Plan Review Details - Permit 08090691
Plan Review Stops For Permit 08090691
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-12-19 Cont ID  
Sent By btrobaug Date 2008-12-19 Time 15:49 Rev Time 0.00
Received By btrobaug Date 2008-12-19 Time 15:37 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-11-20 Cont ID  
Sent By btrobaug Date 2008-11-20 Time 11:57 Rev Time 0.00
Received By btrobaug Date 2008-11-20 Time 11:50 Sent To PC
Notes
2008-11-20 11:57:25 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE ARE REPEAT COMMENTS
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3),
 IF REQUIRED***NO RECEPTACLE LOCATION IS SHOWN, IF
 WHITHIN 25 FEET A NOTE ON THE PLAN WILL SUFFICE.
  
 NEW COMMENT
  
 2} INDICATE THE FEED SIZE AND OCPFOR THE AHU AND
 CONDENSING UNIT..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By btrobaug Date 2008-10-02 Time 09:07 Rev Time 0.00
Received By btrobaug Date 2008-10-02 Time 08:54 Sent To Z
Notes
2008-10-02 09:07:27 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3),
 IF REQUIRED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-19 Cont ID  
Sent By adarroug Date 2008-11-19 Time 08:51 Rev Time 0.00
Received By adarroug Date 2008-11-19 Time 08:51 Sent To E
Notes
2008-11-19 08:51:22TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 12:18 Rev Time 0.00
Received By tgordon Date 2008-11-07 Time 12:18 Sent To M
Notes
2008-11-07 12:18:40TO MECH.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 12:13 Rev Time 0.00
Received By tgordon Date 2008-09-30 Time 14:27 Sent To  
Notes
2008-09-30 14:27:47TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-07 Cont ID  
Sent By tgordon Date 2008-11-07 Time 12:14 Rev Time 0.30
Received By tgordon Date 2008-11-07 Time 12:14 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By tgordon Date 2008-10-02 Time 08:33 Rev Time 0.30
Received By tgordon Date 2008-10-02 Time 08:22 Sent To E
Notes
2008-10-02 08:33:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A FLOOR PLAN SHOWING WHERE IN THE
 BUILDING THE AIR HANDLER IS BEING INSTALLED AND WHERE
 OUTSIDE THE BUILDING THE CONDENSER UNIT IS BEING
 INSTALLED. ALSO ADD AN EQUIPMENT SCHEDULE TO THE PLAN
 WITH ALL THE PERTINENT INFORMATION ON IT, PER 2004 FBC
 106.1.1 AND FBC/R M1401.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-24 Cont ID  
Sent By mcruz Date 2008-12-24 Time 11:02 Rev Time 0.00
Received By mcruz Date 2008-12-24 Time 11:02 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-18 Cont ID  
Sent By adavila Date 2008-11-18 Time 17:58 Rev Time 0.00
Received By adavila Date 2008-11-18 Time 17:57 Sent To I
Notes
2008-11-18 17:58:35PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT - PLEASE PROVIDE ALL RESPONSES IN
 WRITING.
  
 2. REPEAT COMMENT - PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY, WHICH INCLUDES THE PROPERTY'S ADDRESS AND LEGAL
 DESCRIPTION.
  
 3. REPEAT COMMENT - INDICATE SETBACK DIMENSIONS FROM
 PROPOSED A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT
 TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-305(B)(4):
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ANDREINA DAVILA Q. OR MAGGIE CRUZ AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-04 Cont ID  
Sent By mcruz Date 2008-10-04 Time 14:53 Rev Time 0.00
Received By mcruz Date 2008-10-04 Time 14:52 Sent To  
Notes
2008-10-04 14:52:56***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  