Plan Review Details - Permit 08090534
Plan Review Stops For Permit 08090534 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-11-17 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-11-17 |
Time |
10:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2008-10-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-27 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-10-27 |
Time |
14:10 |
Sent To |
|
|
Notes |
2008-10-27 14:23:55 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. SEE PAGE 14 OF THE PRODUCT APPROVAL. A 3" EDGE | | DISTANCE REQUIRES A FACTOR OF .83. | | | | 2. THE "SHUTTER CONNECTION MOUNTING TYPE" SHOULD | | CORRELATE WITH THE ANCHOR CHARTS ON THE PRODUCT | | APPROVAL. IT APPEARS THAT YOU ARE USING MOUNTING TYPES | | A, D, AND I. PLEASE NOTE THAT, IF THE ANCHOR SPACING | | WERE COMPLIANT (SEE COMMENT #1), THIS PERMIT WOULD NOT | | HAVE BEEN DENIED FOR THIS REASON ONLY. | | | | 3. ACCORDION SHUTTERS ARE, TO MY KNOWLEDGE, ALWAYS | | INSTALLED VERTICALLY (NOT HORIZONTALLY AS NOTED ON THE | | INSTALLATION SCHEDULE). PLEASE REVISE. ALSO PLEASE | | REVISE SPANS. FOR INSTANCE, OPENING 4 SPECIFIES A 209" | | SPAN. THIS EXCEEDS THE SPAN ALLOWED. FOR ACCORDION | | SHUTTERS, THE SPAN EQUALS BLADE LENGTH. | | | | THE INSTALLATION SCHEDULE SUBMITTED DID NOT ADDRESS THE | | COMMENTS; ALL INFORMATION IS THE SAME EXCEPT FOR THE | | SHUTTER SPAN. PLEASE HAVE THE QUALIFIER REVIEW THE | | COMMENT LIST AND THE INSTALLATION SCHEDULE BEFORE | | RESUBMITTING. IF YOU NEED ASSISTANCE, PLEASE HAVE THE | | QUALIFIER CONTACT ME. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-10-17 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-17 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-10-17 |
Time |
10:17 |
Sent To |
|
|
Notes |
2008-10-17 10:23:37 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FS FLORIDA STATUTE | | | | 1. SEE PAGE 14 OF THE PRODUCT APPROVAL. A 3" EDGE | | DISTANCE REQUIRES A FACTOR OF .83. | | | | 2. THE "SHUTTER CONNECTION MOUNTING TYPE" SHOULD | | CORRELATE WITH THE ANCHOR CHARTS ON THE PRODUCT | | APPROVAL. IT APPEARS THAT YOU ARE USING MOUNTING TYPES | | A, D, AND I. PLEASE NOTE THAT, IF THE ANCHOR SPACING | | WERE COMPLIANT (SEE COMMENT #1), THIS PERMIT WOULD NOT | | HAVE BEEN DENIED FOR THIS REASON ONLY. | | | | 3. ACCORDION SHUTTERS ARE, TO MY KNOWLEDGE, ALWAYS | | INSTALLED VERTICALLY (NOT HORIZONTALLY AS NOTED ON THE | | INSTALLATION SCHEDULE). PLEASE REVISE. ALSO PLEASE | | REVISE SPANS. FOR INSTANCE, OPENING 4 SPECIFIES A 209" | | SPAN. THIS EXCEEDS THE SPAN ALLOWED. FOR ACCORDION | | SHUTTERS, THE SPAN EQUALS BLADE LENGTH. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-10-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-06 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-10-06 |
Time |
14:09 |
Sent To |
|
|
Notes |
2008-10-06 14:12:11 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY | | | | ____ 1. PROVIDE BUILDING HEIGHT ON THE PLAN. DESIGN | | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE | | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A | | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT | | OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16. | | | | _XX_ 2. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR | | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN | | ANOTHER FORMAT, FBC*106. TWO SETS REQUIRED. | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | ____ 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL | | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. | | | | ____ 4. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310. | | | | ____ 5. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS | | WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH | | THE INSTALLATION SCHEDULE, ITEM 2 ABOVE. | | | | _XX_ 6. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE | | FOR EXPOSURE B. NOTE THAT THE DEFINITION FOR EXPOSURE C | | HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC | | R301.2.1.4. | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-11-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-11-03 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-11-03 |
Time |
14:05 |
Sent To |
B |
|
Notes |
2008-11-03 14:06:10 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-22 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-22 |
Time |
13:51 |
Sent To |
B |
|
Notes |
2008-10-22 13:52:11 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-10-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-07 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-07 |
Time |
15:45 |
Sent To |
B |
|
Notes |
2008-10-07 15:45:52 | TO "SHILL" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-10-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2008-10-06 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2008-09-23 |
Time |
10:39 |
Sent To |
|
|
Notes |
2008-09-23 10:39:21 | TO "MISC" BOX#1 |
|
|
|