 Sent To  
Notes
2008-10-30 17:02:36BUILDING VALUE @ $554,461 ACCORDING TO PAPA. NOTE THAT
 ALL IMPROVEMENTS PERMIT VALUE WITHIN ONE YEAR TO THIS
 BUILDING (BOTH BAYS) MAY NOT EXCEED $277,230 OR A
 LANDSCAPE PLAN MEETING ALL CODE STANDARDS IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.