Plan Review Details - Permit 08100010
Plan Review Stops For Permit 08100010
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-20 Cont ID  
Sent By jwitmer Date 2008-10-20 Time 10:28 Rev Time 0.77
Received By jwitmer Date 2008-10-20 Time 10:28 Sent To  
Notes
2008-10-20 10:33:11BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. PLANS SUBMITTED
 ARE COPIED PLANS PLEASE PROVIDE ORIGINAL PLANS AND
 INDICATE THE AUTHOR OF THE PLANS WITH TELEPHONE NUMBER.
  
 1D ) INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 1F) VALUE FOR GENERATOR, TRANSFER SWITCH, 100 GALLON
 DEISEL TANK AND SLAB IS EXTREMELY LOW, THE FAIR MARKET
 VALUE WILL BE ASSESSED USING MARSHAL & SWIFT OR ICC
 VALUATIONS.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) MISSING WIND INFORMATION: 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 3) SLAB CUT SHEET HAS INDICATED 1/2 INCH LAG BOLTS INTO
 PAD. THE PLANS DO NOT INDICATE THE QUANTITY OF BOLTS TO
 BE USED, LOCATION OF LAG BOLTS, LENGHT OF LAG BOLTS
 WITH NOT HAVING THE LOCATON OF LAG BOLTS KNOWN IF
 DERATING VALUES WOULD BE A CONCERN. 1609.1.3. ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIPPAGE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-17 Cont ID  
Sent By btrobaug Date 2008-10-17 Time 15:43 Rev Time 0.00
Received By btrobaug Date 2008-10-17 Time 15:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 11:06 Rev Time 0.00
Received By mwennerg Date 2008-10-23 Time 11:06 Sent To  
Notes
2008-10-23 11:11:38***DENIED***
  
 1) EQUIPMENT PROTECTION MAY BE REQUIRED IF THE
 POSSIBILITY OF MECHANICAL DAMAGE EXISTS.
  
 2) IN ADDITION TO NFPA 101, 2003, WORK SHALL COMPLY
 WITH NFPA 110, STANDARD FOR EMERGENCY POWER AND STANDBY
 SYSTEMS.
  
 3) WHAT BUILDING EQUIPMENT AND OR LIFE SAFETY SYSTEMS
 WILL BE TIED INTO THE GENEREATOR?
  
 4) CLEARLY IDENTIFY THE LOCATION AND DIMENSIONS OF
 EXHAUST TERMINUS AS IT RELATES TO BUILDING OPENINGS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 15:49 Rev Time 0.30
Received By tgordon Date 2008-10-03 Time 15:49 Sent To  
Notes
2008-10-03 15:50:43100 GAL. DIESEL.

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-10-10 Cont ID  
Sent By kstevens Date 2008-10-10 Time 14:32 Rev Time 0.00
Received By kstevens Date 2008-10-10 Time 14:28 Sent To  
Notes
2008-10-10 14:32:48INDICATED AS A DIESEL GENERATOR

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2008-10-02 Time 10:12 Sent To  
Notes
2008-10-02 10:15:08TO "COMM" BD#19

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-10-03 Cont ID  
Sent By tgordon Date 2008-10-03 Time 15:50 Rev Time 0.30
Received By tgordon Date 2008-10-03 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By kdfreema Date 2008-10-09 Time 10:01 Rev Time 0.00
Received By kdfreema Date 2008-10-09 Time 10:01 Sent To  
Notes
2008-10-09 10:45:39***FAILED***
  
 1. A MINOR AMENDMENT TO THE AUSTRALIAN AVENUE OFFICE
 PARK COMMERCIAL PLANNED DEVELOPMENT IS REQUIRED.
  
 2. PLEASE PROVIDE A SURVEY SHOWING THE AREA IN WHICH
 THE PROPOSED WORK IS TO BE DONE. A SPOT SURVEY IS
 SUFFICIENT.
  
 3. PROVIDE A SITE PLAN SHOWING THE ENTIRE PROPERTY.
 WITH ONLY A PARTIAL PLAN WE ARE UNABLE TO DETERMINE HOW
 THE PROPOSED GENERATOR INTERACTS WITH THE REST OF THE
 SITE.
  
 4. THE PLANS DO NO CLEARLY SHOW HOW THE GENERATOR
 ENCLOSURE COMPLIES WITH SEC. 94-444(B) OF THE ZONING
 CODE. NOTE THAT THE GENERATOR MUST BE SCREENED BY A
 FENCE. CHAIN LINK WITH SLATS IS NOT PERMITTED. THE
 LANDSCAPING AROUND THE GENERATOR MUST BE PROTECTED BY
 "TYPE D" CURB ON ALL BUT THE NORTH SIDE. THE PLANS MUST
 SPECIFY THE PLACMENT OF THE SHRUBS, QUANTITY, SIZE, AND
 SPECIES. SHRUBS AND HEDGES MUST BE PLANTED AT 2 FEET ON
 CENTER.
  
 5. THE SUBMITTED PLANS DO NOT SHOW THE LOCATION OF THE
 GATE ACCESSING THE ENCLOSURE, PLEASE ADD IT.
  
 6. THE PROPOSED ADDITION OF PARKING SPACES WILL REQUIRE
 A SEPARATE PERMIT TO BE ISSUED SO A SEPARATE
 APPLICATION WOULD NEED TO BE MADE.
  
 7. IF IT HASN'T BEEN DONE ALREADY, THE 20 PARKING
 SPACES ALONG THE WEST SIDE OF THE BUILDING WILL HAVE TO
 BE CLEARED OUT. THEY MAY NOT BE USED FOR STORAGE. DOING
 THIS MAY SAVE YOU THE EXPENSE OF HAVING TO CONSRUCT
 ADDITIONAL PARKING SPACES.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.
  
  