Plan Review Details - Permit 08090412
Plan Review Stops For Permit 08090412
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-22 Cont ID  
Sent By jwitmer Date 2009-10-22 Time 14:59 Rev Time 5.00
Received By jwitmer Date 2009-10-22 Time 08:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-09-02 Cont ID  
Sent By jwitmer Date 2009-09-02 Time 15:59 Rev Time 2.00
Received By jwitmer Date 2009-09-02 Time 14:09 Sent To  
Notes
2009-09-02 16:51:54BUILDING PLAN REVIEW
 PERMIT: 08090412
 ADD: 1610 PALM BEACH LAKES
 CONT: CFR COASTAL
 TEL: (954) 868-9692
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 WEDNESDAY SEPTEMBER 02/2009
 3RD REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD
 BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE
 REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER
 BUILDING DATA DOES NOT PROVIDE AS TO WHAT CODE (YEAR)
 THIS PROJECT WAS DESIGNED.
  
 1E) PLEASE CORRECT. STRUCTURAL SHEET S.02 ALSO NEEDS TO
 BE UPDATED TO THE 2007 SUPPLEMENTS CURRENTLY READS 2006
 SUPPLEMENTS..
  
 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING
 INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE
 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING
 INFORMATION IN REGUARDS TO THE 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) TYPE OF OCCUPANCY, SHEET SP.01 INDICATE A A2
 OCCUPANCY, SECTION 303.1 INDICATES AN A2 OCCUPANCY IS
 RESTARAUNT, NIGHTCLUBS, BANQUET HALL, BARS AND
 NIGHTCLUBS PLEASE SEE A3 OCCUPANCY OF COMMUNITY HALLS,
 CHURCHES &AND COURT ROOMS, PLEASE REVISE.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE
 THIS TO BE A TYPE V-B / A-3 ASSEMBLY WITH 115373 SQ FT
 A TYPE V-B BUILDING WITH AREA INCREASESAND SPRINKLER
 THE MAXIMUM IS 28,500 SQ FT.. PLEASE CORRECT.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H) SP.01- REFRENCES A 4 HR FIRE SEPERATION WALL WITH 3
 HR OPENING PROTECTIVES IS THIS AN ADDITION OR IS THIS A
 TRUE 4 HR FIRE WALL CREATING 2 SEPERATE BUILDINGS? I
 BELIEVE THE ELECTRICAL PLAN REVIEWERR HAD BROUGHT UP
 MANY PROBLEMS IN THE ELECTRICAL DESIGN IF THIS WAS TO
 BE CONSIDERED A SEPERATE BUILDING?
 .
 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD
 BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S.
 S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR
 AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD
 MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) COMPLIED.
  
 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS
 REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR
 WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR
 RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE
 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN
 THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY
 SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING
 AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING
 BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE.
 LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK
 INTO THE BUILDING, PLEASE PROVIDE RATIONAL .
  
 3B) COMPLIED.
  
 3C) COMMENT 3A) COVERS THIS OPENING.
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUIULDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6) COMPLIED.
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 &
 A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE
 OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK.
  
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9-15 ) COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-01-12 Cont ID  
Sent By jwitmer Date 2009-01-12 Time 11:28 Rev Time 2.22
Received By jwitmer Date 2009-01-12 Time 11:28 Sent To  
Notes
2009-01-12 14:44:50BUILDING PLAN REVIEW
 PERMIT: 08090412
 ADD: 1610 PALM BEACH LAKES
 CONT: CFR COASTAL
 TEL: (954) 868-9692
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 MONDAY JAN.12,2009
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD
 BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE
 REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER
 BUILDING DATA DOES NOT PROVIDE AS TO
 WHAT CODE (YEAR) THIS PROJECT WAS DESIGNED.
  
 1E) SP.01 BUILDING DATA, THE PLANS ALSO NEGLECT TO
 IDENTIFY THE 2004 FBC, EXISTING BUILDING CODE, CHAPTER
 9 THAT DEALS WITH ADDITIONS, PLEASE CORRECT. STRUCTURAL
 SHEET S.01& S.02 ALSO NEEDS TO BE UPDATED TO THE 2007
 SUPPLEMENTS.
  
 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING
 INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE
 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING
 INFORMATION IN REGUARDS TO THE 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE
 THIS TO BE A TYPE IV OR HEAVY TIMBER STRUCTURE, PLEASE
 CORRECT.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 H) SP.01- REFRENCES A TABLE 704.1 FIRE SEPERATION BY
 OCCUPANCY PLEASE UPDATE CODE SECTION THIS IS A 2001 FBC
 REFERENCE.
 .
 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD
 BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S.
 S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR
 AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR
 THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY
 FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD
 MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) REQUIRED STATEMENT ON PLANS: THRESHOLD BLDG, W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS
 REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR
 WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR
 RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE
 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN
 THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY
 SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING
 AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING
 BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE.
 LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK
 INTO THE BUILDING, PLEASE PROVIDE RATIONAL .
  
 3B) COMPLIED.
  
 3C) COMMENT 3A) COVERS THIS OPENING.
  
 4) BUILDING PROVISO:
 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) BUIULDING PROVISO:
 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL
 FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE
 UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A
 HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE
 WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED
 FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER
 AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO
 PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO
 FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A
 HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A
 FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A
 LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE
 SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS
 CHAPTER.
  
 6) 2ND REQUEST, 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 &
 A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE
 OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK.
  
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) COMPLIED.
  
 10) SHEET S.02 NOTE # 5 FOR WIND INFORMATION IS
 MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7-02.
  
 2. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 3. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 11) 2ND REQUEST, SHEET PA.01 PARKING GARAGE PLEASE
 PROVIDE THE FOLLOWING INFORMATION IN REGUARDS TO THE
 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 12) COMPLIED.
  
 13-14) COMPLIED.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By jwitmer Date 2008-10-08 Time 14:28 Rev Time 6.65
Received By jwitmer Date 2008-10-08 Time 14:28 Sent To  
Notes
2008-10-08 16:57:18BUILDING PLAN REVIEW
 PERMIT: 08090412
 ADD: 1610 PALM BEACH LAKES
 CONT: CFR COASTAL
 TEL: (954) 868-9692
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS,
 REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL
 REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD
 BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE
 REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004
 SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE
 CODE.
  
 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER
 BUILDING DATA DOES NOT PROVIDE AS TO
 WHAT CODE (YEAR) THIS PROJECT WAS DESIGNED.
  
 1E) SP.01 BUILDING DATA, THE PLANS ALSO NEGLECT TO
 IDENTIFY THE 2004 FBC, EXISTING BUILDING CODE, CHAPTER
 9 THAT DEALS WITH ADDITIONS, PLEASE CORRECT. STRUCTURAL
 SHEET S.01 ALSO NEEDS TO BE UPDATED TO THE 2007
 SUPPLEMENTS.
  
 1F) SP.01 CALCULATIONS THE BUILDING INFORMATION AND
 CODE SECTIONS ARE NOT TAKEN FROM THE 2004 FBC PLEASE
 PROVIDE THE FOLLOWING BUILDING INFORMATION IN REGUARDS
 TO THE 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD
 BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S.
 S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) SUBMIT: THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) REQUIRED STATEMENT ON PLANS: THRESHOLD BLDG, W.P.B.
 AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS
 REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR
 WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR
 RATED OPENING. IS THE INTENT TO MAKE
 THIS KITCHEN NOT AN DDITION BUT A SPERATE SINGLE STORY
 BUILDING THAT WOULD NOT MEET THE THRESHOLD
 REQUIREMENTS?
  
 3B) LS.01 THIS PLAN INDICATES ON THE EXISTING BUILDING
 A PARTIAL BREAK ROOM, AND THE DOOR# 5 FROM THE BREAK
 ROOM INTO THE NEW HALLWAY NOT PART OF A REQUIRED
 EGRESS. SHEET A.01 PROVIDES ENOUGH
 WALLS TO CALCULATE THE AREA OF THE BREAK ROOM AS 827 SQ
 FT/ /15 = 56 AS AN OCCUPANT LOAD. THIS WOULD REQUIRE
 TWO MEANS OF EGRESS PLEASE PROVIDE DETAILS ENOUGH ON
 THE EXISTING BREAK ROOM PROVIDING
 2 EGRESS PATHS. TABLE 1014.1.
  
 3C) LS.01 THIS DOOR# 5 IT WOULD ALSO APPEAR TO NEED 3
 HR OPENING PROTECTION IF THE OVERHEAD DOOR WITHIN THE
 SAME BREAK ROOM REQUIRES IT? ADDITIONAL INFORMATION
 REQUIRED.
  
 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO
 THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2
 DOES NOT PROVIDE INFORMATION AS TO TYPE OF ROOFING
 ASSEMBLIES.
 3B) METAL ROOF DECK PARKING GARAGE
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) A.01 THE KITCHEN EXTERIOR WALLS INDICATE
 WATERPROOFING TO BE APPLIED, PLEASE PROVIDE PRODUCT
 INFORMATION . 1807.3.2.1 & 1807.3.2.
  
 10) SHEET S.02 NOTE # 5 FOR WIND INFORMATION IS
 MISSING:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7-02.
  
 2. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 3. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED
 DESIGN PROFESSIONAL.
  
