Plan Review Details - Permit 08090591
Plan Review Stops For Permit 08090591
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-20 Cont ID  
Sent By mjacobs Date 2008-10-20 Time 14:56 Rev Time 0.00
Received By mjacobs Date 2008-10-20 Time 14:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By mjacobs Date 2008-09-30 Time 10:34 Rev Time 0.00
Received By mjacobs Date 2008-09-30 Time 10:34 Sent To  
Notes
2008-09-30 10:34:54BUILDING PLAN REVIEW
 PERMIT: 08090591
 ADD: 250 S. AUSTRALIAN AVE. #104
 CONT: FISHER CONTRACTING
 TEL: (561)691-4716
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 9-30-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) THE OCCUPANT LOAD CALCULATIONS ON SHEET CS HAS
 CONFLICTING INFORMATION REGARDING THE SQUARE FOOTAGE OF
 THE SPACE. THE PROJECT SCOPE SECTION INDICATES A 1434
 SQUARE FOOT AREA AND THE CALCULATIONS SECTIONS SHOWS
 THE TOTAL SQUARE FOOTAGE AS 8956 WITH THE STORAGE AREA
 BEING 8315 S.F/100. SEE FBC TABLE 1004.1.2. PLEASE
 CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-10-02 Cont ID  
Sent By btrobaug Date 2008-10-02 Time 16:55 Rev Time 0.00
Received By btrobaug Date 2008-10-02 Time 16:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 10:10 Rev Time 0.00
Received By mwennerg Date 2008-10-08 Time 10:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-01-30 Cont ID  
Sent By adarroug Date 2009-01-30 Time 08:48 Rev Time 0.00
Received By adarroug Date 2009-01-30 Time 08:48 Sent To M
Notes
2009-01-30 08:49:29TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-23 Cont ID  
Sent By adarroug Date 2009-01-23 Time 09:06 Rev Time 0.00
Received By adarroug Date 2009-01-23 Time 09:06 Sent To M
Notes
2009-01-23 09:06:50TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 16:42 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 16:42 Sent To  
Notes
2008-10-17 16:45:02TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-08 Cont ID  
Sent By mwennerg Date 2008-10-08 Time 10:12 Rev Time 0.00
Received By mwennerg Date 2008-09-24 Time 14:53 Sent To  
Notes
2008-09-24 14:58:11TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-02-18 Cont ID  
Sent By rregueir Date 2009-02-18 Time 14:06 Rev Time 0.00
Received By rregueir Date 2009-02-03 Time 19:16 Sent To PC
Notes
2009-02-18 14:07:50*****SEE REDLINED NOTE ON PLANS*****
 THROUGH-PENETRATION FIRESTOP SYSTEM OR FIRE DAMPER
 REQUIRED AT NEW 10" ROUND DUCT PENETRATION PER FBC-M
 607.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 13:57 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 13:53 Sent To PC
Notes
2009-01-24 13:57:15REVISED M2.1 DENIED:
  
 FLOOR PLAN SHOWS NEW AND EXISTING DUCTS PENETRATING
 FIRE RESISTANT RATED WALL WITHOUT PROTECTION. SHOW HOW
 THESE PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE
 WITH FBCM 607.5. ALSO, SHOW THE LOCATION OF EACH FIRE
 DAMPER ON THE PLANS IN ACCORDANCE WITH FBCM 607.8.
  
 NOTE: ARCHITECTURAL PLAN NOTE CALLSL FOR CONTRACTOR TO
 INSPECT AND REPAIR RATED WALLS TO MAINTAIN INTEGRITY OF
 SAME.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By tgordon Date 2008-10-24 Time 08:08 Rev Time 0.30
Received By tgordon Date 2008-10-24 Time 08:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By tgordon Date 2008-09-26 Time 09:03 Rev Time 0.40
Received By tgordon Date 2008-09-26 Time 09:03 Sent To  
Notes
2008-09-26 09:04:35PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) PLEASE ADD A DETAIL TO THE MECHANICAL PLANS FOR THE
 INSTALLATION OF THE FIRE DAMPERS. PER 2004 FBC/M THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-10-03 Cont ID  
Sent By mflis Date 2008-10-03 Time 11:44 Rev Time 0.00
Received By mflis Date 2008-10-03 Time 11:44 Sent To  
Notes
2008-10-03 11:45:07ZONING REVIEW: NOT REQUIRED
  
 * INTERIOR BUILD-OUT ONLY
  
 MATT FLIS - 822-1445