Plan Review Details - Permit 08090593
Plan Review Stops For Permit 08090593
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2009-04-06 Cont ID  
Sent By jnguyen Date 2009-04-06 Time 16:27 Rev Time 0.00
Received By jnguyen Date 2009-04-06 Time 15:23 Sent To  
Notes
2009-04-06 16:23:30I HAVE ANALYZED THE SITE PLANS & CONSULTED WITH JIM
 WITMER TO PINPOINT THE EXACT LOCATION OF THE
 FREE-STANDING PAVILION AREA (SLIGHTLY TO THE NORTHEAST
 OF THE SWA OPERATIONS BUILDING AT 6880 N JOG RD) IN THE
 EAST PARCEL BOUNDARY. UNDER PCN# 74424227000001010 -
 SEQUENTIAL UNIT RECORD 0008, I HAVE ASSIGNED THIS
 PAVILION THE SECONDARY ADDRESS OF 6882 N JOG RD. I
 NOTIFIED ALL THE RELEVANT PARTIES VIA E-MAIL & HAVE
 RETURNED THE PERMIT APPLICATION FOLDER & SITE PLANS TO
 THE BOX.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-10-22 Cont ID  
Sent By jnguyen Date 2008-10-22 Time 14:46 Rev Time 0.00
Received By jnguyen Date 2008-10-22 Time 10:40 Sent To  
Notes
2008-10-22 14:32:50THIS PERMIT# 08090593 IS BEING ATTACHED TO THE WRONG
 PCN# 74-42-42-34-00-000-1010 WHEN IT ACTUALLY SHOULD BE
 CONNECTED TO PCN# 74-42-42-27-00-000-1010. I HAVE
 ISSUED THE EXISTING 6880 N JOG RD TO THE PROPOSED SWA
 OPERATIONS BUILDING BECAUSE LILI CREATED THIS ADDRESS
 POINT IN GIS ON 12-20-2007 & LISTED IT FOR THIS
 SPECIFIC PURPOSE (IN CP LISTED AS UNIT 0006 UNDER THE
 CORRECT PCN# 74-42-42-27-00-000-1010). I HAVE ALSO
 ISSUED 6890 N JOG RD FOR THE PROPOSED SWA MAINTENANCE
 BUILDING (IN CP LISTED AS UNIT 0007 UNDER THE CORRECT
 PCN# 74-42-42-27-00-000-1010).

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-06-03 Cont ID  
Sent By jwitmer Date 2009-06-03 Time 10:30 Rev Time 0.77
Received By jwitmer Date 2009-06-03 Time 09:45 Sent To  
Notes
2009-06-03 10:46:30OPERATIONS BUILDING - PASSED
 6-03-09 CONTRACTOR HAS SUBMITTED FOR SEPERATE PERMIT
 FOR THE ;
  
 MAINTENACE BUILDING: 09060065 6890 N JOG RD- PASSED
  
 PAVILION: 09060067 6882 N JOG RD- DENIED
  
 NOTES : COMMENT FOR THE PAVILION FROM THE LAST REVIEW
 WILL NOW BE TRANSFERRED TO THE NEW PAVILION PERMIT .
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-06-01 Cont ID  
Sent By jwitmer Date 2009-06-01 Time 13:12 Rev Time 0.55
Received By jwitmer Date 2009-06-01 Time 13:10 Sent To  
Notes
2009-06-01 13:15:28 
 BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:WEST CONSTRUCTION
 TEL: (561)248-3868
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B
 1,800 SQ FT
 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B
 1,000 SQ FT
 6882 N JOG RD. PAVILION TYPE II-B 728 SQ FT.
  
 THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE
 PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND
 ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE
 INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING,
 AND SEPERATE TRACKING OF INSPECTIONS.
  
 THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE
 ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT
 NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION.
  
 1-12) COMPLIED.
  
 13) THIRD REQUEST, 1ST UNDER PERMIT APPLICATION. THE
 RESPONSE COMMENTS INDICATE THIS TO BE A PAVILION, TO BE
 PART OF THIS PERMIT WE DO NEED INFORMATION AS FAR AS
 COMPONENTS AND CLADDING YOU INDICATE THIS IS A
 PRE-ENGINEERED CANOPY, EITHER IT HAS GONE THROUGH THE
 MANUFACTURED BUILDING PROGRAM WITH THE STATE AND IS
 APPROVED AS A MANUFACTURED MODULAR BUILDING PROGRAM
 WITH STATE APPROVED PLANS OR IT WILL NEED PRODUCT
 APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT PLANS THIS
 AREA WILL BE EXEMPTED FROM THE PERMIT AND PLANS TO BE
 SUBMITTED UNDER A SEPERATE PERMIT.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE
 FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS
 FOR RATED WALLS BEING BUILDINGS AND OPENING
 PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS,
 NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS
 PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004
 FL 3778-R1
 IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING
 SUBSHEATHING DECK. 1507.4.1.
  
 14-17) COMPLIED.
  
 18) 3RD REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A
 BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION,
 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM.
 PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 19) 3 RD REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING
 ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE
 PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO
 NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY.
 WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE
 PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE
 PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 20)2 COMPLIED.
  
 21)INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1,
 IS THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL
 BE REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE
 AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE
 GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD.
  
 22) STAIR DELETED, COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 B

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-04-06 Cont ID  
Sent By jwitmer Date 2009-04-06 Time 14:18 Rev Time 2.22
Received By jwitmer Date 2009-04-06 Time 14:18 Sent To  
Notes
2009-04-06 14:29:56BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (772)231-4301
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B
 1,800 SQ FT
 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B
 1,000 SQ FT
 6882 N JOG RD. PAVILION TYPE II-B 728 SQ FT.
  
 THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE
 PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND
 ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE
 INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING,
 AND SEPERATE TRACKING OF INSPECTIONS.
  
 THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE
 ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT
 NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION.
  
 1-12) COMPLIED.
  
 13) THIRD REQUEST, 1ST UNDER PERMIT APPLICATION. THE
 RESPONSE COMMENTS INDICATE THIS TO BE A PAVILION, TO BE
 PART OF THIS PERMIT WE DO NEED INFORMATION AS FAR AS
 COMPONENTS AND CLADDING YOU INDICATE THIS IS A
 PRE-ENGINEERED CANOPY, EITHER IT HAS GONE THROUGH THE
 MANUFACTURED BUILDING PROGRAM WITH THE STATE AND IS
 APPROVED AS A MANUFACTURED MODULAR BUILDING PROGRAM
 WITH STATE APPROVED PLANS OR IT WILL NEED PRODUCT
 APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT PLANS THIS
 AREA WILL BE EXEMPTED FROM THE PERMIT AND PLANS TO BE
 SUBMITTED UNDER A SEPERATE PERMIT.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE
 FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS
 FOR RATED WALLS BEING BUILDINGS AND OPENING
 PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS,
 NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS
 PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004
 FL 3778-R1
 IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING
 SUBSHEATHING DECK. 1507.4.1.
  
 14-17) COMPLIED.
  
 18) 3RD REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A
 BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION,
 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM.
 PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 19) 3 RD REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING
 ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE
 PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO
 NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY.
 WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE
 PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE
 PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 20)2 COMPLIED.
  
 21)INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1,
 IS THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL
 BE REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE
 AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE
 GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD.
  
 22) STAIR DELETED, COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-06 Cont ID  
Sent By jwitmer Date 2009-01-06 Time 08:39 Rev Time 5.55
Received By jwitmer Date 2009-01-05 Time 16:00 Sent To  
Notes
2009-01-06 09:03:04BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (772)231-4301
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 OFFICE BUILDING TYPE II-B 1,800 SQ FT
 S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT
  
 JAN 06/2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
 1B) PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C-1E) COMPLIED.
  
 2) 2ND REQUEST, COMMENT RESPONSE SHEET INDICATES SOILS
 REPORTS WERE SUBMITTED, NOT IN THIS REVIEW. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) COMPLIED, BUILDING PROVISO: 109.3.10* IMPACT OF
 CONSTRUCTION.
  
 4) COMPLIED, BUILDING PROVISO: 109.3.10.1 HURRICANE
 PROTECTION.
  
 5) COMPLIED.
  
 6) ENERGY CALCULATION ARE IN THIS SUBMITTAL, BUT ARE
 THE WRONG VERSION . PLEASE REVIEW SECTION 13-400.3..A.
  
 7-10) THE COUNTY DOES NOT REQUIRE PRODUCT APPROVALS AT
 TIME OF PERMIT SUBMISSION. THE CITY OF WEST PALM DOES
 REQUIRE THE FULL PRODUCT APPROVAL PACKAGE, THERE ARE
 OLD MIAMI-DADE REPORTS THAT STILL HAVE NOT HAD THEIR
 ANCHOR CALCULATION UPDATED TO THE 2004 FBC, WHICH MEANS
 UNDER THE 2001 FBC 1.33 INCREASES WERE TAKEN IN STEEL
 FASTENERS, 1605.3.1.1. AS STATED IN COMMENT (1B)
 PRODUCT APPROVAL REPORTS ARE REQUIRED AT TIME OF
 APPLICATION. HIGHLIGHT GLAZING SYSTEM TO BE USED IF
 THERE IS MULTIPLE GLAZING UNIT TYPES.
  
 7) 2ND REQUEST,1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST. 2. GLAZED OPENINGS LOCATED MORE
 THAN 30 FEET (9.1 M) ABOVE GRADE SHALL MEET THE
 PROVISIONS OF THE SMALL MISSILE TEST.
  
 8)2ND REQUEST, FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS,
 MISSING REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS
 8B) MULLIONS
 8C) EXTERIOR GLAZED DOORS
 8D) EXTERIOR METAL DOORS
 8E) ROLL UP DOORS
 8F) WALL LOUVERS
 8G) TRUSS ANCHORS
 8H) ROOF ASSEMBLIES
 8I) SOFFITS
  
 9) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 10) 2ND EQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 OFFICE BUILDING TYPEII-B
  
 11A) COMPLIED.
  