 11) SHEET PA.01 PARKING GARAGE PLEASE PROVIDE THE
 FOLLOWING INFORMATION IN REGUARDS TO THE 2004 FBC:
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503,
 CHAPTER 6, & TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 12) PA.02 INDICATES RAMPED DRIVE TO BACK UP AGAINST
 BACK WALL OF OPEN PARKING GARAGE, PLEASE PROVIDE
 WATERPROOFING DETAILS 1807.3.2.1 & 1807.3.2.
  
 13) PA.02 / PS.02 OPEN WALL SECTION INDICATES THE METAL
 DECKING TO BE FASTENED TO METAL TRUSSES PER
 MANUFACTURERS SPEC, PLEASE PROVIDE
 1609.6.2.2.COMPONENTS AND CLADDING.
  
 14) PA.02/ PS.02 OPEN WALL SECTION DOES NOT PROVIDE
 METAL HI-HAT CONNECTION TO THE METAL TRUSS, PLEASE
 PROVIDE 1609.2.2 COMPONENTS AND CLADDING.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-20 Cont ID  
Sent By dpalmer Date 2009-10-20 Time 09:22 Rev Time 0.00
Received By dpalmer Date 2009-10-20 Time 09:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-15 Cont ID  
Sent By dpalmer Date 2009-09-15 Time 14:51 Rev Time 0.00
Received By dpalmer Date 2009-09-15 Time 14:51 Sent To  
Notes
2009-09-15 14:51:16 
  
 ** TEMPORARY DENIED PLANS **
  
  
 1) NOTE: THIRD SET IS MISSING ES.01. MISSING SHEET MAY
 BE BROUGHT IN. MUST SET UP TIME TO MEET WITH REVIEWER
 AND INSERT SHEETS.
  
 2) NOTE: PRESCRIPTIVE METHOD C ON PLANS, ALTHOUGH
 METHOD A SUBMITTED IN FLA COM FORM VERSION. EITHER IS
 OK WITH ELECTRICAL HOWEVER MAY NOT USE BOTH.
 PLEASE CONTACT REVIEWER FOR OPTIONS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-01-14 Cont ID  
Sent By dpalmer Date 2009-01-14 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2009-01-14 Time 11:42 Sent To  
Notes
2009-01-14 11:42:59** DENIED 2ND REVIEW **
  
  
 ** UNTIL DATE OF REVIEW THERE WAS NO SPECIFIC CONTACT
 FOR ELECTRICAL. DURING REVIEW A CALL WAS PLACED TO JOHN
 VAUGHAN. ELECTRICAL ENGINEER JAMES MAKO CALLED TO GO
 OVER COMMENTS.
 SEVERAL ITEMS WERE GONE OVER HOWEVER AS THE REVIEW WAS
 NOT COMPLETE AT THE TIME OF THE CONVERSATION A FUTURE
 CALL MAY BE NEEDED ONCE ALL REVIEW NOTES ARE POSTED.
 SOME NOTES FROM PREVIOUS REVIEW WILL REMAIN ALONG WITH
 NEW COMMENTS BASED ON THE DOCUMENTS NOW PLACED ON THE
 PLANS AND SUBMITTED WITH THE DOCUMENTS.
  
 1) NOTE: PLEASE BE AWARE THAT THE NOTICE OF
 COMMENCEMENT WHICH WAS RECORDED ON SEPTEMBER 15TH, 2008
 HAS BECOME VOID. PLEASE SEE FS 713.13(2).
 WHEN WORK HAS NOT COMMENCED WITHIN 90DAYS OF RECORDING
 SUCH NOC THE NOC BECOMES VOIDED. THIS WOULD ONLY NEED
 TO BE RE-RECORDED.
 THIS COMMENT IS GIVEN AS INFORMATION ONLY TO HELP
 AVOIDED ANY DELAYS IN THE PERMITTING AND INSPECTION
 PROCESS FOR THE OWNER AND CONTRACTOR.
  
 2) NOTE: PLEASE SEE FBC 13-101.1, 13-400.0.
 THE PREVIOUS REVIEW REQUESTED LIGHTING PERFORMANCE
 CALCULATIONS IN CONFORMANCE WITH THE FBC CHAPTER 13,
 13-415.2.
 PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3.
 THE SUBMITTED METHOD *A* MAY BE USED WHEN YOU HAVE A
 WHOLE BUILDING OR AN ADDITION WHICH IS NOT INCLUDING
 ANY RENOVATION TO ANY EXISTING BUILDING AREAS.
 THE METHOD *A* SUBMITTED DOES NOT CONTAIN ANY
 SIGNATURE, OR DATE BY THE RESPONSIBLE DESIGNER.
 MUST CONTAIN THESE PER 13-103.1. PLEASE SEE DESIGNERS
 PERMITTED TO DO THIS UNDER FLORIDA STATUTES 471, 481
 AND 489.
 THE METHOD *A* SUBMITTED CLEARLY STATES *RENOVATION TO
 EXISTING BUILDING*. IF THIS IS NOT AN ADDITION, OR
 WHOLE BUILDING NEW CONSTRUCTION THEN THIS METHOD MAY
 NOT BE USED.
 IN ANY CASE ALL INFORMATION ON ANY INPUT DATA REPORT
 NEEDS TO COORDINATE WITH ALL INFORMATION ON PLANS.
 THERE ARE SEVERAL ITEMS ON THE IDR AS SUBMITTED WHICH
 ARE EITHER NOT COMPLETE OR THESE ITEMS ARE NOT THE SAME
 AS ON PLANS.
 EXAMPLES:
 THE METHOD OF LIGHTING CONTROLS STATE *MANUAL ON/OFF*.
 THIS IS NOT THE CASE AS ANY NEW PRESCRIPTIVE LIGHTING
 CONTROLS IN A BUILDING GREATER THAN 5K SQ FT SHALL
 COMPLY WITH 13-415.1.ABC.1, .1.1, .1.2, .1.3 AND .1.4.
 SEE THE FOLLOWING COMMENT WITH RESPECT TO LIGHTING
 CONTROLS.
 EXAMPLE:
 THE EXTERIOR LIGHTING ON THE IDR IS COMPLETELY BLANK.
 THIS IS ONE ITEM WHICH THE PLANS CLEARLY CONTAIN
 EXTERIOR LIGHTING YET THERE ARE NO FIXTURES ON THE
 IDR.??
 THE PLANS INDICATE SPACE BY SPACE FROM TABLE *B*.
 PLEASE SEE 13-415.2.ABC.1 WHICH CLEARLY STATES THAT IS
 NOTE PERMITTED TO USE MORE THAN ONE METHOD.
 THIS REVIEWER IS OK WITH USE OF SPACE BY SPACE FOR
 LIGHTING PERFORMANCE LEVELS HOWEVER WE WOULD STILL NEED
 EXTERIOR PER 13-415.2.ABC.1.3.
  
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR REQUIRED LIGHTING CONTROLS.
 ALL LIGHTING IN A BUILDING GREATER THAN 5K SQ FT SHALL
 CONTAIN SOME SORT OF AUTOMATED CONTROLS SO WHEN THE
 BUILDING IS NOT OCCUPIED THE LIGHTING. THERE ARE
 COUNTLESS ARTICLES ON THE ENERGY CODE IN THE STATE OF
 FLORIDA AS WELL AS THE REQUIREMENTS NATIONALLY IN THE
 IECC.
 THE FEDERAL CHANGES IN JULY OF 2004 IN THE INTEREST OF
 ENERGY CONSERVATION REQUIRED ALL STATES BY THEIR
 FOLLOWING CODE CYCLE TO ADOPT THE 1999 ASHAE 90.1 OR
 BETTER. SINCE OCTOBER 1ST, 2005 THE 2004 FBC HAS
 REQUIRED THIS. THIS HAS BEEN IN THE CODE FOR OVER 3 AND
 HALF YEARS. THERE HAVE ALSO BEEN SEVERAL REVISIONS TO
 THE 2004 FBC SINCE ADOPTED IN OCT.2005
 THE RESPONSE LETTER CONTAINS RESPONSES TO ALL OTHER
 COMMENTS WITH THE EXCEPTION OF THIS PREVIOUS COMMENT.
 THE RESPONSE IS BLANK?
 ** PLEASE CALL TO GO OVER IF NEEDED. THIS IS NOT A
 SEPARATE BUILDING BY DEFINITION SMALLER THAN 5K SQ FT.
 THE SWITCHING SHOWN ON PLANS IS DONE BY STANDARD SINGLE
 POLE SWITCHES ALONG WITH STANDARD 3-WAY SWITCHES. THE
 INFORMATION ON SHEET E.04.11 IS NOT ENOUGH FOR
 COMPLIANCE. THE KITCHEN IS NOT AN AREA WHICH IS EXEMPT
 PER THE FBC. PLEASE CALL TO GO OVER. THERE ARE
 SUBSTANTIAL DIFFERENCES IN MOTION SENSORS COMPARED TO
 DUAL TECHNOLOGY DEVICES AND ALSO THESE SAME TYPE OF
 DEVICES USED FOR EGRESS WHICH WOULD BE FAIL SAFE
 OPERATION.
  
