Plan Review Details - Permit 08090596
Plan Review Stops For Permit 08090596
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-10 Cont ID  
Sent By mjacobs Date 2008-11-10 Time 13:46 Rev Time 0.00
Received By mjacobs Date 2008-11-10 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By mjacobs Date 2008-10-01 Time 10:57 Rev Time 0.00
Received By mjacobs Date 2008-10-01 Time 10:57 Sent To  
Notes
2008-10-01 10:57:38BUILDING PLAN REVIEW
 PERMIT: 08090596
 ADD: 5707 S. DIXIE HIGHWAY #B
 CONT: P&T CONSTRUCTION, INC.
 TEL: (561)833-0614
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 10-1-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) SHEET A2 CONFERENCE ROOM AND OFFICE #1 DOORS SHALL
 MEET THE REQUIREMENTS OF FBC SECTION 11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25.
  
 4) SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES UNDERNEATH THE SINK. PROVIDE ELEVATION DETAIL
 DRAWINGS SHOWING THESE REQUIREMENTS.
  
 5) SHEET A3 IS MISSING THE SEAL, SIGNATURE AND DATE OF
 THE DESIGN PROFESSIONAL. THE SEAL OF THE ENGINEER IS
 NOT LEGIBLE. 106.1.3* THE SEAL SHALL BE OF SUFFICIENT
 CLARITY FOR OUR RECORDS MANAGEMENT PROGRAM. TITLE BLOCK
 WITH THE INFORMATION SPECIFIED PER 61G1-16.004 FAC
 SHALL BE PRESENT ON DRAWINGS ISSUED BY THE RESPONSIBLE
 ARCHITECT AND MUST, AT A MINIMUM CONTAIN
 1) FIRM NAME, ADDRESS, AND TELEPHONE #
 2) FIRM LICENCE #
 3) NAME OF PROJECT
 4) DATE PREPARED
 5) A SPACE FOR SIGNATURE & DATED SEAL
 6) A SPACE FOR PRINTED NAME OF PERSON SEALING THE
 DOCUMENT
  
 6) THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 INCLUDING STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISHES, MARKETING COST, OVERHEAD AND PROFIT
 EXCLUDING LAND VALUE. OUR VALUARTION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-13 Cont ID  
Sent By btrobaug Date 2008-11-13 Time 17:01 Rev Time 0.00
Received By btrobaug Date 2008-11-13 Time 14:07 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By btrobaug Date 2008-10-03 Time 10:36 Rev Time 0.00
Received By btrobaug Date 2008-10-03 Time 09:19 Sent To  
Notes
2008-10-03 10:34:47 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE
 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND FOR
 LIGHTING DENSITIES. ALL THAT IS REQUIRED FOR THE
 ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE
 REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE
 CALCULATION PROCEDURES, GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED
 INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH
 SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR
 LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.THE PLAN INDICATES NEW LIGHTING.
  
 3} THE PANEL SCHEDULE SCHEDULE MUST COMPLY WITH 408.4
 AND BE ROOM SPECIFIC.
  
 4} THE EMERGENCY LIGHTING MUST COMPLY WITH 700.12(F)-"
 THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE
 THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES." A NOTE ON THE PLAN WILL SATISFY THIS
 REQUIREMENT.
  
 5} THERE IS A RECEPTACLE SHOWN AT THE NEW WATER HEATER
 LOCATION. SEE 422.16 FLEXIBLE CORDS
 (A) GENERAL FLEXIBLE CORD SHALL BE PERMITTED (1) FOR
 THE CONNECTION OF APPLIANCES TO FACILITATE THEIR
 FREQUENT INTERCHANGE OR TO PREVENT THE TRANSMISSION OF
 NOISE OR VIBRATION OR (2) TO FACILITATE THE REMOVAL OR
 DISCONNECTION OF APPLIANCES THAT ARE FASTENED IN PLACE,
 WHERE THE FASTENING MEANS AND MECHANICAL CONNECTIONS
 ARE SPECIFICALLY DESIGNED TO PERMIT READY REMOVAL FOR
 MAINTENANCE OR REPAIR AND THE APPLIANCE IS INTENDED OR
 IDENTIFIED FOR FLEXIBLE CORD CONNECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-12 Cont ID  
Sent By mwennerg Date 2008-11-12 Time 14:08 Rev Time 0.00
Received By mwennerg Date 2008-11-12 Time 14:08 Sent To  
Notes
2008-11-12 14:13:24LIFE SAFETY TO COMPLY WITH NFPA 101, 2003. RED LINED
 EXIT SIGN ON SHEET E-1 TO INDICATE CORRECT DIRECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-10-08 Time 10:35 Sent To  
Notes
2008-10-08 10:42:56***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) IS THIS PROJECT CURRENTLY PROTECTED BY AN AUTOMATIC
 FIRE SPRINKLER SYSTEM?
  
 4) PROVIDE LOCATION(S) OF REQUIRED 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
 5) THE EXIT SIGN LOCATED NEXT TO OFFICE #1 APPEARS TO
 BE DIRECTIONAL. WHAT WOULD PREVENT PERSONS FROM EXITING
 INTO THE CONFERENCE ROOM AND NOT THROUGH THE 3'-0"
 OPENING?
  