 11B) 2ND REQUEST, SHEET A-11 & SHEET A-14 APPEAR TO
 HAVE A 2'X2' LAY IN TILE CEILING, PLANS DO NOT PROVIDE
 HOW THE 1 HOUR RATING OF WALLS IS TO OCCUR, THROUGH TO
 THE ROOF DECK OR A 1HR RATED CEILING. 708.1.
 A) YOUR RESPONCE IS CONFUSING, SHEET AD-3, THE NOTE
 ADDED TO EXTEND DRYWALL AND INSULATION TO THE UNDER
 SIDE OF THE ROOF DECK DOES NOT TIE TO A WALL TYPE. A
 GENERIC WALL TYPE IS DEPICTED AND THE
 NOTE IS NOT LOCATED NEXT TO WALL TYPE 2A A NONRATED
 WALL NOR NEXT TO 2-1 A 1 HR RATED WALL ASSEMBLY.
  
 B) PLEASE PROVIDE THE DETAIL OF HOW THE RATED WALL WILL
 FASTEN INTO THE ROOF DECK ASSEMLBY, ALSO NOTE WHAT TYPE
 OF FLEXIBLE SEALENT SHALL BE USED.713.1 FIRE RESISTANT
 JOINT SYSTEMS.
  
 C) THIS SAME CORRIDOR 111 HAS A DOOR# 107 WHICH IS PART
 OF THE RATED CORRIDOR THE DOOR SCHEDULE DOES NOT
 INDICATE AS SUCH TABLE 1016.1.
  
 D) AD-3 LIFE SAFETY SHEET WILL ALSO NEED TO BE UPDATED
 FOR A RATED LOBBY WALL AND DOOR 107.
  
 E) THE RATING OF CORRIDOR 111 FOR 1 HOUR IS REQUIRED
 BECAUSE OF THE OCCUPANT LOAD BEING GREATER THAN 30 FOR
 TRAINING ROOM AND BREAK ROOM WHEN THE FOLDING PARTITION
 IS NOT USED. IT BECOMES AN
 ASSEMBLY OCCUPANCY REQUIRING THE CORRIDOR 111TO BE
 RATED FOR 1 HR. THIS RATING WILL CONTINUE THROUGH TO
 THE EXIT. THE LOBBY AREA WALL IS NOT INDICATED AS A
 FIRE RATED WALL. 1016.5CORRIDOR CONTINUITY
 FIRE-RESISTANCE-RATED CORRIDORS SHALL BE CONTINUOUS
 FROM THE POINT OF ENTRY TO AN EXIT, AND SHALL NOT BE
 INTERRUPTED BY INTERVENING ROOMS. EXCEPTION: FOYERS,
 LOBBIES OR RECEPTION ROOMS CONSTRUCTED
 AS REQUIRED FOR CORRIDORS SHALL NOT BE CONSTRUED AS
 INTERVENING ROOMS. THE LOBBY CAN BE USED AS PART OF THE
 MEANS OF EGRESS BUT THE WALL LABELED 2A WILL NEED TO BE
 RATED ONE HOUR.
  
 F) CORRIDOR 101 IS WITHIN A BUSINESS OCCUPANCY AND WILL
 NOT BE REQUIRED TO BE 1 HR RATED, IF THE DESIGNER
 WISHES TO RATE THIS CORRIDOR YOU MAY DO THAT.
  
 11C-D) COMPLIED.
  
 12)2ND REQUEST SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH
 11-4.22.2 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS
 SHALL COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIXTURE. SEE ROOMS
 120,& 121.
 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. OTHER TOILET ROOMS
 PROVIDED FOR THE USE OF OCCUPANTS OF SPECIFIC SPACES
 (I.E., A PRIVATE TOILET ROOM FOR THE OCCUPANT OF A
 PRIVATE OFFICE) SHALL BE ADAPTABLE. IF BATHING ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE BATHROOM
 SHALL COMPLY WITH SECTION 11-4.23. ACCESSIBLE TOILET
 ROOMS AND BATHING FACILITIES SHALL BE ON AN ACCESSIBLE
 ROUTE.
  
 13) 2ND REQUEST, THE RESPONSE COMMENTS INDICATE THIS TO
 BE A PAVILION, TO BE PART OF THIS PERMIT WE DO NEED
 INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED
 PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. WITHOUT
 PLANS THIS AREA WILL BE EXEMPTED FROM THE PERMIT AND
 PLANS TO BE SUBMITTED UNDER A SEPERATE PERMIT.
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 15-17) COMPLIED.
 T THE CONNECTION STATES THAT WELDING OF CONNECTIONS IS
 PROHIBITED, PLEASE PROVIDE MANUFACTURERS APPROVAL FOR
 WELDING OF THIS TYPE OF CONNECTION. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 18) 2ND REQUEST. SHEET S-4 INDICATES A FOOTING TYPE A
 BUT THE PLANS ARE LACKING COLUMN AND BEAM INFORMATION,
 1609.2.1 PART OFTHE MAIN WIND FORCE-RESISTING SYSTEM.
 PLEASE PROVIDE ADDITONAL INFORMATION, 106.1..2. 106.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 19) 2ND REQUEST, SHEET A-4 ALSO INDICATES THE ROOFING
 ASSEMBLY TO BE A PREMANUFACTRED CANOPY, PLEASE PROVIDE
 PRODUCT INFORMATION, TO BE PART OF THIS PERMIT WE DO
 NEED INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU
 INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS
 GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE
 STATE AND IS APPROVED AS A MANUFACTURED MODULAR
 BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL
 NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY.
 WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE
 PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE
 PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
  
 20)2ND REQUEST, STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF
 PRESSURE ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO
 INDICATE CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES,
 PLEASE REVIEW FIGURE 1609.6.2.2 COMPONENTS AND
 CLADDING. WITH THE RESPONSE FOR THIS COMMENT IT APPEARS
 THAT YOUR CODE BOOK HAS NOT BEEN UPDATED. IN 2006
 SUPPLEMENTS( BLUE PAGES) THE TABLE 1609.6C HAS BEEN
 ELIMINATED. PLEASE REVISE SHEET S-6 FOR PRESSURES IN
 ZONE 3.
  
 21) 2ND REQUEST, GENERATOR PAD IS SHOWN ON SHEET SD-1,
 IS THIS PAD GOING TO BE PART OF THIS PERMIT OR JUST
 INFORMATIONAL, THE GENERATOR AND ATTACHMENT TO SLAB
 WILL BE REVIEWED UNDER A SEPERATE PERMIT. PLEASE
 PROVIDE SIZE OF GENERATOR PAD, IF STELL REINFORCEMENT
 IS TO BE INSTALLED AND ANCHORS TO RESIST THE MOMENT OF
 OVER TURNING. 1609.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDDING.
  
 22) STAIR DELETED, COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-10 Cont ID  
Sent By jwitmer Date 2008-10-10 Time 09:41 Rev Time 8.55
Received By jwitmer Date 2008-10-10 Time 09:41 Sent To  
Notes
2008-10-10 12:15:00BUILDING PLAN REVIEW
 PERMIT: 08090593
 ADD: 6880 N JOG RD
 CONT:MAJOR WORKING DRAWING REVIEW
 TEL: (772)231-4301
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 OFFICE BUILDING TYPE II-B 1,800 SQ FT
 S-2 MAINTENANCE BUILDING TYPE II-B 1,000 SQ FT
  
 OCT 10,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) BOTH THE ARCHITECTURAL AND STRUCTURAL PLANS
 INDICATE A PAVILION NEST TO THE ADMINISTRATIVE OFFICE
 THE PLAN REVIEW SHEET SUBMITTED ONLY INDICATES A REVIEW
 FOR THE OPERATIONS BUILDING AND MAINTENACE BUILDING .
 IS THIS STRUCTURE TO BE PERMITTED WITH THIS WORK? IN
 THE MINIMUM BUILDING CLASSIFICATION TYPE, IS THIS
 STRUCTURE TO BE CONSIDERED IN THE SQ FT OF THE
 OPERATIONS BUILDING UNDER SECTION 503.1.3 OR TWO
 SEPERATE STRUCTURES WHERE TABLE 602 AND 704.8 WILL NEED
 TO BE CONSIDERED? ADDITIONAL INFORMATION REQUIRED,
 106.1.2.
  
 1E) I PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS, PLEASE REVISE.
  
 2) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 5) NOTE SHEET CD-6 IS NOT SIGNED NOR SEALED, PLEASE
 CORRECT. SHEET PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 6) PLANS DO NOT ENCLUDE ENERGY CALCULATIONS 106.3.5.1.4
 AND INPUT ENERGY CALCULATIONS.
  
 7) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS
 8B) MULLIONS
 8C) EXTERIOR GLAZED DOORS
 8D) EXTERIOR METAL DOORS
 8E) ROLL UP DOORS
 8F) WALL LOUVERS
 8G) TRUSS ANCHORS
 8H) ROOF ASSEMBLIES
 8I) SOFFITS
  
 9) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 OFFICE BUILDING TYPEII-B
  
 11A) SHEET A3 INDICATES THE CORRIDOR# 111 TO BE ONE
 HOUR RATED, THERE IS NO DOOR BETWEEN THE CORRIDOR AND
 LOBBY 100, PLEASE INDICATE HOW OPENING PROTECTIVE
 (715.3) ARE ACHIEVED IN THIS AREA.
  
 11B) SHEET A-11 & SHEET A-14 APPEAR TO HAVE A 2'X2' LAY
 IN TILE CEILING, PLANS DO NOT PROVIDE HOW THE 1 HOUR
 RATING OF WALLS IS TO OCCUR, THROUGH TO THE ROOF DECK
 OR A 1HR RATED CEILING. 708.1.
  
 11C) SHEET A-4 INDICATES WALL TYPE AS 1 HOUR RATED
 WALLS WITH WALL TAG (AD3) WITHIN THE CORRIDORS, SHEET
 AD-1 INDICATES WITHIN THE DOOR LEGOND 45 MINUTE OPENING
 PROTECTION FOR THE DOORS, DOOR D114 & D115 INDICATE THE
 WRONG TYPE OF FRAMES, PLEASE CORRECT.
  