 4) NOTE: PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO
 FBC 11-4.28.1, .2 AND .3 FOR ALL DEVICES FOR FA SYSTEM
 TO COMPLY WITH MINIMUM LEVELS, HEIGHTS ETC FOR ADA
 COMPLIANCE.
 THE RESPONSE MENTIONS TO SEE REVISED PLANS HOWEVER THE
 FA SHEET E.06 DOES NOT INDICATE THE MINIMUM LEVELS FOR
 STROBES AND SOUNDING DEVICES.
 PLEASE ALSO SEE THERE ARE SEVERAL NOTES WHICH THERE
 SEEMS TO HAVE BEEN SOME SORT OF MISHAP WITH THE
 PRINTING. SEE NOTES 17 UNDER FIRE ALARM NOTES, NOTES
 UNDER SEQUENCE OF OPERATION, NOTES UNDER THE SYMBOL
 LEGENDS WHICH HAS NOTES PRINTED OVER NOTES. MANY ITEMS
 CAN NOT BE READ.
 THESE HAVE BEEN HIGH-LIGHTED ON ONE OF THE SET OF
 PLANS.
 SHEET E.06.1 ALSO DOES NOT CONTAIN ANY OF THIS MONTHS
  
 5) NOTE: THE FOLLOWING ITEMS WITH RESPECT TO RISER,
 PANELS, ETC STILL NEED COORDINATION.
  
 A) PLEASE SEE PANEL HU-2 WHICH INDICATES 125AMP OVER
 CURRENT PROTECTION TO A 100AMP DISCONNECT ON THE LINE
 SIDE OF TRANSFORMER
 B) PLEASE SEE TRANSFORMER EK. RISER AND PLANS NOTE THIS
 NEW 45KVA UNIT WILL BE REPLACING THE EXISTING 30 KVA
 TRANSFORMER. THIS IS OK, HOWEVER PLEASE SEE THE
 TRANSFORMER SCHEDULE ALONG WITH THE PRIMARY OVER
 CURRENT PROTECTION.
 THE SCHEDULE SHOWS A 45KVA TRANSFORMER HOWEVER ONLY
 WITH THE AMPERAGE RATING OF THE PREVIOUS 30KVA UNIT.
 45KVA AT 480V IS 54.15AMPS NOT THE 36 AS LISTED ON
 SCHEDULE. THE 36 AS LISTED ON SCHEDULE WOULD BE A 30KVA
 UNIT AT 480V.
 THIS WILL AFFECT THE OVER CURRENT PROTECTION ON THE
 PRIMARY ALSO AS THIS IS NOTED AS 45AMPS.
 THESE ITEMS AFFECT THE POWER PANEL SCHEDULE SHEET AS
 WELL AS *BOTH* RISERS ON SHEET E.02.
 110.3,110.14,450.3,240.4,310.16,408, 240.21 ETC
  
 6) NOTE: PLEASE SEE 210.8B2 AS ALL 15/20AMP 120V
 RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI/ OR GFCI
 PROTECTED. SEE CIRCUITS SUCH AS EK-9, EK-11 ARE TWO
 EXAMPLES IN WHICH NO PROTECTION IS SHOWN. THESE ARE NOT
 THE ONLY TWO.
  
 7) NOTE: AS NO LIGHTING ETC IS SHOWN FOR A COMPLETE
 HOOD SYSTEM AND HOOD MAY BE UNDER SEPARATE PERMIT
 PLEASE KNOW THAT ALL LIGHTING AND ELECTRICAL PER
 NFPA-96 SHALL BE INTERCONNECTED AND SHUT DOWN UPON
 ACTIVATION OF SYSTEM FOR FIRE SUPPRESSION.
 NO INFORMATION NOTED AT THIS TIME AND WILL NEED TO BE
 NOTED UNDER SEPARATE PERMIT.
  
 8) NOTE: SHEET E.05 CONTAINS SOME NOTES FOR POSSIBLE
 ACCESS CONTROL. THE SYMBOL LEGEND MAKES NOTE OF
 POSSIBLE MAG-LOCKS ETC.
 PLEASE SEE NFPA-101 CHAPTER 7 FOR EGRESS CONTROLS. NO
 DEVICES UNDER NORMAL OR EMERGENCY CONDITIONS SHALL
 IMPEDE THE EGRESS OUT OF ANY AREAS. SEE COMMENTS FROM
 FIRE MARSHAL.
 AS THE COMPLETE SYSTEM IS NOT DETAILED, THIS MAY BE
 UNDER SEPARATE PERMIT FOR LOW VOLTAGE ACCESS CONTROLS.
 FBC 105.1.
  
 9) NOTE: MANY OF THE FIXTURES ARE HALF SHADED AND
 SYMBOL LEGEND SEEMS TO INDICATE EMERGENCY POWER. THE
 FIXTURE LEGEND HOWEVER DOES NOT LIST ANY BATTERY BACK
 UP BALLAST AS REQUIRED.
 PLEASE ADJUST. NFPA-101 7.8, 7.9, FBC 1006.1
 PLEASE ALSO KNOW AS NOTED ABOVE, ANY EGRESS LIGHTING
 BEING CONTROL BY OCCUPANCY SENSOR TYPES DEVICES PER FBC
 13-415.1.ABC.1, SHALL BE FAIL SAFE TYPE CONTROL DEVICES
 PER FBC 1006.1.2, NFPA-101 7.8.1.2.2.
  
 10) NOTE: PLEASE COMPLETE ALL LIGHTING CIRCUITS ON
 PLANS AND COORDINATE WITH THE PANEL SCHEDULES.
 BE SURE TO SEE 7..12F FOR CIRCUITING FOR EMERGENCY AND
 EXIT LIGHTS.
 408.4, FBC 106.1.1, 106.5.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 08:39 Sent To  
Notes
2008-10-08 08:39:58 
 ** DENIED **
  
 1) NOTE: PLEASE SEE THERE IS A LIST OF *EXPIRED*
 PERMITS BASED ON PRIME PERMIT APPLIED FOR THIS SCOPE OF
 WORK FROM 2005. THE BASE PERMIT IS 05041896.
 THERE ARE ITEMS ON PLANS WHICH DO NOT SHOW UP ON RECORD
 PLANS SUBMITTED IN LAST 10YEARS. THE EXPIRED APPLIED
 SCOPE OF WORK AS MENTIONED SHOWS SOME OF THIS WORK TO
 BE DONE HOWEVER NO RECORD OF PERMITTING. A FIELD
 PRE-INSPECTION MAY BE NEEDED TO VERIFY ALL PERMITTED
 SCOPE OF WORK.
  
 2) NOTE: PLEASE SEE COMMENTS WHICH WILL BE FROM OTHER
 TRADES WHICH WILL HAVE AN AFFECT ON THE ELECTRICAL
 PLANS.
 PLEASE BE SURE THESE ARE ALL COORDINATED.
 PLEASE SUBMIT COMPLETED PLANS. SEE NOTES BELOW AS THERE
 ARE SEVERAL ITEMS WHICH WERE EITHER NOT SHOWN ON NOT IN
 DESIGN AT THIS TIME. THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE ON
 PLANS.
 2004 FBC W/ 2007 REVISIONS.
  
 4) NOTE: THE PLANS SUBMITTED DO NOT INCLUDE ANY
 ELECTRICAL FOR THE NEW DETACHED PARKING STRUCTURE.
 PLEASE BE SURE TO SEE 225.31-225.39, AND 250.32, 250.50
  
 5) NOTE: PLEASE PROVIDE MINIMUM LOCATIONS AND LEVELS
 FOR ALL HORN/STROBE DEVICES FOR FIRE ALARM SYSTEM
 MEETING FS 633, NFPA-72 AND FBC 11-4.28.1, 2 AND .3.
 PLEASE BE SURE TO SHOW ALL LOCATIONS AND MINIMUM LEVELS
 OF DEVICES.
  
 6) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS THERE
 ARE SEVERAL INCONSISTENCIES. BELOW ARE SOME EXAMPLES
 HOWEVER THESE ARE ARE NOT ALL.
  
 EXAMPLE: PLEASE SEE MAIN DISTRIBUTION PANEL AS THIS
 INDICATES A FEED TO DP1 THROUGH A TRANSFORMER HOWEVER
 THE RISER DOES NOT INDICATE ANY TRANSFORMER AND BOTH
 MAIN SWITCH BOARD AND DP1 IS 277/480. PLEASE CORRECT.
  
 EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL EK AS
 EXISTING YET THE SCHEDULE SHOWS THIS AS NEW.
  
 EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL K AS
 EXISTING YET THE SCHEDULE SUBMITTED SHOWS THIS AS NEW.
  
 EXAMPLE: NOTES ON RISER SHEETS MENTIONS SOME
 TRANSFORMER WILL BE CHANGED TO 75 KVA YET THE RISER
 SHOWS BOTH OF THEM AS 45KVA.
  
 EXAMPLE: PLEASE SEE HU2 ON RISER WHICH INDICATES AS
 80AMP BREAKER TO THE TRANSFORMER YET THE PANEL SCHEDULE
 INDICATES 90AMP BREAKER.
  
 THESE ARE SOME EXAMPLES ONLY WHICH ELECTRICAL RISER AND
 PANELS NEED SOME COORDINATION.
  
 NEC 230,215,240,408,220, ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY AND COORDINATION.
  
