Plan Review Details - Permit 08090615
Plan Review Stops For Permit 08090615
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-09-25 Cont ID  
Sent By jwitmer Date 2008-09-25 Time 15:40 Rev Time 2.72
Received By jwitmer Date 2008-09-25 Time 15:40 Sent To ENG
Notes
2008-09-25 16:06:13 
  
  
  
  
  
  
  
  
  
 BUILDING PROVISO:
 1) 2304.11.2.5 WOOD SIDING. CLEARANCE BETWEEN WOOD
 SIDING AND EARTH ON THE EXTERIOR OF A BUILDING SHALL
 NOT BE LESS THAN 6 INCHES (152 MM) EXCEPT WHERE SIDING,
 SHEATHING AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
 BUILDING PROVISO:
 2) THIS BUILDING IS LOCATED IN A A-5 FLOOD ZONE, BASE
 FLOOD ELEVATION PLUS 6" IS 7-'6". FBC BUILDING 3110.1.2
 / CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED.
 BUILDING PROVISO:
 3) 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER DISCRETION, ISSUE A
 SPECIAL PERMIT FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST OF THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH
 A SPECIAL PERMIT IS PROCEEDING AT HIS OR HER OWN RISK
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE REMAINDER
 OF THE WORK WILL BE GRANTED AND THAT CORRECTIONS WILL
 NOT BE REQUIRED IN ORDER TO MEET THE PROVISIONS OF THE
 TECHNICAL CODE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-09-25 Cont ID  
Sent By btrobaug Date 2008-09-25 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2008-09-25 Time 10:22 Sent To Z
Notes
2008-09-25 10:29:12 
  
 BUILDING FOUNDATION ONLY UNDER THIS PERMIT./WRT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-09-26 Cont ID  
Sent By rchokshi Date 2008-09-26 Time 09:20 Rev Time 0.00
Received By rchokshi Date 2008-09-26 Time 09:16 Sent To  
Notes
2008-09-26 09:19:55PASS WITH PROVISO: YOU MUST MEET /PROVIDE THE FOLLOWING
 ITEMS FOR FULL PERMIT.
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B), EFFECTIVE
 MAY 1, 2003
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT & STORM WATER QUALITY CALCULATIONS TO 1000 45TH
 STREET FOR THEIR APPROVAL BEFORE WE APPROVE.
  
 10. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-25 Cont ID  
Sent By jwitmer Date 2008-09-25 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2008-09-25 Time 15:40 Sent To E
Notes
2008-09-25 15:41:42HAND DELIVEERED TO TRADES JW

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-25 Cont ID  
Sent By jroach Date 2008-09-25 Time 14:35 Rev Time 0.00
Received By jroach Date 2008-09-25 Time 14:35 Sent To  
Notes
***NONE***