 11D) SHEET A-4 CORRIDORS ARE INDICATED AS A 1 HOUR FIRE
 RATED CORRIDORS BUT THERE IS NO SEPERATION OF THE 1
 HOUR RATED CORRIDOE AND THE FILE STORAGE ROOM# 107.
  
 12) SHEET A-8 PLEASE PROVIDE COMPLIANCE WITH 11-4.22.2
 DOORS. ALL DOORS TO ACCESSIBLE TOILET ROOMS SHALL
 COMPLY WITH 11-4.13. DOORS SHALL NOT SWING INTO CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 SEE ROOMS 117, 120, 121, & 1124.
  
 13) SHEET A-14 THE REFLECTED CEILING PLAN INDICATES A
 LARGE SQUARE TO THERIGHT OF THE RIGHT OF THE KITCHEN
 AND MECANICAL ROOM 24'X30' WITH 3 LIGHT FIXTURES? SHEET
 E-5 THIS AREA APPEARS EITHER AS ANOTHER
 BUILDING OR A OPEN PAVILION,(SHEET S2-S3) IS THIS
 STRUCTURE TO BE PART OF THIS PERMIT? ARE THEY TO
 REQUIRE FIRE SEPERATION BETWEEN THE TWO BUILDINGS TABLE
 602, OR ARE THEY TO BE CONSIDEREDAS ONE BUILDING AS
 UNDER SECTION 503.1.3 TWO BUILDINGS ON THE SAME LOT.
  
 14) SHEET A-7 INDICATES A BRICK VENNEER PLEASE PROVIDE
 DOCUMENTATION AS HOW THE VENEERS ARE TO BE ADHERRED.
 PLEASE SEE SECTION 2114.2 CONCRETE BEARING LEDGE.
 BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A
 CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL
 THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS
 POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO
 SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL
 CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT
 SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE
 IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL
 BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL
 SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED
 IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW
 GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED
 TO THE CAVITY CREATED BETWEEN THE VENEER AND THE
 FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 ACI 530/ASCE 5/TMS 402, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXIST BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
  
 15) SHEET S-2 DOES NOT INDICATE COMPLIANCE WITH 1816.1
 TERMITE PROTECTION.
  
 16) SHEET S-3 INDICATES THE TYPE OF CONNECTION TO BE
 USED AT EACH TRUSS LOCATION BUT THE FORCES THE
 CONNECTION NEEDS TO RESIST IS NOT PROVIDED, VERTICAL,
 HORIZONTAL AND LATERALL LOADS. 1609.2.1.
 PART OF THE MAIN WINDFORCE-RESISING SYSTEM. NOTE
 CONNECTION TYPE TS1WTCS INFORMATION COULD NOT EVEN BE
 ACCESSED ON THE TRUSSTEEL WEBSITE.
  
 17) SHEET S-3 TRUSS NOTE# 5 INDICATES TO SEE TRUSSSTEEL
 STANDARD DETAIL TS027A FOR THE WELDING OF TRUSS
 CONNECTION TO STEEL BEAM, NO SUCH DETAILS HAVE BEEN
 PROVIDED. NOTE IN MANY CASES
 THE MANUFACTURER OF THE CONNECTION STATES THAT WELDING
 OF CONNECTIONS IS PROHIBITED, PLEASE PROVIDE
 MANUFACTURERS APPROVAL FOR WELDING OF THIS TYPE OF
 CONNECTION. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 18) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS
 ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART
 OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE
 ADDITONAL INFORMATION, 106.1..2.
  
 19) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE
 A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT
 INFORMATION, WILL NEED TO MEET THE REQUIREMENTS OF
 COMMENT NUMBER 8,9 & 10.
  
 20) STRUCTURAL SHEETS S-4, S-6 AND S-8 ROOF PRESSURE
 ZONES FAIL TO INDICATE PRESSURE ZONE 3 FAIL TO INDICATE
 CORNER ZONE# 3 AND THE ASSOCIATED PRESSURES, PLEASE
 REVIEW FIGURE 1609.6.2.2 COMPONENTS AND CLADDING.
  
 21) GENERATOR PAD IS SHOWN ON SHEET SD-1, IS THIS PAD
 GOING TO BE PART OF THIS PERMIT OR JUST INFORMATIONAL,
 THE GENERATOR AND ATTACHMENT TO SLAB WILL BE REVIEWED
 UNDER A SEPERATE PERMIT.
  
 22) SD-3 PLANS INDICATE STAIRS BUT THE STAIR LOCATION
 IS NOT SHOWN ON THE ARCHITECTURAL PLANS NOR THE
 STRUCTURAL PLAN INDICATES THEY ARE TO BE LOCATED WITHIN
 THE OPERATIONS AND MAINTENANCE BUILDING, WHERE /
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-05-29 Cont ID  
Sent By dpalmer Date 2009-05-29 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2009-05-29 Time 10:13 Sent To  
Notes
2009-05-29 10:14:04*** NOTES/ REDLINES****
  
 1) NOTE: MANUFACTURES SPECS/CUT SHEETS WERE SUBMITTED
 FOR THREE COMPLETELY DIFFERENT TRANSFER SWITCHES.
 A) ONE AS AUTOMATIC NON SERVICE ENTRANCE RATED.
 B) ONE FOR NON-AUTOMATIC, MTS.
 C) ONE FOR SERVICE ENTRANCE RATE AUTOMATIC TRANSFER
 SWITCH.
  
 AS THE RISER INDICATES AND REQUIRES THE SWITCH TO BE
 SERVICE ENTRANCE RATED ONLY *(C) * ABOVE MEETS AND
 COORDINATES WITH RISER.
  
 THE SPECS/CUT SHEETS FOR BOTH A AND B WAS REMOVED FROM
 SETS TO ALLEVIATE ANY CONFUSION.
  
 2) NOTED FOR INFORMATION. THE NEW BUILDING OFFICIAL
 WILL BE REQUIRING THE MAINTENANCE/OPERATION BUILDING TO
 BE UNDER SEPARATE PERMIT. THE SAME PLANS WILL BE USED ,
 HOWEVER WILL NEED SEPARATE APPLICATION. PLEASE CONTACT
 DOUGLAS WISE FOR ANY QUESTIONS. 561-805-6654
  
 3) NOTE: GATE SHALL BE UNDER SEPARATE FENCE PERMIT
 ALONG WITH PLANS.
  
 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS DATE, PHONE, AND
 CAMERAS ALL SHALL BE UNDER SEPARATE PERMITS. ** MAY
 REFERENCE THESE PLANS IF NO CHANGES ARE MADE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-03-30 Cont ID  
Sent By dpalmer Date 2009-03-30 Time 10:48 Rev Time 0.00
Received By dpalmer Date 2009-03-30 Time 10:48 Sent To  
Notes
2009-03-30 10:48:38** DENIED REVIEW **
 3RD REVIEW, 1ST REVIEW UNDER PERMIT APPLICATION.
  
  
 1) NOTE: PLEASE BE SURE ALL INFORMATION ON THE INPUT
 DATA REPORT OF THE SUBMITTED ENERGY CALCULATIONS
 COORDINATES WITH THE PLANS. THIS HAS BEEN NOTED FOR THE
 THIRD TIME. 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PREVIOUS REVIEW GAVE SOME EXAMPLES OF ITEMS ON PLANS
 WHICH WERE NOT IN THE IDR. THE EXTERIOR LIGHTING WAS
 NOTED AS AN EXAMPLE; HOWEVER THERE IS A SUBSTANTIAL
 AMOUNT OF EXTERIOR FIXTURES ON PLANS WHICH ARE STILL
 NOT IN THE IDR.
 FOR EXAMPLE: WHAT ABOUT ALL THE LIGHTING ON SHEET E-2?
  
 FOR EXAMPLE: THE IDR SHOWS MANUAL CONTROLS FOR ALL
 INTERIOR LIGHTING. PLANS DO NOT SHOW THE SAME.
  
 FOR EXAMPLE: THE M FIXTURE ON THE FIXTURE LEGEND IS
 SHOWN WITH 2-42WATT BULBS YET THE IDR ONLY INDICATES
 ONE -42WATT BULB IN EACH FIXTURE.
 THE M FIXTURES ON E-8 ARE MISSING IN THE COUNT ALSO.
  
 FOR EXAMPLE: THE KW RATING OF THE WATER HEATER ON PLANS
 IS GREATER THAN THAT OF THE IDR.
  
 PLEASE BE SURE THE ENERGY CALCULATIONS CERTIFICATION
 SHEET IS SIGNED, DATED AND SEALED. THE COVER SHEET IS
 NOT COMPLETE AS AN EXCEPTION FOR COVER SHEETS OF
 REPORTS. FS 471.025, FAC 61G15-23.002
 13-101, 13-103.1.1.1, 13-400.A.3
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2 FOR SPACE
 CONTROLS REQUIRED IN ROOMS 114/115. THE RESPONSE SEEMS
 TO MAKE NOTE OF POLE SWITCHES. WHERE IS THE OCCUPANCY
 SENSORS/DEVICES LOCATED? SEE SECTION 13-415.1.ABC.1.2
 FOR CONFERENCE ROOMS AND BREAK ROOMS WHICH REQUIRE
 OCCUPANCY SENSORS OF SOME TYPE. LIGHTING NEEDS TO BE
 TURNED OFF WITHIN 30MINS. IT IS NOT CLEAR HOW THE
 DEVICES AND THE NOTES PROVIDED WILL ACCOMPLISH THIS
 REQUIREMENT.
 BASED ON THE SYMBOL LEGEND THESE ARE STANDARD DEVICES.
  
 3) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE SERVICE ENTRANCE RATED MAIN/ATS. THE
 RESPONSE MENTIONS THIS WILL BE DONE BY CONTRACTOR
 HOWEVER NO SUBMITTAL WAS IN THE SUBMITTED
 PLANS/PACKAGE.
 THE RESPONSE LETTER GOES INTO DETAIL WITH RESPECT TO
 THE MANUFACTURE WHICH IS NOT KNOWN AT THIS TIME BASED
 ON THE BID PROCESS ETC. PLEASE SUBMIT ANY LISTED SE
 RATE MAIN/ATS WHICH MEETS LISTING REQUIREMENTS AND
 MINIMUM CODE REQUIREMENTS. AS LONG AS A PRODUCT IS
 CHOSEN WHICH MEETS CODE THE, SUBMITTAL MAY ALWAYS BE
 CHANGED AT A LATER DATE.
 110.3, 90.7, 230.70, 230.76, 230.79.
  