 7) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 THE PANEL SCHEDULE. THERE ARE SEVERAL INCONSISTENCIES
 WITH WHAT IS SHOWN ON THE PLANS WITH CIRCUITS WHICH ARE
 SHOWN ON SCHEDULES. SOME CIRCUITS ON PANELS WHICH ARE
 ON PLANS ARE BLANK, SOME ARE SPARES, AND MANY ARE NOTED
 FOR ELECTRICAL EQUIPMENT AND CIRCUITS WHICH ARE NOT THE
 SAME ON PLANS. BELOW ARE SOME EXAMPLES AND IS IN NO WAY
 ALL ITEMS.
  
 EXAMPLE: PLEASE SEE PLANS AS SOME CIRCUITS ARE LABELED
 WITH AN *XXX-XX* ETC
  
 EXAMPLE: PLEASE SEE CIRCUIT K-23 ON PLANS AS THIS IS
 BLANK ON SCHEDULE.
  
 EXAMPLE: PLEASE SEE K 16, AND 18 AS THESE ARE NOTED AS
 THE DISHWASHERS ON PLANS YET THE PANEL SCHEDULE
 INDICATES THESE ARE MICROWAVES.
  
 EXAMPLE: PLEASE SEE EK-23,25,27 ON PLAN AS ALL OF THESE
 ARE BLANK ON THE PANEL SCHEDULE.
  
 EXAMPLE: PLEASE SEE EK-14, 12 WHICH ARE SHOWN ON PLAN
 FOR REFRIGERATOR/FREEZER EQUIPMENT YET THE PANEL
 SCHEDULES INDICATES A BREAKER FOR LIGHTING AND THE
 OTHER IS SHOWN AS A SPARE.
  
 EXAMPLE: PLEASE SEE K-29 WHICH IS SHOWN ON PLANS
 FEEDING GFI RECEPTACLES FOR BATH ROOM ETC YET THE PANEL
 SCHEDULE INDICATES THIS AS LIGHTING.
  
 EXAMPLE: PLEASE SEE CIRCUITS EK 4, AND 6 WHICH IS SHOWN
 AS REFRIGERATOR EQUIPMENT YET THE PANEL SCHEDULE
 INDICATES A 3-POLE BREAKER FOR SUMP PUMPS.
  
 *** THESE ARE ONLY SOME OF THE EXAMPLES IN WHICH
 COORDINATION IS NEEDED. THERE ARE OTHERS HOWEVER THIS
 REVIEW IS GIVING SOME EXAMPLES AS BENEFIT TO THE
 DESIGNER OF RECORD.
 PLEASE SEE THE SECTION OF 408.4 WHICH WAS EXTRACTED
 FROM THE 2005 NEC.
  
 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.
 THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND
 LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANELBOARDS AND
 SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT
 DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE
 OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND
 LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT
 IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS
 AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE
 PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR
 CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS
 SPECIFIC TO SWITCHBOARDS AND PANELBOARDS; HOWEVER, THE
 IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL
 DISCONNECTING MEANS.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 NEC 408.4, 310.16,240.4 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION,
 COORDINATION AND CLARITY OF PLANS.
  
 8) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT
 PROTECTION ON RISER FOR TRANSFORMER FEEDING PANEL *K*
 IS TOO HIGH. THE RISER DOES CONTAIN A SCHEDULE WHICH
 NOTES OVER CURRENT PROTECTION AT THE MAXIMUM OF 125%.
 HOWEVER THE RISER STILL ALSO SHOWS THIS SAME
 TRANSFORMER AS A 45KVA UNIT. IF THIS UNIT IS REVISED TO
 75KVA THEN THE 90AMP OCP WOULD BE OK.
  
 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS FOR ALL NEW LIGHTING
 BEING INSTALLED. AS NO DEVICES OR SYSTEM IS BEING SHOWN
 AT THIS TIME NO REVIEW OF THESE CAN BE DONE.
  
 10) NOTE: PLEASE COMPLETE A FIXTURE LEGEND FOR SPECIFIC
 FIXTURES. PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS FOR ALL AREAS IN SCOPE OF WORK. PLEASE SEE
 FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3.
 PLEASE KNOW AS NO PERFORMANCE CALCULATIONS WERE
 SUBMITTED IT IS NOT POSSIBLE TO SUPPLY ANY REVIEW
 COMMENTS ON THOSE ITEMS.
  
 11) NOTE: PLEASE KNOW ANY LOW VOLTAGE FOR SOUND, ACCESS
 CONTROL WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT,
 WITH PLANS AND FEES BASED ON THAT SCOPE OF WORK.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-10-22 Cont ID  
Sent By mgonzale Date 2009-10-22 Time 11:35 Rev Time 4.00
Received By mgonzale Date 2009-10-22 Time 11:32 Sent To  
Notes
2009-10-22 11:35:29PASSED WITH PROVISOS
  
 #1 PROJECT HAS COMPLIED WITH DOCUMENTATION ASKED BY
 ENGINEERING DEPT.
 #2 SITE IS UNDER AN ACRE HOWEVER PROJECT HAS COMPLIED
 WITH SFWMD AND CITY STORMWATER ENG REVIEW 10-16-09
 #3 PROJECT IS STILL SUBJECT TO NDPES REQUIREMENTS AS TO
 POLLUTION PREVENTION PLANS
 #4 PROVIDE AS-BUILTS TO ENGINEERING DIV FOR FINAL
 APPROVAL.
  
 MANUEL JULIAN GONZALEZ
 CS ENGINEERING REVIEWER
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2009-09-29 Cont ID  
Sent By mgonzale Date 2009-09-29 Time 11:26 Rev Time 1.00
Received By mgonzale Date 2009-09-29 Time 11:26 Sent To  
Notes
2009-09-29 11:37:13FAILED:
  
 THE CITY NEEDS A SEPERATE SUBMITTAL FROM YOUR CIVIL
 ENGINEER TO CITY OF WEST PALM BEACH ENGINEERING.
  
 IT'S IMPORTANT TO UPDATE YOUR PERVIOUS AND IMPERVIOUS
 GROUND AREAS SO THAT WE CAN UPDATE YOUR STORMWATER
 ACCOUNT WITH THE CITY.
  
 FLORIDA STATE LEGISLATURE CREATED WATER MANAGEMENT
 DISTRICTS TO CONTROL WATER FLOWS FOR FLOOD PROTECTION
 AND PRESERVE WATER RESOURCES. THE SOUTH FLORIDA WATER
 MANAGEMENT DISTRICT IS ONE OF 5 DISTRICTS WHICH WERE
 CREATED, AND ENCOMPASSES THE SOUTHEAST COAST OF
 FLORIDA. CHAPTER 373 OF THE FLORIDA STATUTES (F.S.)
 (THE FLORIDA WATER RESOURCES ACT OF 1972), GIVES
 AUTHORITY TO THE SFWMD TO CARRY OUT ITS REGULATORY
 DUTIES, THE ENVIRONMENTAL RESOURCE PERMIT INFORMATION
 MANUAL VOLUME IV UPDATED IN DECEMBER 2003, IS THE
 LATEST EDITION.
  
 WATER QUALITY CRITERIA MUST BE IN PLACE AS RUNOFF SHALL
 BE DISCHARGED FROM IMPERVIOUS SURFACES THROUGH
 RETENTION AREAS, DETENTION DEVICES, FILTERING AND
 CLEANSING DEVICES, OR SUBJECT TO SOME OTHER TYPE OF
 BEST MANAGEMENT PRACTICE (BMP) PRIOR TO DISCHARGE FROM
 THE PROJECT SITE. PROJECTS WHICH INCLUDE SUBSTANTIAL
 PAVED AREAS, SUCH AS, SHOPPING CENTERS, LARGE HIGHWAY
 INTERSECTIONS WITH FREQUENT STOPPED TRAFFIC, AND HIGH
 DENSITY DEVELOPMENTS, PROVISIONS SHALL BE MADE FOR THE
 REMOVAL OF OIL, GREASE, AND SEDIMENT FROM STORMWATER
 DISCHARGES.
  
 OFF-SITE DISCHARGES ARE LIMITED TO RATES NOT CAUSING
 ADVERSE IMPACTS, AND: A) HISTORIC DISCHARGE RATES, OR,
 B) RATES DETERMINED IN PREVIOUS DISTRICT PERMIT
 ACTIONS, OR; C) RATES SPECIFIED IN DISTRICT CRITERIA.
  
 OTHER ELEMENTS THAT MUST BE CONSIDERED ARE FLOOD
 PROTECTION OF BUILDING FLOORS AND FLOOD PROTECTION OF
 ROADS AND PARKING LOTS.
  
 STORMWATER BEST MANAGEMENT PRACTICES (BMPS) ARE METHODS
 FOUND TO BE EFFECTIVE WAYS TO PREVENT POLLUTION FROM
 ENTERING WATERWAYS THROUGH STORMWATER RUNOFF. THE
 SECTION CONSIDERS BOTH STRUCTURAL BMPS, AS WELL AS, AN
 EXPLORATION OF NON-STRUCTURAL SOURCE CONTROLS.
 STRUCTURAL BMPS ARE ENGINEERED AND CONSTRUCTED TO
 REDUCE, CAPTURE, AND TREAT POLLUTION GENERATED BY
 STORMWATER RUNOFF. GENERALLY, STRUCTURAL BMPS REQUIRE
 ADDITIONAL LEVELS OF MAINTENANCE TO REMAIN OPERATIONAL
 AND EFFECTIVE. NON-STRUCTURAL BMPS INCLUDE GENERAL
 PRACTICES AND POSSIBLY RULES AND REGULATIONS TO CONTROL
 POLLUTANTS BEFORE THEY ENTER THE STORMWATER SYSTEM.
  
