Plan Review Details - Permit 08100246
Plan Review Stops For Permit 08100246
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-19 Cont ID  
Sent By lmartine Date 2008-11-19 Time 16:12 Rev Time 0.00
Received By lmartine Date 2008-11-19 Time 16:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-17 Cont ID  
Sent By amorse Date 2008-10-17 Time 13:04 Rev Time 1.00
Received By amorse Date 2008-10-17 Time 13:04 Sent To PC
Notes
2008-10-17 13:30:18 
 DENIED
  
 1) PER 1609.6.1 FBC THE SIMPLIFIED CALCULATION METHOD
 FOR WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT ENGINEERED CALCULATIONS
  
 2) BE SURE TO INCLUDE THE LOCATION OF THE DOOR AND
 WINDOWS (ZONE 4 OR 5)
  
 3) PROVIDE THE SIZE/TYPE OF MULLION AS SOME MAY NOT
 MEET DESIGN PRESSURES.
  
 4) PROVIDE THE TYPE (EQUAL/UNEQUAL) AND TYPE OF GLAZING
 FOR THE SINGLE HUNG WINDOW UNITS THAT WILL MEET THE
 DESIGN PRESSURES INDICATED BY THE ENGINEERS
 CALCULATIONS. THE INFORMATION CAN BE STATED ON THE
 DRAWING OR MARKED IN THE PRODUCT APPROVAL.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-10-17 Time   Rev Time 0.00
Received By adarroug Date 2008-10-14 Time 11:33 Sent To  
Notes
2008-10-14 11:33:39TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***