 ** AN EXAMPLE WOULD BE JUST LIKE A WINDOW PRODUCT
 APPROVAL: A WINDOW IS REQUIRED TO BE CHOSEN MEETING
 MINIMUM WIND LOADS, IMPACT RATINGS ETC AND HAVE FLORIDA
 PRODUCT APPROVAL/MIAMI-DADE APPROVAL. THAT WINDOW MAY
 NOT BE THE ONE CHOSEN FOR THE BID HOWEVER IT MEETS CODE
 AND MINIMUM DESIGN CRITERIA. THEY OFTEN ARE REVISED AT
 A LATER DATE WHICH IS ONLY A SUBMITTAL TO CHANGE THE
 PRODUCT.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-05 Cont ID  
Sent By dpalmer Date 2009-01-05 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2009-01-05 Time 13:55 Sent To  
Notes
2009-01-05 13:55:32** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
 1) NOTE: PLANS STILL ONLY SUBMITTED FOR PLAN REVIEW AND
 PERMIT APPLICATION HAS YET TO BE MADE. PLEASE KEEP IN
 MIND THE NEW FLORIDA BUILDING CODE IS SET TO GO INTO
 EFFECT ON MARCH 1ST, 2009.
 VERIFICATION OF SEVERAL ITEMS INCLUDING LICENSING WILL
 BE DONE ONCE PERMIT APPLICATION IS MADE.
 *** PLEASE BE SURE ALL DOCUMENTATION CONTAINS THE
 CORRECT ADDRESS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH
 RESPECT TO LIGHTING CONTROLS. ROOMS/AREAS 114 AND 115
 SHOW SWITCHES HOWEVER THESE ARE NOT THE SAME SYMBOLS AS
 USED IN THE OTHER ROOMS. THERE IS A NOTE #2 WHICH LENDS
 TO POSSIBLE USE OF A SINGLE OCCUPANCY SENSOR TYPE
 DEVICE HOWEVER THIS IS NOT CLEAR AT THIS TIME.
 PLEASE SHOW THE SAME SYMBOL AS USED ON OTHER LOCATIONS.
 13-415.1.ABC.1.1,.1.2 AND .1.3.
  
 3) NOTE: THE PREVIOUS SUBMITTED WERE NOT SUBMITTED WITH
 THE REQUIRED ENERGY CALCULATIONS PER FBC 13-101,
 13-400, 13-415.2 ETC
 THE SPECIFIC SECTIONS WERE GIVEN HOWEVER THESE WILL BE
 NOTED ONCE MORE. PLEASE SEE 13-400.3.A FOR VERSION
 WHICH WAS ADOPTED ON DECEMBER 8TH, 2006. THE CURRENT
 FLA COM VERSION AS NOTED IN THIS SECTION TO BE USED AT
 A MINIMUM IS VERSION 2.5. THE SUBMITTED CALCULATIONS
 ARE VERSION 2.11 WHICH IS NO LONGER AN ADOPTED VERSION
 IN THE STATE OF FLORIDA.
 PLEASE BE SURE ALL ITEMS ON PLANS COORDINATES WITH THE
 SUBMITTED INPUT DATA REPORT. THIS INCLUDES OTHER TRADES
 AS WELL.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3 FOR LIGHTING.
 SEE THE EXTERIOR LIGHTING ON THE IDR ONLY INDICATES 4
 FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS SHOW A
 CONSIDERABLE AMOUNT OF MORE FIXTURES THAN THE FOUR
 NOTED.
 PLEASE SEE 13-401- 13-412 FOR OTHERS.
 ITEMS SUCH AS FLOORS WHICH ARE ALL SHOWN AS
 CARPET/RUBBER PADDING IS NOT CORRECT AS THERE ARE
 SEVERAL AREAS WHICH ARE NOT THIS FINISH ARE SOME WHICH
 ARE NOT PERMITTED TO CONTAIN THIS TYPE OF FINISH. (ELEC
 ROOM, MECH ROOM ETC).
 SEE COMMENTS FROM OTHER TRADES.
  
 ** PLEASE SEE THE COVER SHEET FOR THE PLANS INDICATES
 THE ADDRESS AS 7501 N JOG RD ALTHOUGH THE APPLIED
 LOCATION IS 6880. PLEASE COORDINATE ALL PLANS AND
 SUPPORTING DOCUMENTATION.
  
 4) NOTE: ON THE PREVIOUS REVIEW THE PHOTO-METRIC LEVELS
 FOR THE LIFE SAFETY EGRESS WERE REQUESTED. THE RESPONSE
 MENTIONS TO SEE ENCLOSED PLANS. THIS INFORMATION NEEDS
 TO BE PART OF THE PLANS, WITH TITLE BLOCKS ALONG WITH
 BEING SIGNED, DATED AND SEALED BY THE RESPONSIBLE
 DESIGNER.
 NFPA-101 7.8, 7.9.
 FS471.003, 471.025, FAC 61G15-23.002
 FBC 106.1.1, 106.5. ADDITIONAL INFORMATION, CLARITY ON
 RECORD PLANS.
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS ON THE GENERATOR, ATS ETC. THE ATS IS AN
 INTEGRAL PART OF THE ELECTRICAL RISER AND COULD NOT BE
 UNDER A SEPARATE PERMIT.
 110.3,90.7
  
 6) NOTE: NOW THAT THE LOADS FOR MDP-OP ARE SHOWN PLEASE
 PROVIDE A GENERATOR WHICH WILL SERVE THE CAPACITY OR
 PLEASE PROVIDE ALL LOAD SHEDDING WHICH WOULD BE NEEDED
 TO DECREASE LOAD ON SYSTEM. AS SHOWN AT THIS TIME THE
 GENERATOR WILL FEED ALL LOADS.
 220, 215.3, 702.5 ETC
  
 7) NOTE: PLEASE PROVIDE WIND LOADS FOR LIGHT POLES PER
 FBC TABLE 1609. RESPONSE MENTIONS THE INFORMATION WAS
 ADDED TO SHEET E-10. HOWEVER THIS INFORMATION AS SHOWN
 IS NOT CORRECT AND HAS BEEN CONFIRMED WITH THE BUILDING
 REVIEWER.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL
 ITEMS. PLEASE SEE SHEET E-7, ROLL UP DOOR FOR EXAMPLE:
 408.4.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD
 CALCULATIONS. PLEASE SUBMIT THE LOAD CALCULATIONS
 SHOWING HOW THE LOADS WERE DERIVED. THERE ARE NO NOTES
 ON WHETHER OR NOT THE CONTINUOUS LOADS SUCH AS THE
 LIGHTING AND WATER HEATER WAS ALREADY FIGURED AT 125%
 OR IF THEY STILL NEED TO BE.
 THE TYPICAL WATER HEATER SHOWN ON PLANS INDICATE 4500
 VA HOWEVER NO INDICATE OF THE 125% COULD BE LOCATED.
 220.12,220.14,220.42,220.44, ETC CONTINUOUS LOADS PER
 215.3,230.42. SEE 422.13 FOR STORAGE TYPE WATER
 HEATERS. THIS WAS A CHANGE IN THE 2005 NEC.
  
 10) NOTE: PLEASE CLARIFY THE FOUNDATION STEEL BEING
 PART OF THE GROUNDING ELECTRICAL SYSTEMS AT BOTH
 STRUCTURES. THE PLANS NOTES *BUILDING STEEL* HOWEVER IT
 IS NOT CLEAR IF THIS IS FOR *FOUNDATION STEEL*.
 250.50
 THIS COMMENT WAS NOT MADE ON THE PREVIOUS REVIEW.
  
 ** AS NOTED ON PREVIOUS REVIEW AS THERE IS SOME
 INFORMATION NOT YET SUBMITTED A COMPLETE REVIEW FOR
 CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-22 Cont ID  
Sent By dpalmer Date 2008-10-22 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2008-10-22 Time 09:06 Sent To  
Notes
2008-10-22 09:06:59 
 ** DENIED REVIEW**
  
  
  
  
 1) NOTE: PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW
 AND NOT FOR PERMIT. EVEN ONCE ALL COMMENTS HAVE BEEN
 ADDRESSED AND PERMIT APPLICATION BY A LICENSED
 CONTRACTOR HAS NOT BEEN MADE THE REVIEW WOULD STILL
 REMAIN IN A FAILED STATUS. THERE ARE SEVERAL ITEMS FOR
 LICENSING WHICH IS VERIFIED AT A LATER DATE WHEN
 APPLICATION HAS BEEN MADE.
  
 2) NOTE: THE PROJECT INFORMATION HAS BEEN SENT TO
 ADDRESSING FOR REVIEW. THE PLANS DO NOT INDICATE ANY
 ADDRESS ON THE TITLE BLOCKS AND TWO SEPARATE BUILDINGS
 ARE BEING CONSTRUCTED. KEEP IN MIND IF THESE TWO
 SEPARATE STRUCTURES ARE SUBMITTED ON THE SAME PLANS
 UNDER ONE PERMIT A CERTIFICATE OF OCCUPANCY,
 INSPECTIONS FINALS ETC WOULD BE FOR BOTH. IT WOULD NOT
 BE POSSIBLE TO CO ONE WITH OUT THE OTHER. IF TWO PERMIT
 APPLICATIONS ARE MADE, ONE FOR EACH BUILDING THIS WOULD
 ALLOW EACH TO CONTAIN A CO ETC.
 PLEASE BE SURE ONCE THE ADDRESS FOR EACH BUILDING IS
 ASSIGNED THE TITLE BLOCKS REFLECT EACH.
 61G15-23.002, 61G1-16.004
 FBC 106.1, 106.5
  
 3) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AND LIGHTING
 PERFORMANCE CALCULATIONS IN COMPLIANCE WITH THE FBC
 13-415.2.ABC.1.1, .1.2 AND .1.3. PLEASE SEE 13-400,
 13-415 ETC
 AS NO CALCULATIONS OR PERFORMANCE CALCULATIONS WERE
 SUBMITTED NO REVIEW OF THESE ITEMS COULD BE DONE.
  