 SEDIMENTS, OILS, GREASES, HYDROCARBON RESIDUE, HEAVY
 METALS, AND ORGANIC NUTRIENTS ARE TYPICAL TYPES OF
 POLLUTION GENERATED BY AN URBAN ENVIRONMENT. IN
 ADDITION, FERTILIZERS AND PESTICIDES CAN CONTRIBUTE TO
 POLLUTANT LOADINGS.
  
 PLEASE CONSIDER THE FOLLOWING AND RESPOND TO CITY OF
 WPB ENGINEERING DEPT. 4TH FLOOR ATTENTION BRIAN MOREE,
 ENGINEERING CONTRUCTION SUPERVISOR. THANK YOU FOR YOUR
 ATTENTION.
 THE WEB LINK BELOW CAN PROVIDE YOU THE "DEVELOPMENT
 PERMIT PACKAGE" FOR YOUR SUBMITTAL .
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
  
 PLAN SPECIFIC COMMENTS:
 SHEET C-2 DOES NOT CALL OUT ONE OF THE CATCH BASINS AS
 EXISTING NOR PROPOSED
 OUTFALL IS NOT CLEARLY SHOWN.
 C-1 AND C-2 COULD BE COMBINES INTO ONE SHOWING ALL
 DRAINAGE IMPROVEMENTS.
 IDENTIFY ALL DRAINAGE EASEMENTS AND OUTFALLS ON THE
 PLAN.
 NO POLLUTION PREVENETION PLAN SHOWN.
  
 PROVIDE WRITTEN RESPONSE TO PREVIOUS COMMENTS BY
 RCHOKSI AND EFABIAN. (PREVIOUS ENGINEERING REVIEW
 COMMENTS)
  
 MANUEL JULIAN GONZALEZ
 CS ENGINEERING REVIEW
 401 CLEMATIS STREET, 1TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2009-01-13 Cont ID  
Sent By efabian Date 2009-01-13 Time 11:06 Rev Time 0.00
Received By efabian Date 2009-01-13 Time 11:06 Sent To  
Notes
2009-01-13 11:05:39DUMPSTER ENCLOSURE SHOWN ON SHEET C.02 IS SMALLER THAN
 THE DETAIL OF IT ON SHEET C.03 AND SHOULD MATCH THE
 DIMENSIONS OF THE DETAIL. THE ENCLOSURE SHOULD BE
 RECONFIGURED TO ALLOW A 5 FOOT PERIMETER LANDSCAPE
 BUFFER.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By rchokshi Date 2008-09-24 Time 08:53 Rev Time 0.00
Received By rchokshi Date 2008-09-24 Time 08:49 Sent To  
Notes
2008-09-24 08:52:56FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B), EFFECTIVE
 MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS &
 TURBIDITY DETAILS OF POLLUTION PREVENTION . PLEASE SHOW
 ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE, &
 TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE. HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 5. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 50, 100 YEAR FLOOD
 CRITERIA AND CROWN OF THE ROAD WHEN YOU DETERMINE THE
 FIRST FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 7. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT & STORM WATER QUALITY CALCULATIONS TO 1000 45TH
 STREET FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT.
  
 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-10-27 Cont ID  
Sent By mawillia Date 2009-10-27 Time 12:51 Rev Time 0.00
Received By mawillia Date 2009-10-27 Time 12:26 Sent To  
Notes
2009-10-27 12:51:51*****APPROVED*****
  
 PLAN SHEETS LS.01, LS.02, AND LS.03 WERE STAMPED,
 INITIALED, AND DATED. PLAN SHEETS A.02, E.04, E.06,
 E.06.1, AND FP.01 WERE PREVIOUSLY FIRE-STAMPED ON
 09/22/2009.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-09-22 Cont ID  
Sent By mawillia Date 2009-09-22 Time 11:33 Rev Time 0.00
Received By mawillia Date 2009-09-22 Time 10:36 Sent To  
Notes
2009-09-22 10:38:58*****PARTIAL APPROVAL*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED. PLAN SHEETS A.02, E.04, E.06, E.06.1,
 AND FP.01 WERE STAMPED, INITIALED, AND DATED; HOWEVER
 SHEETS LS.01, LS.02, AND LS.03 ARE TO BE FIRE-STAMPED
 WHEN THE BUILDING EXAMINER'S COMMENTS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-02-09 Cont ID  
Sent By mawillia Date 2009-02-09 Time 15:36 Rev Time 0.00
Received By mawillia Date 2009-02-09 Time 14:42 Sent To  
Notes
2009-02-09 15:36:01*****DENIED*****
  
 THE FOLLOWING COMMENTS (NOT MARKED OK) TAKEN FROM THE
 PREVIOUS FIRE REVIEW STILL NEED TO BE ADDRESSED:
  
 1. LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
 ADD TO CODE ANALYSIS DATA SECTION OF THE SUBMITTED PLAN
  
 2. OK
  
 3. IN ADDITION TO 2A-10BC RATED, "K" RATED FIRE
 EXTINGUISHERIS REQUIRED FOR SMALL GREASE FIRE
 PROTECTION. COULD NOT LOCATE THE "K" EXTINGUISHER ON
 SHEET LS-1 AS INDICATED IN YOUR RESPONSE LETTER
  
 4.
  
 5. OK
  
 6. OK
  
 7. SHEET E.05 INDICATES CARD READERS AND KEYPADS.
 ACCESS CONTROL SYSTEMS SHALL COMPLY WITH NFPA 101,
 SEC.7.2.1.6.2. ADD COMMENT TO THE APPROPIATE PLAN SHEET
  
 8. OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 13:19 Rev Time 0.00
Received By mwennerg Date 2008-10-23 Time 13:19 Sent To  
Notes
2008-10-23 13:30:04***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) RAMPS TO COMPLY WITH 101, SEC. 7.2.5. PROVIDE
 PRESCRIPTIVE STRENGTH REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 3) IN ADDITION TO 2A-10 B,C RATED, "K" RATED FIRE
 EXTINGUISHER IS REQUIRED IN KITCHEN FOR SMALL GREASE
 FIRE PROTECTION.
  
 4) IT DOES NOT APPEAR THAT ENOUGH AUDIBLE FIRE ALARM
 EQUIPMENT IS ILLUSTRATED IN KITCHEN AND SURROUNDING
 AREA.
  
 5) IS THE KITCHEN AREA CONSIDERED A SEPARATE STRUCTURE
 AS A RESULT OF THE EXISTING (4) HOUR RATED FIRE WALL?
  
 6) HOOD/SUPPRESSION SYSTEM TO COMPLY WITH THE
 REQUIREMENTS OF NFPA 96 AND SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM. SEPARATE SHOP DRAWINGS AND
 PERMITS ARE REQUIRED FOR HOOD/SUPPRESSION SYSTEM.
  
 7) SHEET E.05 INDICATES CARD READERS. ACCESS CONTROL
 SYSTEMS SHALL COMPLY WITH 101, SEC. 7.2.1.6.2. SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO INSTALLATION
 OF EQUIPMENT.
  
 8) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-08-27 Cont ID  
Sent By kstevens Date 2009-08-27 Time 16:53 Rev Time 0.00
Received By kstevens Date 2009-08-27 Time 16:53 Sent To  
Notes
2009-08-27 16:54:52PASSED/PROVISO:
  
 REVISION REQUIRED SHOWING THE CORRECT PIPE SIZES ON THE
 GAS RISER DIAGRAM.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 16:18 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 16:18 Sent To  
Notes
2009-01-28 16:36:08DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. OK
 B. OK
 C. OK
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT DELEVERY PRESSURE IS NOT
 INDICATED.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE GAS
 WATER HEATER HAVE NOT BEEN SUBMITTED.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE, NOTED, BUT THE MANUAL SHUT OFF VALVE AND
 THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE
 EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER
 HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL?
 PLEASE CLARIFY.
  
 2. OK
 3. OK
 4. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-01-28 Cont ID  
Sent By kstevens Date 2008-09-22 Time 16:16 Rev Time 0.00
Received By kstevens Date 2008-09-22 Time 16:15 Sent To  
Notes
2009-01-28 16:18:00DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 2. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES
 NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE
 RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES
 ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 &
 402.
  
 3. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION
 OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS
 408.2 & 408.4.
  