 6) PLEASE SEE OTHER REVIEW COMMENTS REGARDING FS AND
 FAC REQUIREMENTS FOR PLANS.
  
 7) PLANS INDICATE A RELOCATED FIRE ALARM AND
 THERMOSTAT, BUT DOES NOT INDICATE WHAT THE FIRE ALARM
 EQUIPMENT IS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 09:21 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 09:21 Sent To M
Notes
2008-12-24 09:21:58TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 08:33 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 08:33 Sent To  
Notes
2008-11-05 08:33:58TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-08 Cont ID  
Sent By mperson Date 2008-10-08 Time 13:55 Rev Time 0.00
Received By mperson Date 2008-09-24 Time 15:14 Sent To PC
Notes
2008-09-24 15:22:03TO "BOB"#18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 10:13 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 10:10 Sent To PC
Notes
2009-01-10 10:13:17REVISED M1. NOTE: TRANSFER DUCTS IN SOME AREAS ARE NOT
 SIZED TO MEET THE EXCEPTIONS UNDER FBCM 601.4. THESE
 AREAS WILL REQUIRE A FIELD TEST TO VERIFY PRESSURE
 DIFFERENCES ACROSS CLOSED DOORS ARE LESS THAN 0.01" WC
 IN ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-05 Cont ID  
Sent By tgordon Date 2008-11-05 Time 11:00 Rev Time 0.30
Received By tgordon Date 2008-11-05 Time 11:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By tgordon Date 2008-09-30 Time 09:55 Rev Time 0.45
Received By tgordon Date 2008-09-30 Time 09:55 Sent To  
Notes
2008-09-30 10:13:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE ENGINEER WROTE BY HIS SEAL 'STRUCTURAL ONLY' IF
 THE ENGINEER IS NOT TAKING RESPONSIBILITY FOR THE
 MECHANICAL DESIGN ON THE PAGE THEN HAVE THE MECHANICAL
 ON A SEPARATE PAGE WITH THE INFORMATION OF THE PERSON
 TAKING RESPONSIBILITY FOR IT. SEE FAC 61G15-34.003 AND
 FS 471.003 (H).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2008-11-10 Cont ID  
Sent By mperson Date 2008-11-10 Time 09:33 Rev Time 0.30
Received By mperson Date 2008-11-10 Time 09:33 Sent To  
Notes
2008-11-10 09:40:26NOTE: THERE IS NO PROPOSED PLUMBING BEING INDICATED ON
 THE RESUBMITTED PLANS AND THERE IS NO PLUMBING PERMIT
 BEING APPLIED FOR AT THIS TIME. THE OCCUPANCY HAS
 EXISTING H/C BATHROOMS. THE DRINKING FOUNTAIN THAT WAS
 ASKED FOR IN THE FIRST PLUMBING REVIEW IS NOT REQUIRED
 DUE TO THIS BEING AN EXISTING BUILDING WITH NO CHANGE
 IN OCCUPANY AND PER FBC-2004 EXISTING BUILDING CODE
 SECTION 610.1 MINIMUM FIXTURES. THE OCCUPANCY LOAD IS
 NOT BEING INCREASED BY MORE THAN 20 PERCENT. *MRPERSON.

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By mperson Date 2008-10-08 Time 13:03 Rev Time 1.00
Received By mperson Date 2008-10-08 Time 13:03 Sent To I
Notes
2008-10-08 13:55:01PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A2 IS INDICATING A PROPOSED SINK THAT IS
 REQUIRED TO BE ACCESSIBLE. PLEASE PROVIDE THE FOLLOWING
 PER THE FBC-2004, CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE SECTIONS.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.2 HEIGHT. MAXIMUM 34" A.F.F. TO RIM OR
 COUNTER.
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 2. SHEETS A1 EXISTING FLOOR/DEMOLITION PLAN AND SHEET
 A2 PROPOSED FLOOR PLAN FAIL TO INDICATE THE REQUIRED
 ACCESSIBLE DRINKING FOUNTAIN FOR A BUSSINESS OCCUPANCY.
 PER FBC-2004 PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES. PLEASE KNOW THAT THE
 REQUIRED DRINKING FOUNTAIN MUST BE COMPLIANT WITH THE
 FBC-2004, CHAPTER 11, FLORIDA ACCESSIBILITY CODE
 SECTIONS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 3. PLEASE KNOW THAT IF THERE IS NOT AN EXISTING
 DRINKING FOUNTAIN THAT ONE WILL NEED TO BE ADDED TO
 SHEET A3 SANITARY ISOMETRIC. PER FBC-2004 CHAPTER 1
 (W.P.B. AS AMENDED) SECTION 106.3.5.1.3 PLUMBING (4),
 (6), (13) AND PER FBC-2004 PLUMBING SECTION 701.1
 SCOPE.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 5. SHEET A3 HAS AN ENGINEER'S TITLE BLOCK, HOWEVER THE
 REQUIRED SEAL, SIGNATURE AND DATE OF THE DESIGN
 PROFESSIONAL ARE MISSING. THE ENGINEER WHOSE NAME
 APPEARS ON THE TITLE BLOCK MUST SIGN, DATE AND SEAL THE
 DOCUMENT. PER FAC 61G15-23.002.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731