 4) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON THE ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
  
 5) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SYSTEMS ARE
 REQUIRED TO BE UNDER A SEPARATE PERMIT. IF THE PLANS
 SHOW ALL OF THE EQUIPMENT THEN THEY MAY BE REFERENCED
 FOR A TURN AROUND PERMIT ONCE THE BASE BUILDING
 PERMIT(S) ARE ISSUED.
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, ATS AND OTHER EQUIPMENT SUCH
 AS THE FUEL TANK. THE FUEL TANKS WILL BE UNDER THE
 REVIEW OF OTHER TRADES.
 110.3, 90.7
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE INFORMATION ON PLANS THAT THE
 MOTORIZED GATES HAVE A FAIL SAFE OR BACK UP FOR
 OPERATION IN THE EVENT OF POWER FAILURE. SEE FIRE
 MARSHAL REVIEW. THIS IS NOTED AS THIS WILL AFFECT THE
 ELECTRICAL PLANS.
  
 8) NOTE: PLEASE PROVIDE A GROUNDING ELECTRODE
 RISER/ATTACHMENT LOCATION FOR ALL TRANSFORMERS.
 250.66,250.50.250.58 ETC
  
 9) NOTE: PLEASE SEE THE LIGHTING CONTROLS TO MEET FBC
 13-415.1.1, .1.2 AND .1.3 ARE IN QUESTION FOR MORE
 INFORMATION. WHAT DOES THE SWITCH 1 DO? THE NOTE ON THE
 PLANS MENTIONS OPERATION HOWEVER DOES THIS DEVICE STILL
 CONTAIN AN AUTOMATED OPERATION TO TURN LIGHTING OFF
 ONCE AN OCCUPANT IS NO LONGER IN THE SPACE?
 PLEASE SEE THE BREAK ROOMS AND OTHER ROOMS SUCH AS
 TRAINING ROOMS MUST MEET 13-415.1.ABC.1.2. ( AREAS 114,
 115 ETC)
 IN LOCATIONS SUCH AS MULIT0GNAG BATH ROOMS PLEASE
 INDICATE THE AUTOMATED DEVICES FOR LIGHTING CONTROLS
 WITH DUAL TECHNOLOGY. IF DEVICE WAS MOTION ONLY THIS
 WOULD AFFECT OTHER AREAS IN THE SAME BATHROOMS WHICH
 MAY BE OCCUPIED YET NO MOTION COULD BE DETECTED.
  
 10) NOTE: PLEASE INDICATE THE CIRCUITING FOR THE
 EMERGENCY BATTERY BACK UP IN ROOM 117 (LADIES
 BATHROOM). 700.12F
  
 11) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR EGRESS PATHS
 UNDER EMERGENCY BACK UP CONDITIONS. THE LIGHTING LEVELS
 UNDER NORMAL ARE NOT NEEDED AS THEY ARE CLEARLY
 SUFFICIENT HOWEVER THE LIGHTING LEVELS UNDER EMERGENCY
 IN SOME AREAS ARE IN QUESTION. PLEASE SEE NFPA-101
 7.9.1 WHICH PERMITS 1FT CANDLE UNDER EMERGENCY
 CONDITIONS.
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARIFICATION.
  
 12) NOTE: PLEASE VERIFY ALL DISCONNECTING MEANS AT THE
 DETACHED ROOF STRUCTURE PER 225.31-225.39.
 ( MAY BE A SNAP SWITCH)
 GROUNDING REQUIRED PER 250.32 ALREADY SHOWN.
  
 13) NOTE: PLEASE CLARIFY THE SERVER ROOM. IF THIS IS AN
 IT ROOM PLEASE BE SURE ALL ITEMS LISTED IN 645.2 ARE
 MET IN ORDER FOR WIRING METHODS PERMITTED IN 645 TO BE
 USED. IF THESE ITEMS ARE NOT MET THE WIRING METHODS
 WHICH ARE PERMITTED IN 645 ARE NOT PERMITTED TO BE USED
 AND THIS MAY AFFECT FUTURE EQUIPMENT INSTALLATION AND
 WIRING. PLEASE PLACE NOTE ON PLANS THAT WILL STATE:
 *THIS IS NOT AN IT ROOM AND WIRING METHODS OF NEC 645
 ARE NOT PERMITTED*. OR WORDS TO THAT AFFECT.
  
 14) NOTE: PLEASE BE SURE LIGHT POLES ARE STATING THE
 WIND LOAD RATINGS AS NOTED IN THE FBC. THE LIGHT POLE
 CALCULATIONS WILL BE UNDER BUILDING/STRUCTURAL REVIEW.
 THIS IS NOTED FOR INFORMATION ONLY.
  
 15) NOTE: PLEASE COMPLETE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. THIS MAY BE ALPHA OR NUMERIC.
 MOST AREAS SHOW BOTH AT THIS TIME.
 PLEASE BE SURE THE PANEL SCHEDULES ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. FOR EXAMPLE SIMPLY
 STATING *RECEPTACLES* OR * LIGHTING* IS NOT ACCEPTABLE.
 PLEASE SEE THE CHANGE IN THE 2005 NEC (HANDBOOK) WHICH
 EXPLAINS THE CHANGE IN 408.4 FOR MORE SPECIFIC
 DESIGNATIONS. THIS IS NOT ONLY FOR ON-SITE HOWEVER ALSO
 FOR RECORD PLANS.
 THIS WOULD INCLUDE THE CIRCUIT FOR ROLL UP DOOR AT
 MAINT BUILDING.
 FBC 106.1.1, 106.5
  
 16) NOTE: PLEASE SEE THE PLANS SHOW A CIRCUIT TO
 GENERATOR ENCLOSURE HOWEVER BUT NOT FOR A PARTICULAR
 PURPOSE. THE PLANS ALSO SHOW AT THE GENERATOR A
 DESIGNATION TO THE PANEL HOWEVER NOT THE CIRCUIT. IF
 THIS CIRCUIT IS FOR A BATTERY CHARGER, BLOCK HEATER ETC
 PLEASE CHECK WITH THE MANUFACTURE OF ANY PARTICULAR
 GENERATOR AS THEY ARE USUALLY DEDICATED CIRCUITS. BLOCK
 HEATERS CAN BE AS HIGH AS 1500WATTS WHICH WOULD NOT
 PERMIT THE BATTERY CHARGER TO BE ON THE SAME CIRCUIT.
 408.4, 220 ETC
 FBC 106.1.2, 106.1.1
  
 17) NOTE: PLEASE SEE ELECTRICAL ROOM 109 AS THIS STATES
 A LINE NOTE FROM THE TRANSFORMER TO *LP-OP2* HOWEVER
 BASED ON RISER AND DESIGNATION ALREADY USED FOR
 TRANSFORMER IN ROOM 113 THIS IS CONFUSING.
 PLEASE CLARIFY HOW BOTH HAVE THE SAME DESIGNATION?
 FBC 106.1.1,
 NEC 230,450,215 ETC GENERAL COORDINATION
  
 18) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR THE
 MDP-OP. AS NO LOADS ARE SHOWN IT IS NOT POSSIBLE TO
 DETERMINE CODE COMPLIANCE FOR ALL EQUIPMENT INCLUDING
 THE LOAD ON THE GENERATOR AND WHETHER OR NOT THE
 GENERATOR IS OF SUFFICIENT SIZE.
 220, 702.5 ETC
 FBC 106.1.1, 106.1.2
 PLEASE BE SURE TO INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125%.
 215.3,230.42
  
 19) NOTE: PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-03-02 Cont ID  
Sent By mgonzale Date 2009-03-02 Time   Rev Time 1.00
Received By mgonzale Date 2009-03-02 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-12-15 Time 09:13 Rev Time 1.00
Received By mgonzale Date 2008-11-06 Time 16:13 Sent To ENG
Notes
2008-11-06 16:42:22APPROVED WITH PROVISO:
  
 EOR MUST SUPPLY NPDES PLAN AT TIME OF PRECONSTRUCTION
 WITH CITY'S ENGINEERING DEPT.
  
 ALL UTILITIES HAVE BEEN COORDINATED WITH THE CITY OF
 WPB.
  
 MANNY GONZALEZ
 (561) 494-1085
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-06-16 Cont ID  
Sent By mwennerg Date 2009-06-16 Time 10:14 Rev Time 0.00
Received By mwennerg Date 2009-06-16 Time 10:13 Sent To  
Notes
2009-06-16 10:14:50SENT TO L. MARTINEZ FOR PROCESSING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-04-09 Cont ID  
Sent By mawillia Date 2009-04-09 Time 17:29 Rev Time 0.00
Received By mawillia Date 2009-04-09 Time 16:22 Sent To  
Notes
2009-04-09 17:29:47*****UNSAT****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 07. AS PER WEST PALM BEACH CODE, THE ADDRESS NUMBERS ON
 THE BUILDING SHALL BE NO LESS THAN 6" IN HEIGHT AND NO
 LESS THAN 1" IN WIDTH PLAINLY VISBLE FROM THE ROADWAY
 TO APPROACHING VEHICLES.
  
 14. IN REFERENCE TO NFPA 241 BEING ADDED TO THE PLANS,
 PLEASE CONTACT THIS OFFICE IN THIS MATTER.
  
  
 (ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS
 HAVE BEEN SATISFIED; THE APPROPROPITE PLAN SHEETS ARE
 TO BE FIRE-STAMPED WHEN THE ABOVE ITEMS AS WELL AS
 OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED.)
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722; PLAN REVIEW OFFICE
 561-804-4724; FIRE PREVENTION BUREAU
 561-644-7326; BUSINESS CELLULAR

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-01-14 Cont ID  
Sent By mwennerg Date 2009-01-14 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2009-01-14 Time 11:11 Sent To  
Notes
2009-01-14 11:23:21***DENIED***
  
 MOST OF THE PREVIOUS COMMENTS HAVE BEEN ADDRESSED.
 PLEASE SEE THE FOLLOWING AND NOTE THAT THE PLANS WILL
 REMAIN IN FAILED STATUS UNTIL REVIEWED AND APPROVED FOR
 PERMIT.
  