 4. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING
 BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61B15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-19 Cont ID  
Sent By dpalmer Date 2009-10-19 Time 16:12 Rev Time 0.00
Received By dpalmer Date 2009-10-19 Time 16:12 Sent To  
Notes
2009-10-19 16:12:47TO C27

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 08:21 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 08:21 Sent To  
Notes
2009-08-27 08:23:05C-5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2008-12-23 Time   Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 16:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-23 Cont ID  
Sent By mwennerg Date 2008-10-23 Time 13:35 Rev Time 0.00
Received By mwennerg Date 2008-09-19 Time 09:19 Sent To  
Notes
2008-09-19 09:19:34TO "COMM" BD#53

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-09-04 Cont ID  
Sent By rkussner Date 2009-09-04 Time 12:20 Rev Time 0.00
Received By rkussner Date 2009-09-04 Time 12:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-09 Cont ID  
Sent By rregueir Date 2009-09-09 Time 11:09 Rev Time 0.00
Received By rregueir Date 2009-09-09 Time 10:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 13:05 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 11:44 Sent To  
Notes
2009-02-01 13:05:17REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE SYMBOL LEGEND PROVIDES NO SYMBOL TO BE USED FOR
 FIRE DAMPERS. THE INDICATION IS THAT FIRE DAMPERS ARE
 TO BE IDENTIFIED WITH "FD" BUT THERE ARE NO LOCATIONS
 INDICATED BY USING THIS DESIGNATION ON FLOOR PLANS.
 PLEASE SHOW ON PLANS WHERE EACH FIRE DAMPER IS LOCATED
 WITH THE USE OF A CLEARLY IDENTIFIED AND RECOGNIZABLE
 SYMBOL OR INDICATOR IN ACCORDANCE WITH FBCM 607.8 AND
 FBCB 106.1.1.
  
 2 THROUGH 9: OK
  
 10. DESIGNER???S RESPONSE INDICATES THERE IS A CONCERN
 REGARDING THE LACK OF A RETURN AIR INTAKE IN THE
 KITCHEN FOR WHEN THE EXHAUST FAN IS NOT RUNNING. IF
 BALANCED RETURN CAN NOT BE ACHIEVED WITH THIS
 CONFIGURATION (AS REQUIRED IN ACCORDANCE WITH FBCM
 601.4) THEN IT IS THE DESIGNER???S RESPONSIBILITY TO
 DESIGN A SYSTEM WHICH MEETS DESIGN REQUIREMENTS IN A
 CODE COMPLIANT MANNER. SOME SUGGESTED OPTIONS ARE:
 DESIGNING A RETURN FOR THIS AREA WITH A MOTORIZED OR
 BAROMETRIC DAMPER THAT WILL OPEN WHEN THE KITCHEN
 EXHAUST IS NOT OPERATIONAL. THERE MAY BE OTHER OPTIONS
 AVAILABLE AT THE DESIGNER???S DISCRETION. PLEASE CALL
 TO DISCUSS IF NECESSARY.
  
 11. OK
  
 12. NOTE ON FLOOR PLAN CLAIMS DUCTS OF 100 SQ. IN. OR
 LESS DO NOT REQUIRE FIRE DAMPERS. NO SUCH EXCEPTION
 COULD BE FOUND IN THE CODE. THERE IS A SIX-PART
 EXCEPTION FOR FIRE DAMPERS IN FIRE PARTITIONS (SEE FBCM
 607.5.3 EXCEPTION #2), BUT ALL SIX CONDITIONS MUST BE
 MET TO UTILIZE THE EXCEPTION. ALSO, FLOOR PLAN SHOWS
 FLEX DUCTS PENETRATING A WALL IDENTIFIED AS FIRE RATED
 ON ARCHITECTURAL PLANS. FLEXIBLE DUCTS AND AIR
 CONNECTORS SHALL NOT PASS THROUGH ANY
 FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH FBCM
 607.7. IN ANY CASE, DUCTS PENETRATING FIRE RATED
 ASSEMBLIES SHALL BE PROTECTED WITH FIRE DAMPERS OR A
 THROUGH-PENETRATION FIRESTOP SYSTEM IN ACCORDANCE WITH
 FBCM 607.1.1. IF AN EXCEPTION TO THE REQUIREMENT FOR
 FIRE DAMPERS IN DUCTS, PLEASE SEE EXCEPTION #1 UNDER
 FBCM 607.5.3 IF THIS IS A FULLY SPRINKLERED BUILDING.
  
 13 THROUGH 15: OK
  
 16. NOTE ???I??? ON M.02 IS IN CONFLICT WITH THE NOTE
 ON M.04 REGARDING DAMPER OPERATION. PLEASE COORDINATE
 NOTES SHOWING COMPLIANCE WITH FBCM 508.1.
  
 17. DETAIL FOR FAN COIL UNIT NOW SHOWS A DUCT DETECTOR
 ON THE SUPPLY AS REQUIRED BY FBCM 606.2.1. HOWEVER,
 DETAIL #15 ON PAGE M.05 SHOWS THE DUCT DETECTOR
 INSTALLED ON THE RETURN. PLEASE CORRECT.
  
 NEW COMMENTS BASED ON NEW INFORMATION AND?OR DETAILS
 PROVIDED:
  
 18. CONDENSATE DETAIL #8 ON PAGE M.05 CALLS FOR AN
 AUXILIARY DRAIN FROM AN AUXILIARY DRAIN PAN TO BE
 ROUTED TO THE "NEAREST WET COLUMN." THIS DOES NOT
 CORRESPOND WITH THE REQUIREMENTS FOR AUXILIARY DRAIN
 PROTECTION UNDER FBCM 607.2.3. PLEASE SHOW A MEANS OF
 AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH THIS
 SECTION.
 NOTE: THE DETAIL CALLS FOR A FLOAT SWITCH IN THE
 AUXILIARY DRAIN PAN. THIS WOULD BE COMPLIANT WITH NO
 AUXILIARY DRAIN LINE INSTALLED ON THE PAN.
  
 19. DETAIL #6 ON M.05 SHOWS A LOUVER INSTALLATION.
 LOUVERS ARE DEFINED AS PANEL WALLS PER FAC RULE 9B-72
 AND ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL SYSTEM.
 PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR THE SPECIFIC
 LOUVERS TO BE INSTALLED WITH INSTALLATION INSTRUCTIONS.
  
 20. ENERGY CALCULATIONS ARE NOT SIGNED AND SEALED BY
 THE DESIGNER OF RECORD AND/OR OWNER-AGENT AS REQUIRED
 BY FBCB 13-103.1.1 AND 13-103.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By rregueir Date 2008-09-30 Time 16:53 Rev Time 0.00
Received By rregueir Date 2008-09-29 Time 14:26 Sent To  
Notes
2008-09-30 16:53:27REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE A.02: THERE ARE SEVERAL SYMBOLS ON THE
 REFLECTIVE CEILING PLAN WHICH DO NOT APPEAR ON THE
 SYMBOL LEGEND. PLEASE PROVIDE CLARIFICATION AND
 IDENTIFICATION OF EACH ITEM TO BE INSTALLED IN THE
 CEILING. THIS CEILING SPACE IS TO SERVE AS A RETURN AIR
 PLENUM AND ALL ITEMS IN THIS PLENUM MUST BE IDENTIFIED
 TO DEMONSTRATE COMPLIANCE WITH FBCM 602.2.
  
 2. PAGE A.02: NOTE ON THIS PAGE INDICATES R-19
 INSULATION TO BE INSTALLED ABOVE THE CEILING. THIS
 CEILING SERVES AS A PLENUM AND THEREFORE THE INSULATION
 AND THERMAL BARRIER MUST BE ABOVE THE PLENUM SPACE.
 CAVITIES BENEATH A ROOF DECK WHICH WILL BE USED AS
 SUPPLY OR RETURN PLENUMS SHALL HAVE AN INSULATED ROOF.
 THE INSULATION SHALL HAVE AN R-VALUE OF AT LEAST R-19
 IN ACCORDANCE WITH FBCB 13-404.1.ABC.2. ALSO, ROOF
 INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED
 CEILING WITH REMOVABLE CEILING PANELS IN ACCORDANCE
 WITH FBCB 13-404.1.ABC.1.
  
 3. KITCHEN EXHAUST SYSTEM: THERE IS NOT ENOUGH
 INFORMATION PROVIDED WITH THIS SUBMITTAL TO DO A
 THOROUGH REVIEW OF THE COMMERCIAL KITCHEN GREASE
 EXHAUST SYSTEM. SEPARATE PLANS AND PERMIT APPLICATIONS
 WILL BE REQUIRED FOR THE HOOD AND HOOD SUPPRESSION
 SYSTEMS. HOWEVER, THE FOLLOWING CONDITIONS ARE EVIDENT
 ON THESE PLANS AND SHALL BE ADDRESSED PRIOR TO PERMIT
 ISSUANCE:
  
 4. EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE
 THROUGH EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES,
 VAPORS, AND ODORS IN THE DISCHARGE FROM SUCH
 TERMINATIONS DO NOT CREATE A PUBLIC NUISANCE OR A FIRE
 HAZARD IN ACCORDANCE WITH FBCM 506.3.12.2. SINCE THIS
 FAN DOES NOT APPEAR TO BE IN A LOCATION ACCESSIBLE TO
 THE PUBLIC, FIRE HAZARD IS THE PRIMARY CONCERN HERE,
 ALTHOUGH GREASE ACCUMULATION ON WALKING SURFACES MAY
 ALSO CREATE A HAZARD.
  
 5. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10
 FEET ABOVE THE ADJOINING GRADE LEVEL IN ACCORDANCE WITH
 FBCM 506.3.12.3. BASED ON THE HEIGHT OF THE BALCONY
 ABOVE IT DOES NOT APPEAR FEASIBLE TO INSTALL A FAN
 WHERE THE BOTTOM OF THE FAN WILL BE A MINIMUM OF 10
 FEET ABOVE GRADE.
  
