Plan Review Stops For Permit 08100160 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2008-10-14 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-10-14 |
Time |
09:38 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-10-14 |
Time |
08:20 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-10-09 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-10-09 |
Time |
16:20 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-10-09 |
Time |
16:19 |
Sent To |
PC |
|
Notes |
2008-10-09 16:26:55 | RESIDENTIAL (R3) DOOR/SHUTTER INSTALLATION, BUILDING | | REVIEW CHECKLIST. | | | | 1- PROVIDE COMPLETE SHUTTER INSTALLATION SCHEDULE AS | | REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE | | DEBRIS IMPACT PROTECTION. SEE ATTACHED SAMPLE. THERE | | WAS NOT INSTALLATION SCHEDULE SUBMITTED WITH PERMIT | | APPLICATION. | | ***NOTE: TAKE INTO CONSIDERATION THAT WHEN ANCHOR | | INSTALLATION EDGE DISTANCE IS LESS THAN 3 1/2" THE | | ANCHOR SPACING NEEDS TO BE REDUCED ACCORDINGLY. SEE | | SHEET 11 OF 13 OF SHUTTER DRAWINGS SUBMITTED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|