 1) PLEASE ADD TO CODE ANALYSIS ON SHEET A-3. NFPA 1,
 2003 CHAPTER-18
  
 2) TYPICALLY DEAD END WATER LINES THAT ARE CONNECTED TO
 FIRE PROTECTION EQUIPMENT IS AN UNACCEPTABLE
 ARRANGEMENT, PARTICULARLY IF FUTURE EQUIPMENT IS
 PROPOSED. PLEASE PROVIDE FURTHER EXPLANATION.
  
 3) PLEASE PROVIDE VERIFICATION THAT EQUIPMENT
 ILLUSTRATED ON SHEET CD-5 IS A DOUBLE CHECK DETECTOR
 ASSEMBLY. THE RESPONSE SEEMS TO SUGGEST A DEVICE THAT
 IS TIED TO THE DOMESTIC WATER SUPPLY INDICATING A
 BACKFLOW DEVICE.
  
 5) OK PLEASE VERIFY THE ACTUAL DISTANCES ON THE
 DRAWINGS AS CODE ANALYSIS INDICATES THAT DISTANCES
 VARY.
  
 7) THE ADDRESS IS SHOWN ON PLANS. PLEASE INCLUDE
 INFORMATION SHOWING CODE COMPLIANCE PER THE CITY OF
 WEST PALM BEACH REQUIREMENTS FOR COMMERCIAL BUILDINGS.
  
 14) PLEASE ADD NOTE TO PLANS. NFPA 241
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-29 Cont ID  
Sent By mwennerg Date 2008-10-29 Time 14:04 Rev Time 0.00
Received By mwennerg Date 2008-10-29 Time 14:04 Sent To  
Notes
2008-10-29 14:22:49***DENIED***
  
 1) PROPERTY ACCESS AND WATER SUPPLY TO COMPLY WITH NFPA
 1, 2003, CHAPTER-18.
  
 2) FIRE LINE APPEARS TO DEAD END AT FIRE HYDRANT. ARE
 THERE ANY OTHER FIRE HYDRANTS ON THE PROPERTY?
  
 3) SHEET CD-5 ILLUSTRATES A DOUBLE CHECK DETECTOR
 ASSEMBLY. IN ADDITION TO ELECTRONIC SUPERVISION, DEVICE
 SHALL BE SECURED WITH CHAIN AND LOCK. SUBJECT BUILDINGS
 ARE NOT FIRE SPRINKLER PROTECTED. WHAT BUILDING IS
 PROTECTED BY DOUBLE CHECK DETECTOR ASSEMBLY?
  
 4) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 5) PLEASE INDICATE ACTUAL MAXIMUM TRAVEL DISTANCES ON
 DRAWINGS. (LIFE SAFETY PLAN)
  
 6) DOORS SHALL SWING IN DIRECTION OF TRAVEL WHERE
 SERVING AREAS WITH (50) OR MORE OCCUPANTS.
  
 7) ADDRESSES ARE REQUIRED ON BUILDINGS THAT SHALL BE
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND.
  
 8) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING IN TERMS OF CLASS A,B OR C. ADD NOTE
 TO ELEVATIONS
  
 9) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED TO BE
 MOUNTED AT LOCATIONS NOT TO EXCEED 75" TRAVEL DISTANCE
 REQUIREMENT. OK ON SHEET A-17.
  
 10) KNOX BOX ENTRY REQUIRED FOR BUILDINGS. CONTACT
 BUREAU OF FIRE PREVENTION AT (561) 804-4724 FOR
 ASSISTANCE.
  
 11) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE
 WITH UL 555 REQUIREMENTS PRIOR TO FINAL INSPECTION.
  
 12) MOTOR OPERATED GATES TO BE PROVIDED WITH FAIL SAFE
 MECHANISM IN THE EVENT OF POWER LOSS.
  
 13) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 14) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-08-09 Cont ID  
Sent By jgomez Date 2010-08-09 Time 10:13 Rev Time 0.00
Received By jgomez Date 2010-08-09 Time 10:12 Sent To  
Notes
2010-08-09 10:12:58SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-05-21 Cont ID  
Sent By dpalmer Date 2009-05-21 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2009-05-21 Time 13:28 Sent To  
Notes
2009-05-21 13:29:04C-42

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-02-26 Cont ID  
Sent By adarroug Date 2009-02-26 Time 16:10 Rev Time 0.00
Received By adarroug Date 2009-02-26 Time 16:10 Sent To  
Notes
2009-02-26 16:14:12TO "COMM" BD#5--PLANS ON RACK--3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-15 Cont ID  
Sent By adarroug Date 2008-12-15 Time 09:40 Rev Time 0.00
Received By adarroug Date 2008-12-15 Time 09:40 Sent To  
Notes
2008-12-15 09:40:20TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-12-15 Cont ID  
Sent By mgonzale Date 2008-11-06 Time 16:42 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 10:38 Sent To ENG
Notes
2008-09-25 10:38:28TO "COMM" BD#48

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-05-26 Cont ID  
Sent By rkussner Date 2009-05-26 Time 17:39 Rev Time 0.00
Received By rkussner Date 2009-05-26 Time 17:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-06-12 Cont ID  
Sent By rregueir Date 2009-06-12 Time 14:50 Rev Time 0.00
Received By rregueir Date 2009-06-12 Time 14:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 17:08 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 15:31 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 15:15 Sent To  
Notes
2009-01-24 15:30:58REVIEW #: 2ND ***PLAN CHECK ONLY***
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTINUITY:
  
 1. OK. SEPARATE PERMIT FOR GENERATOR REQUIRED. SUBMIT
 PLANS FOR THAT PERMIT WHICH HAVE BEEN REVIEWED AND
 APPROVED BY PBC DERM. FOR MORE INFORMATION PLEASE
 CONTACT PBC DERM AT: 561-233-2400 OR
 HTTP://WWW.PBCGOV.COM/ERM/
  
 2. *PREVIOUS COMMENT* PAGE H-1 REFERS TO FORM 400A FOR
 ENERGY CODE COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH
 THIS SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY
 CODE COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A
 COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE
 WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS
 SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF
 THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL
 COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS.
 *PARTIALLY ADDRESSED* FORM 400A VERSION 2.11 WAS
 SUBMITTED WITH COOLING LOAD CALCULATIONS. AN ACCURATELY
 COMPLETED FORM 400A-04R (GENERATED BY THE FLA/COM-2004
 COMPUTER PROGRAM, VERSION 2.5) DEMONSTRATING THAT CODE
 COMPLIANCE HAS BEEN ACHIEVED SHALL BE SUBMITTED TO THE
 BUILDING OFFICIAL FOR METHOD A COMPLIANCE IN ACCORDANCE
 WITH FBCB 13-400.3.A. METHOD A VERSION 2.11 HAS NOT
 BEEN IN EFFECT SINCE THE DECEMBER 8, 2006 REVISIONS TO
 THE FBC. REVIEW FOR COMPLIANCE WITH FBCB CHAPTER 13 IS
 NOT POSSIBLE AT THIS TIME.
  
 3. *PREVIOUS COMMENT* PAGE H-2: MULTIPLE DUCTS ON FLOOR
 PLAN DO NOT HAVE A SIZE DESIGNATION. EXAMPLES: OUTSIDE
 AIR DUCTS IN MECHANICAL ROOMS, RETURN TRUNK AND BRANCH
 LINES. PLEASE CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE
 MISSING SIZE INFORMATION. DUCTS SHALL BE DESIGNED AND
 INSTALLED TO PROVIDE THE REQUIRED DISTRIBUTION OF AIR
 IN ACCORDANCE WITH FBCM 603.1.
 *PARTIALLY ADDRESSED* SOME DUCTS ON PLANS ARE STILL
 MISSING SIZES, SUCH AS THE OA DUCTS IN MECHANICAL ROOM
 113 AND THE RETURN BRANCH IN THE KITCHEN. PLEASE
 PROVIDE ALL MISSING INFORMATION. ALSO, PLEASE SEE FBCM
 407.1 FOR REQUIREMENTS RELATED TO RETURN AIR INTAKES IN
 KITCHENS.
  
 4. OK
  
 5. OK
  
 6. OK
  
 7. *PREVIOUS COMMENT* PAGE HD-2: THERE IS NO DETAIL
 PROVIDED FOR INSTALLATION OF GRAVITY HOOD, ASSOCIATED
 ROOF CURB OR ROOF JACKS FOR WIND RESISTANCE. MECHANICAL
 EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO RESIST
 WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13.
 *PARTIALLY ADDRESSED* DETAIL ON HD-3 CALLS FOR EYEBOLT
 EMBEDDED 3 INCHES WITH EPOXY GROUT. HOW IS THIS
 POSSIBLE ON A METAL STANDING SEAM ROOF? THIS DETAIL
 APPEARS TO BE FOR A CONCRETE DECK, WHICH DOES NOT APPLY
 TO THIS PROJECT. PLEASE CORRECT FOR THE APPROPRIATE
 ROOF ASSEMBLY.
  