 6. EXHAUST FANS SHALL BE POSITIONED SO THAT THE
 DISCHARGE WILL NOT IMPINGE ON THE ROOF, OTHER EQUIPMENT
 OR APPLIANCES OR PARTS OF THE STRUCTURE IN ACCORDANCE
 WITH FBCM 506.5.2. THE LOCATION OF THE FAN AS SHOWN ON
 THE PLANS WILL BE DIRECTLY ADJACENT TO THE ROOF/BALCONY
 ABOVE, PROMOTING GREASE ACCUMULATION ON THE STRUCTURE
 AND CREATING A FIRE HAZARD. SEE ALSO COMMENT 3A ABOVE.
  
 7. EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS IN
 ACCORDANCE WITH FBCM 401.5.2.
  
 8. DETAIL #9 ON PAGE M0.5 SHOWS THE KITCHEN EXHAUST
 DUCT SIZED AT 16X20. WITH A VOLUME OF 1930 CFM AS SHOWN
 ON THE EQUIPMENT SCHEDULE, THE VELOCITY OF THE EXHAUST
 AIR WITHIN THE GREASE DUCT WILL BE APPROXIMATELY 869
 FPM. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE
 DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY
 WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER
 MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE IN
 ACCORDANCE WITH FBCM 506.3.4.
  
 9. THE AIR BALANCE SCHEDULE DOES NOT CORRESPOND WITH
 THE INFORMATION ON FLOOR PLANS AND SCHEDULES. EXAMPLE:
 THERE IS NO INFORMATION ON THE PLANS REGARDING THE BATH
 EXHAUST, UTILITY EXHAUST OR WATER HEATER EXHAUST. THESE
 APPLIANCES SHALL BE LISTED IN THE EQUIPMENT SCHEDULE IN
 ACCORDANCE WITH FBCB 106.3.5 AND FBCM 301.1.
  
 10. THE REFLECTIVE CEILING PLAN SHOWS A RETURN AIR
 GRILL IN THE KITCHEN ADJACENT TO THE KITCHEN HOOD. AS
 THIS UNIT PROVIDES AIR FOR STORAGE, OFFICE AND RESTROOM
 SPACES, IT IS NOT DEDICATED TO THE KITCHEN AREA
 EXCLUSIVELY. RETURN AIR INTAKE SHALL BE PROHIBITED IN
 NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH
 FBCM 407.1.
  
 11. PAGE M0.4 FLOOR PLAN SHOWS CEILING MOUNTED EXHAUST
 FANS IN BATHROOM AND UTILITY ROOM. PLAN ALSO INDICATES
 A POWER VENT TYPE SYSTEM FOR THE WATER HEATER. THESE
 SYSTEMS CAN NOT BE INSTALLED IN A RETURN AIR PLENUM
 CEILING. EXHAUST DUCTS UNDER POSITIVE PRESSURE,
 CHIMNEYS, AND VENTS SHALL NOT EXTEND INTO OR PASS
 THROUGH PLENUMS IN ACCORDANCE WITH FBCM 601.3.
  
 12. PLEASE IDENTIFY ON PLANS THE LOCATION OF EACH FIRE
 DAMPER AT EACH DUCT PENETRATION OR TRANSFER OPENING.
 THE SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH
 FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER SHALL BE
 SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING PLANS BY
 THE DESIGNER IN ACCORDANCE WITH FBCM 607.8.
  
 13. MECHANICAL PLAN INDICATES GAS WATER HEATER IN THE
 UTILITY ROOM WITH POWER VENT. PLUMBING AND
 ARCHITECTURAL PLANS SHOW THIS WATER HEATER IN THE
 MECHANICAL ROOM WHICH SERVES AS A RETURN AIR PLENUM.
 WHICH IS CORRECT? COMBUSTION WATER HEATERS AND
 ATMOSPHERIC COMBUSTION FURNACES SHALL NOT BE LOCATED IN
 MECHANICAL CLOSETS USED AS RETURN AIR PLENUMS IN
 ACCORDANCE WITH FBCM 603.9.
  
 14. PLEASE INDICATE ON PLANS THE TYPE OF WALL FINISHES
 TO BE USED ON THE TYPE 1 AND TYPE 2 WALLS AT THE
 MECHANICAL ROOM. THE WALL SCHEDULE INDICATES THE TYPE 1
 WALLS FINISHED ON 1 SIDE AND THE TYPE 2 WALLS WITH NO
 FINISH. THIS ROOM IS BEING USED AS A PLENUM. THE PLENUM
 SHALL BE LINED WITH AN APPROVED AIR BARRIER AND
 INSULATED IN ACCORDANCE WITH FBCM 607.8, 607.9 AND FBCB
 TABLE 13-410.1.ABC.2.2. SEE FBCM 603.9.1 FOR A LIST OF
 APPROVED AIR BARRIERS.
  
 15. COOLING LOAD CALCULATIONS: THESE CALCULATIONS
 INDICATE TOTAL OUTSIDE AIR OF 400 CFM WHILE THE PLANS
 INDICATE THAT A MINIMUM OF 1930 CFM IS REQUIRED FOR
 KITCHEN EXHAUST MAKEUP AIR. PLEASE CLARIFY. ALSO, PAGE
 A0.1 INDICATES REMOTE CONDENSERS FOR THE REFRIGERATORS
 AND FREEZERS ARE TO BE LOCATED IN THE CLOSET. THESE ARE
 HEAT PRODUCING APPLIANCES. ARE THEY ACCOUNTED FOR IN
 THE CALCULATIONS? ARE THESE CONDENSERS APPROVED FOR
 INSTALLATION IN A PLENUM? SEE FBCB 13-407.1.ABC.1 AND
 FBCM 602.2.
  
 16. NOTE I ON FAN COIL SCHEDULE INDICATES THAT THE OA
 DAMPER IS ONLY TO BE OPEN DURING OCCUPIED HOURS AS SET
 BY THE BAS. THIS DAMPER, AND THE RELATED FAN COIL UNIT
 SHALL BE INTERLOCKED WITH THE KITCHEN HOOD EXHAUST
 SYSTEM TO ENSURE THAT THE DAMPER IS OPEN AND THE FAN
 COIL IS OPERATING DURING ALL COOKING OPERATIONS,
 REGARDLESS OF THE SETTINGS OF THE BAS. FOR MECHANICAL
 MAKEUP AIR SYSTEMS, THE EXHAUST AND MAKEUP AIR SYSTEMS
 SHALL BE ELECTRICALLY INTERLOCKED TO ENSURE THAT MAKEUP
 AIR IS PROVIDED WHENEVER THE EXHAUST SYSTEM IS IN
 OPERATION IN ACCORDANCE WITH FBCM 508.1.
  
 17. THERE IS NO INDICATION ON MECHANICAL OR ELECTRICAL
 PLANS THAT THERE IS A DUCT SMOKE DETECTOR INSTALLED ON
 THE FAN COIL UNIT. FAN SHUT DOWN BY SMOKE DETECTOR IS
 REQUIRED IN ACCORDANCE WITH FBCM 606.2. DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBCM 606.4.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A
 DESCRIPTION OF HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE RELEVANT INFORMATION CAN BE FOUND. THIS WILL ASSIST
 IN FACILITATING A TIMELY REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-08-27 Cont ID  
Sent By kstevens Date 2009-08-27 Time 16:55 Rev Time 0.00
Received By kstevens Date 2009-08-27 Time 16:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-01-28 Cont ID  
Sent By kstevens Date 2009-01-28 Time 16:36 Rev Time 0.00
Received By kstevens Date 2009-01-28 Time 16:36 Sent To  
Notes
2009-01-28 16:46:10DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. OK
 B. OK
 C. OK
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, PRESSURE NOT INDICATED.
  
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT MANUF SHEETS FOR THE WATER
 HEATER NOT SUBMITTED.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND
 THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE
 EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER
 HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL?
 PLEASE CLARIFY.
  
 8. OK
 9. OK
 10. OK
  
 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 604.
 ****RESPONSE NOTED. BUT THE PIPING TO THE P-6 SINK
 STILL DOES NOT REFLECT THE FLOOR PLAN AS INDICATED.
 PLEASE CORRELATE. ALSO THE WATER HAMMER ARRESTORS SHALL
 BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201.
  
 12. OK
 13. OK
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX
 (561) 659-7458 - E-MAIL [email protected]. ARTICLE III
 SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON
 INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT.
 ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR A 1250
 GAL INTERCEPTOR AND THE PLANS SHOW A 750 GAL
 INTERCEPTOR. PLEASE SHOW REQUIRED SIZE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-22 Cont ID  
Sent By kstevens Date 2008-09-22 Time 14:23 Rev Time 0.00
Received By kstevens Date 2008-09-19 Time 15:59 Sent To  
Notes
2008-09-22 15:31:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS ARE REVIEWED UNDER THE ADOPTED CODES WHICH ARE
 THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE CODES
 THE WORK IS DESIGNED UNDER ON THE PLANS. SECTION
 106.1.1.
  
 2. SHT A.01 FLOOR PLAN SHOWS A KITCHEN WITH PANTRY, A
 TOILET ROOM, AN OFFICE, A MECHANICAL ROOM AND UPPER
 LEVEL WORK AS WELL AS A COVERED PARKING STRUCTURE. THE
 APPLICATION INDICATES A KITCHEN ADDITION & A COVERED
 PARKING STRUCTURE. PER APPLICATION, PLEASE DESCRIBE THE
 PROJECT IN DETAIL. INDICATE ALL WORK TO BE DONE UNDER
 THIS PERMIT. SECTIONS 105.1 & 105.3.
  
 3. SHT A.04 COLUMN LINE 37 INDICATES A RAIN WATER
 LEADER IN THE COLUMN. IS THIS A NEW RWL? IF SO PLEASE
 INDICATE WHERE IT TERMINATES, THE SIZE OF THE RWL, AND
 FROM WHERE DOES THE RWL ORIGINATE. SECTIONS 106.1.2,
 1106 & 1107.
  
 4. SHT A.05 SHOW COMPLIANCE WITH SECTIONS 11-4.16.5
 FLUSH CONTROLS, 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED
 PIPES & SURFACES & 11-4.19.5 FAUCETS.
  
 5. SHT P.01 THE LOCATION OF THE GAS WATER HEATER DOES
 NOT CORRELATE WITH THE LOCATION OF THE WATER HEATER
 SHOWN ON THE FLOOR PLAN ON SHT A.01, NOR DOES THE GAS
 PIPING SHOWN ON THE FLOOR PLAN & GAS RISER REFLECT THE
 LOCATION OF THE WATER HEATER ON EITHER SHEET. PLEASE
 CORRELATE & CLARIFY. SECTIONS 106.1.1 & 402.
  
 6. SHT P.01 FLOOR PLAN AND PLUMBING RISER. THE DISH
 WASHERS SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT
 THE GREASE SYSTEM. MUNICIPAL CODE, ARTICLE III SECTION
 90-124(7)(B).
  
 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. LENGHTS NOT SHOWN.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000.
  
 C. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. FOR WATER HEATER.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 8. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES
 NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE
 RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES
 ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 &
 402.
  
 9. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION
 OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS
 408.2 & 408.4.
  
 10. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING
 BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61B15-23.002(2) & FS 471.025.
  
 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 604.
  
 12. SHT P.02 WATER HEATER DETAIL. A VACUUM RELIEF VALVE
 IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS PER
 SECTION 504.2. -- THE P/T RELIEF VALVE SHALL BE
 INSTALLED IN THE SHELL OF THE WATER HEATER TAN, PER
 SECTION 504.4.1. -- THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION SECTION 607.3.2. PLEASE INDICATE
 METHOD.
  
 13. SHT P.03 A VACUUM BREAKER IS REQUIRED ON THE HOSE
 BIBB INDICATED ON THE CAN WASH DETAIL. SECTION
 608.15.4.2.
  
 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT
 MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX
 (561) 659-7458 - E-MAIL [email protected]. ARTICLE III
 SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON
 INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-10-26 Cont ID  
Sent By eschneid Date 2009-10-26 Time 17:09 Rev Time 0.50
Received By eschneid Date 2009-10-26 Time 17:09 Sent To  
Notes
2009-10-26 17:12:10PASSED W/PROVISOS
  
 1) THE POSTS/BOLLARDS SHOWN INSIDE THE DUMPSTER
 ENCLOSURE ARE NOT ALLOWED
  
 2) SHEETS PA.01 THROUGH PA.03 SHALL BE USED FOR THE
 PARKING SPACES AND THE COVERED PARKING STRUCTURE ONLY.
 THE SHEET SP.1 AND LANDSCAPE PLANS SHALL GOVERN SITE
 WORK OUTSIDE OF THE COVERED PARKING STRUCTURE.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2009-09-04 Cont ID  
Sent By eschneid Date 2009-09-04 Time 11:34 Rev Time 0.50
Received By eschneid Date 2009-09-04 Time 11:34 Sent To  
Notes
2009-09-04 11:56:56FAILED
  
 1) SHEET C.03 MISSING FROM ONE SET OF PLANS.
  
 2) WHEEL STOP DETAILS ON SHEETS SP.01 AND C.03 ARE NOT
 THE SAME.
  
 3) SHEET C.02 DOES NOT MATCH APPROVED SITE PLAN LAYOUT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-01-02 Cont ID  
Sent By eschneid Date 2009-01-02 Time 10:34 Rev Time 0.50
Received By eschneid Date 2009-01-02 Time 10:34 Sent To  
Notes
2009-01-02 10:45:54FAILED
  
 PROVIDE RESPONSES IN WRITING:
  
 1) AS STATED IN THE 1ST REVIEW, THIS PERMIT REQUIRES A
 MINOR PD AMENDMENT AND FORMAL SITE PLAN APPROVAL PRIOR
 TO ZONING PASSING THE PERMIT. NEITHER OF THESE HAVE
 BEEN GRANTED.
  
 2) ZONING COMMENTS:
  
 A. PARKING DETAILS MEETING CITY OF WEST PALM BEACH
 STANDARDS ARE REQUIRED ON THE PLANS. SPECIFIC ISSUE -
 WHEEL STOP LOCATION NOT TWO (2) FEET FROM THE HEAD OF
 THE SPACE. NOTE THE DETAIL DIMENSIONS DO NOT MATCH THE
 DIMENSIONS ON THE PLAN.
 B. THE NEW DUMPSTER ENCLOSURE SHOW ON THE PLANS DOES
 NOT MEET CITY SIZE OR LANDSCAPE STANDARDS. NOTE THE
 DETAIL DIMENSIONS DO NOT MATCH THE DIMENSIONS ON THE
 PLAN.
 C. D-TYPE CURBING SHALL BE USED TO PROTECT THE
 LANDSCAPE AREAS FROM VEHICULAR ENCROACHMENT ALONG THE
 DRIVE AISLES. THIS IS NOT INDICATED ON THE PLANS.
 D. THE SITE AND THE LANDSCAPE PLANS DO NOT MATCH.
 SPECIFICALLY IN THE NORTHWEST CORNER OF THE LIMITS OF
 WORK.
 E. THE AMERICANS WITH DISABILITIES ACT (ADA) REQUIRES
 THAT IF COVERED PARKING IS PROVIDED, THEN COVERED ADA
 PARKING SHALL BE PROVIDED AS WELL. EITHER SHOW WHERE
 THERE CURRENTLY EXISTS COVERED ADA PARKING ON THE
 CHRISTIAN CONVENTION CENTER CAMPUS, OR PROVIDE A
 COVERED ADA SPACE IN THE NEW COVERED PARKING AREA. IF
 ADA SPACE IS REQUIRED, THE DETAILS SHALL BE PROVIDED.
 F. WHAT ARE THE DOTS SHOWN IN THE DRIVE AISLE? ARE
 THESE COLUMNS OR STRAY MARKS. COLUMNS ARE NOT ALLOWED,
 STRAY MARKS SHALL BE REMOVED.
  
 3) LANDSCAPE COMMENTS:
  
 A. SHEETS LA.01 AND SP.01 WITH THE LATEST REVISION DATE
 OF 10/31/08 ARE INCONSISTENT. THERE IS AN APPARENT
 WALKWAY SHOWN ON ONE PLAN AND A RETAINING WALL ON THE
 OTHER.
 B. SHEET LA.01 THAT WAS SUBMITTED WITH THE ?TREE
 ALTERATION PERMIT? IS DIFFERENT FROM SHEET LA.01 THAT
 WAS MOST RECENTLY SUBMITTED AND YET SHARES THE SAME
 REVISION DATE. THERE WERE TWO (2) ALEXANDER PALMS SHOWN
 ON THE TREE ALTERATION PERMIT SET THAT WERE TO BE
 RELOCATED AND THEN REPLANTED AFTER CONSTRUCTION. THESE
 TWO (2) PALMS WERE NOT SHOWN ON THE MOST RECENT
 SUBMITTAL AND THREE (3) UNIDENTIFIED UNDERSTORY TREES
 WERE SHOWN. A PALM PLANTING DETAIL SHOWN ON THE
 ORIGINAL SET OF PLANS WAS MISSING FROM THE MOST RECENT
 SET.
 C. PURSUANT TO SECTION 94-444(B), WALLS OF THE DUMPSTER
 ENCLOSURE SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO FOOT INTERVALS. A HEDGE WAS SHOWN ON
 ONLY ONE SIDE OF THE PROPOSED ENCLOSURE. IT IS REQUIRED
 ON THREE (3) SIDES.
 D. ALL PROPOSED LIGHTING SHALL BE SHOWN ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS.
 E. PURSUANT TO SECTION 94-442(G), IN KEEPING WITH
 XERISCAPE GUIDELINES, THE PALMS THAT SURROUND THE PLAZA
 SHOULD BE UNDER PLANTED AND CONTAINED WITHIN A PLANT
 BED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By adavila Date 2008-09-23 Time 13:46 Rev Time 0.00
Received By adavila Date 2008-09-23 Time 13:46 Sent To  
Notes
2008-09-23 13:52:04PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. APPROVAL OF A MINOR PD AMENDMENT TO THE WEST PALM
 BEACH CHRISTIAN CONVENTION CENTER COMMUNITY SERVICE
 PLANNED DEVELOPMENT (CSPD), AND OF A FORMAL SITE PLAN
 REVIEW ARE REQUIRED FOR THE PROPOSED ADDITION AND SITE
 WORK PRIOR TO OBTAINING A BUILDING PERMIT. AN
 APPLICATION SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING DEPARTMENT. THE APPLICATION MAY BE OBTAINED FROM
 THE PLANNING AND ZONING DEPARTMENT'S WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  