 8. OK
  
 NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO
 BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT
 APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS
 DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR
 COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-10-25 Cont ID  
Sent By rregueir Date 2008-10-25 Time 12:18 Rev Time 0.00
Received By rregueir Date 2008-10-25 Time 12:15 Sent To  
Notes
2008-10-25 12:18:21REVIEW #: 1ST ***PLAN CHECK ONLY***
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A-3 INDICATES TWO 1,000 GALLON DIESEL FUEL
 STORAGE TANKS, ONE FOR EACH BUILDING. PAGE E-2 SHOWS
 ONLY ONE GENERATOR WITH DIESEL STORAGE TANK. WHICH IS
 CORRECT? NO INFORMATION WAS PROVIDED REGARDING THE
 DIESEL GENERATOR OR FUEL STORAGE SYSTEM TO BE USED.
 PROVIDE SUBMITTAL DOCUMENTATION FOR EACH TO DEMONSTRATE
 COMPLIANCE WITH FBCM SECTION 915. ALSO, ABOVE GROUND
 FUEL STORAGE TANKS GREATER THAN 550 GALLONS SHALL BE
 SUBMITTED TO PALM BEACH COUNTY DERM FOR APPROVAL PRIOR
 TO PERMIT ISSUANCE. INCORPORATE DERM APPROVED PLANS
 INTO THESE PERMIT DOCUMENTS. FOR MORE INFORMATION
 PLEASE CONTACT PBC DERM AT: 561-233-2400 OR
 HTTP://WWW.PBCGOV.COM/ERM/
  
 2. PAGE H-1 REFERS TO FORM 400A FOR ENERGY CODE
 COMPLIANCE. NO SUCH FORM WAS PROVIDED WITH THIS
 SUBMISSION. WITHOUT SUCH FORM, AN OVERALL ENERGY CODE
 COMPLIANCE REVIEW CAN NOT BE PERFORMED. PROVIDE A
 COMMERCIAL ENERGY CODE COMPLIANCE FORM IN ACCORDANCE
 WITH FBCB 13-400.0. ALSO, COOLING LOAD CALCULATIONS
 SHALL BE APPENDED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBCM 13-407.1.ABC.1. AS A RESULT OF
 THIS INFORMATION NOT BEING PROVIDED, RELATED ADDITIONAL
 COMMENTS ARE LIKELY IN SUBSEQUENT REVIEWS.
  
 3. PAGE H-2: MULTIPLE DUCTS ON FLOOR PLAN DO NOT HAVE A
 SIZE DESIGNATION. EXAMPLES: OUTSIDE AIR DUCTS IN
 MECHANICAL ROOMS, RETURN TRUNK AND BRANCH LINES. PLEASE
 CHECK ALL DUCTS ON FLOOR PLAN AND PROVIDE MISSING SIZE
 INFORMATION. DUCTS SHALL BE DESIGNED AND INSTALLED TO
 PROVIDE THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE
 WITH FBCM 603.1.
  
 4. PAGE H-2: SEVERAL BRANCH DUCTS SHOW CONTROL DAMPERS
 ABOVE GYPSUM BOARD CEILINGS. SHOW HOW THESE DAMPERS ARE
 TO BE ACCESSED FOR TESTING AND BALANCING IN ACCORDANCE
 WITH FBCB 13-410.1.ABC.4.
  
 5. PAGE H-2: THE OUTSIDE AIR INTAKE LOUVER FOR AHU-3
 AND AHU-4 IS SHOWN TO BE APPROXIMATELY 5 FEET FROM THE
 PARKING LOT FOR THE OPERATIONS BUILDING. MECHANICAL
 OUTSIDE AIR INTAKE OPENINGS SHALL BE LOCATED A MINIMUM
 OF 10 FEET FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS IN ACCORDANCE
 WITH FBCM 401.5.1.
  
 6. PAGE H-2: THE RETURN DUCT PENETRATING A RATED WALL
 ASSEMBLY AT BREAK ROOM 106 SHOW NO FIRE DAMPER AT THE
 DUCT PENETRATION BUT SHOWS THE FIRE DAMPER AT ANOTHER
 LOCATION IN THE WALL, AWAY FROM THE DUCT. PLEASE SHOW
 THE DUCT PENETRATION TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 AND SHOW THE CORRECT LOCATION OF THE DAMPER
 IN ACCORDANCE WITH FBCM 607.8.
  
 7. PAGE HD-2: THERE IS NO DETAIL PROVIDED FOR
 INSTALLATION OF GRAVITY HOOD, ASSOCIATED ROOF CURB OR
 ROOF JACKS FOR WIND RESISTANCE. MECHANICAL EQUIPMENT
 SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 8. PAGE HD-2: NO INFORMATION SHOWN ON PLANS OR IN
 DETAIL REGARDING AUXILIARY OR SECONDARY DRAIN
 PROTECTION FOR CONDENSATE DRAIN SYSTEMS. PROVIDE
 AUXILIARY OR SECONDARY DRAIN PROTECTION IN ACCORDANCE
 WITH FBCM 307.2.3.
  
 NOTE: THE 2007 FLORIDA BUILDING CODE IS SCHEDULED TO
 BECOME EFFECTIVE ON MARCH 1, 2009. IF A PERMIT
 APPLICATION FOR THIS PROJECT IS SUBMITTED AFTER THIS
 DATE, THESE PLANS WILL NEED TO BE REVIEWED FOR
 COMPLIANCE WITH THE NEW CODE PRIOR TO PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2009-06-01 Cont ID  
Sent By kstevens Date 2009-06-01 Time 15:29 Rev Time 0.00
Received By kstevens Date 2009-06-01 Time 15:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-04-14 Cont ID  
Sent By kstevens Date 2009-04-14 Time 15:53 Rev Time 0.00
Received By kstevens Date 2009-04-14 Time 15:53 Sent To  
Notes
2009-04-14 15:54:49 
  
 PASSED/PROVISO:
  
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RNAGE" NOT IN THE CEILING.
 PDI-WH 201.

Review Stop P PLUMBING
Rev No 4 Status F Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 16:36 Rev Time 0.00
Received By kstevens Date 2009-04-13 Time 16:36 Sent To  
Notes
2009-04-13 16:44:42DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 ********FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. OK
  
 ___FOR SINKS:
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH (PROVISO)
 D. OK
 E. OK
 F. OK
 G. OK
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT
 ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD),
 HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW
 THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN
 THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF
 THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE
 INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2
 SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH
 DUE REGARD TO PRESERVATION OF THE STRENGHT OF
 STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS
 AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE
 CLARIFY.
 ********NO WRITTEN RESPONSE. COMMENT TO BE ADDRESSED
 WITH A SIGNED, SEALED COMMENT RESPONSE TO THE ABOVE
 COMMENT. THE FINISH SCHEDULE FOR THE MAINTENANCE
 BUILDING INDICATE P-1 FININSH. PLEASE INDICATE WHAT P-1
 FINISH IS AND WHERE IN THE PLANS THIS CAN BE FOUND. THE
 ARCHITECT OR ENGINEER OF RECORD WILL BE REQUIRED TO
 TAKE RESPONSIBILITY FOR THE CODE SECTION 301.2.
  
 7. OK
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE
 PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS
 NEAR THE FIXTURES, NOT IN THE CEILING.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED.
 ********NO RESPONSE, COMMENT NOT ADDRESSED.
  
 9. OK
 10. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-03-26 Cont ID  
Sent By kstevens Date 2009-03-26 Time 08:36 Rev Time 0.00
Received By kstevens Date 2009-03-25 Time 17:12 Sent To  
Notes
2009-03-26 08:47:38DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. OK
  
 ___FOR SINKS:
 A. OK
 B. OK
 C. 11-4.24.4 SINK DEPTH (PROVISO)
 D. OK
 E. OK
 F. OK
 G. OK
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE SECTION OF THE COMMENT
 ABOUT WHAT WILL HAPPEN TO THE WATER, (AND NOW THE MUD),
 HAS NOT BEEN ADDRESSED. THERE IS NO INDICATION OF HOW
 THE WALLS WILL BE PROTECTED FROM THE STANDING WATER IN
 THE MAINTENANCE BUILDING, NO INDICATION OF SLOPING OF
 THE FLOORS AWAY FROM THE WALLS, NO WALL FINISH SCHEDULE
 INDICATING WATER PROOFING OF WALLS ETC. SECTION 301.2
 SYSTEM INSTALLATION. PLUMBING SHALL BE INSTALLED WITH
 DUE REGARD TO PRESERVATION OF THE STRENGHT OF
 STRUCTURAL MEMBERS AND PREVENTION OF DAMAGE TO WALLS
 AND OTHER SURFACES THROUGH FIXTURE USAGE. PLEASE
 CLARIFY.
  
 7. OK
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE
 PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS
 NEAR THE FIXTURES, NOT IN THE CEILING.
 ******RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS
 ARE STILL SHOWN IN THE CEILING AND NOT DOWN NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" AS REQUIRED.
  
 9. OK
 10. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-27 Cont ID  
Sent By kstevens Date 2009-01-27 Time 10:19 Rev Time 0.00
Received By kstevens Date 2009-01-27 Time 10:19 Sent To  
Notes
2009-01-27 10:44:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR DRINKING FOUNTAIN:
 A. OK
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOW IN TOILET ROOMS 120 & 121.
 B. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT NO INDICATION OF THE
 REQUIREMENT FOR CONTROLS TO THE WIDE SIDE OF THE
 TOILET.
 C. W/C TO BE 18" OFF THE WALL TO THE C/L OF THE
 FIXTURE. FIGURES 28 AND 30E.
 ****RESPONSE NOTED, BUT THE W/C'S IN TOILET ROOMS 120 &
 121 NOT ADDRESSED.
  
 ___FOR URINALS:
 A. OK
 B. OK
  
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOW IN TOILET ROOMS 120 & 121.
 B. 11-4.19 4 EXPOSED PIPES & SURFACES
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 C. OK
 D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE.
 FIG. 32.
 ****RESPONSE NOTED, BUT THE LAV'S IN TOILET ROOMS 120 &
 121 NOT ADDRESSED.
  
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 ****NO RESPONSE, COMMENT NOT ADDRESSED
 B. 11-4.21.3 SEAT
 ****HEIGHT NOT INDICATED.
 C. 11-4.21.4 GRAB BARS
 ****NOT SHOWN AS REQUIRED IN FIGURE 37. ALSO SHOW THE
 HEIGHT.
 D. 11-4.21.5 CONTROLS
 ****THE LOCATION OF THE CONTROLS NOT SHOWN.
 E. 11-4.21.6 SHOWER UNIT
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 F. 11-4.21.7 CURBS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 ___FOR TOILET ROOMS:
 A. 11-4.22.2 DOOR SWING
 ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS
 120 & 121.
 B. 11-4.22.3 TURNING AREA
 ****NO RESPONSE, COMMENT NOT ADDRESSED FOR TOILET ROOMS
 120 & 121.
  
 ___FOR BATHROOMS:
 A. OK
 B. OK
  
  
 ********** NOTE: PER SECTION 11-4.1.3(11) IF TOILET
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE
 TOILET ROOM SHALL COMPLY WITH SECTION 11-4.22. COMMENT
 RESPONSE "IT SHOULD BE NOTED THAT TOILET ROOMS 120 &
 121 ARE NOT INTENDED TO ACCOMMODATE THE PHYSICALLY
 DISABLED" IS NOT ACCEPTABLE. PLEASE SHOW COMPLIANCE.
  
 ___FOR SINKS:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA
 ****NO RESPONSE TO A THRU G AND COMMENTS NOT ADDRESSED.
 THIS IS FOR THE KITCHEN/BREAK ROOM. SUBMIT AN ELEVATION
 DETAIL SHOWING ALL INFORMATION REQUIRED.
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 7. OK
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. MOST
 WATER HAMMER ARRESTORS DO NOT REQUIRE ACCESS AND THE
 PDI-WH 201 GUIDLINES SHOW THE WATER HAMMER ARRESTORS
 NEAR THE FIXTURES, NOT IN THE CEILING.
  
 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION
 TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT
 SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART
 INDICATING THE MODEL AND CORRECT SIZING OF THE
 EXPANSION TANK. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT THE ATTACHED MANUFACTURER'S
 SIZING GUIDELINES WERE NOT FOUND. PLEASE INDICATE WHERE
 THE GUIDELINES WERE ATTACHED AND CAN BE LOCATED.
  
 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR SINK OR HUB DRAIN IS REQUIRED
 FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES.
 SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE
 INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER
 HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT
 A TRIPPING HAZARD.
 ****RESPONSE NOTED, BUT THE FLOOR DRAIN IS STILL NOT AN
 APPROVED INDIRECT WASTE RECEPTOR. COMMENT NOT COMPLETLY
 ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By kstevens Date 2008-10-03 Time 11:12 Rev Time 0.00
Received By kstevens Date 2008-10-02 Time 15:57 Sent To  
Notes
2008-10-03 14:03:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT CD-6 IS NOT SIGNED, SEALED & DATED AS REQUIRED
 IN SECTION 106.1, THE FLORIDA ADMINISTRATIVE CODE &
 FLORIDA STATUTES.
  
 2. SHT A-1 BARRIER-FREE FIXTURE MOUNTING HEIGHT SHOWS
 THE GRAB BAR FOR THE W/C ON THE SIDEWALL TO BE 40".
 MINIMUM LENGTH IS 42" PER FIG 29 & SECTION 11-4.16.4.
  
 3. SHT A-3 BUILDING CODE ANALYSIS FOR OPERATIONS &
 MAINTENANCE BLDGS SHALL INCLUDE THE 2005, 2006 & 2007
 REVISIONS/AMENDMENTS. PLEASE INDICATE ON PLANS. SECTION
 106.1.1.
  
 4. SHT A-3 MAINTENANCE BUILDING FIXTURE REQUIREMENTS
 PER TABLE 403.1 ARE NOT INDICATED. IF USING THE
 EXCEPTION TO SECTION 403.4, THEN THIS MUST BE STATED ON
 THE PLANS AS WELL AS THE DISTANCE FROM THE MAINTENANCE
 BUILDING TO THE OPERATIONS BUILDING FACILITIES. SECTION
 106.1.1.
  
 5. SUBMIT DETAILS FOR THE ACCESSIBLE FIXTURES SHOWING
 COMPLIANCE WITH THE FOLLOWING:
  
 ___FOR DRINKING FOUNTAIN:
 A. 11-4.15.5 CLEAR FLOOR SPACE
  
 ___FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 C. W/C TO BE 18" OFF THE WALL TO C/L OF FIXTURE.
 FIGURES 28 & 30E
  
 ___FOR URINALS:
 A. 11-4.18.3 CLEAR FLOOR SPACE
 B. 11-4.18.4 FLUSH CONTROLS
  
 ___FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19 4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. LAVS TO BE A MINIMUM 15" OFF WALL TO C/L OF FIXTURE.
 FIG. 32.
  
 ___FOR SHOWERS:
 A. 11-4.21.2 SIZE & CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
  
 ___FOR TOILET ROOMS:
 A. 11-4.22.2 DOOR SWING
 B. 11-4.22.3 TURNING AREA
  
 ___FOR BATHROOMS:
 A. 11-4.23.2 DOOR SWING
 B. 11-4.23.3 TURNING AREA
  
 ___FOR SINKS:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE. FORWARD APPROACH
 REQUIRED. CABINET DOORS NOT APPROVED.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 G, 11-4.2.3 AN UNOBSTRUCTED TURNING AREA
  
 6. SHT P-3 MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE WHAT THE HOSE REELS WILL BE WASHING OFF. WHAT
 WILL HAPPEN TO THE WATER USED TO WASH OFF WHATEVER IS
 BEING WASHED OFF? WILL THERE BE ANY CHANCE OF GREASE OR
 OIL WASHED OFF? PLEASE CLARIFY. SECTIONS 106.1.2 &
 301.2. MORE COMMENTS MAY FOLLOW DEPENDING TO THE
 COMMENT RESPONSES TO THESE QUESTIONS.
  
 7. SHT P-4 SANITARY RISER DIAGRAM. THE VENT FOR THE
 CLEANOUTS AT THE END OF EACH GANG BATH IS NOT APPROVED.
 THESE ARE HORIZONTAL DRY VENTS. SECTION 905.3. (VENTS
 ARE NOT REQUIRED FOR CLEANOUTS AND CAN BE DELETED).
  
 8. SHT P-4 WATER RISER DIAGRAM. WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE REFRIGERATOR ICE
 MAKER LINES. SECTION 604.9. -- A SHUT OFF VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WALL HYDRANT NEAR
 OFFICE ROOM 102. SECTION 606.2(2).
  
 9. SHT PD-1 EWH-1 WATER HEATER DETAIL STATES "EXPANSION
 TANK SEE SPECIFICATIONS". SPECIFICATIONS WERE NOT
 SUBMITTED. PLEASE SUBMIT CALCULATIONS OR MANUF. CHART
 INDICATING THE MODEL AND CORRECT SIZING OF THE
 EXPANSION TANK. SECTION 607.3.2.
  
 10. SHT PD-1 A FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. A FLOOR DRAIN OR HUB DRAIN IS REQUIRED
 FOR THE P&T RELIEF VALVE AND EMERGENCY PAN DRAIN LINES.
 SECTIONS 504.6.1, 504.7.2, 802.3 & 802.3.2. THE
 INDIRECT WASTE RECEPTOR SHALL BE LOCATED NEAR THE WATER
 HEATER SO THE RELIEF AND PAN DRAIN LINES DO NOT PRESENT
 A TRIPPING HAZARD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-05-26 Cont ID  
Sent By eschneid Date 2009-05-26 Time 17:24 Rev Time 0.50
Received By eschneid Date 2009-05-26 Time 17:23 Sent To  
Notes
2009-05-26 17:25:13PASSED
  
 SIGNAGE AND ANY NEW FENCING REQUIRE SEPARATE PERMITS.

Review Stop Z ZONING
Rev No 3 Status F Date 2009-04-20 Cont ID  
Sent By eschneid Date 2009-04-20 Time 15:55 Rev Time 0.25
Received By eschneid Date 2009-04-20 Time 15:55 Sent To  
Notes
2009-04-20 16:01:36FAILED - REVIEW COMPLETED ON 3/12.
  
 THE FOLLOWING CONDITIONS FROM THE 3/12/09 SITE PLAN
 APPROVAL LETTER HAVE NOT BEEN ADDRESSED:
  
 A. THE BICYCLE RACK SHOWN ON ALL PLANS SHALL MATCH THE
 DETAIL SHOWN ON SHEET CD-2, INCLUDING ALL DIMENSIONS.
 B. THE WHEEL STOP DETAIL ON SHEET CD-2 SHALL CONFORM TO
 THE CITY OF WEST PALM BEACH STANDARD WHEEL STOP SHOWN
 ON FIGURE XIV-2 OF CHAPTER 94 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
 C. WHEEL STOPS SHALL BE PROVIDED AT ALL PARKING SPACES
 SINCE THE PARKING SPACES DO NOT MEET THE OVERHANG
 REQUIREMENTS SHOWN ON FIGURE XIV-2 OF CHAPTER 94 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-12-18 Cont ID  
Sent By eschneid Date 2008-12-18 Time 15:54 Rev Time 0.00
Received By eschneid Date 2008-12-18 Time 15:54 Sent To  
Notes
2008-12-18 16:01:12FAILED
  
 ALL REPEAT COMMENTS.
  
 1) THE CITY STAFF COMMENTS PROVIDED AS PART OF THE
 FORMAL SITE PLAN HAVE NOT BEEN SUFFICIENTLY ADDRESSED
 AND THEREFORE THE FORMAL SITE PLAN IS NOT APPROVED.
  
 2) THE PLANS SUBMITTED WITH THIS PLAN REVIEW ARE THE
 SAME AS THE PLANS THAT WERE INSUFFICIENT DURING THE
 FORMAL SITE PLAN REVIEW.
  
 3) ZONING WILL NOT REVIEW PLANS SUBMITTED TO THE
 CONSTRUCTION SERVICES DEPARTMENT UNTIL THE FORMAL SITE
 PLAN HAS BEEN APPROVED. NOTE THE PLANS REVIEWED AS PART
 OF THE BUILDING PERMIT APPLICATION SHALL BE THE SAME AS
 THOSE APPROVED DURING THE FORMAL SITE PLAN PROCESS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By eschneid Date 2008-10-01 Time 08:44 Sent To  
Notes
2008-10-01 08:46:53FAILED
  
 THIS PROJECT IS REQUIRED TO HAVE APPROVAL OF A FORMAL
 SITE PLAN REVIEW BY THE PLANNING AND ZONING DEPARTMENT
 PRIOR TO THE SUBMITTAL FOR BUILDING PERMIT. CODE
 COMPLIANCE WILL BE REVIEWED AT THE TIME OF FORMAL SITE
 PLAN APPLICATION.
  
 CONTACT KELLY FREEMAN @ (561) 822-1435 FOR APPLICATION
 PROCEEDURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved