Plan Review Details - Permit 08090412
Plan Review Stops For Permit 08090412 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2009-10-22 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-10-22 |
Time |
14:59 |
Rev Time |
5.00 |
Received By |
jwitmer |
Date |
2009-10-22 |
Time |
08:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2009-09-02 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-09-02 |
Time |
15:59 |
Rev Time |
2.00 |
Received By |
jwitmer |
Date |
2009-09-02 |
Time |
14:09 |
Sent To |
|
|
Notes |
2009-09-02 16:51:54 | BUILDING PLAN REVIEW | | PERMIT: 08090412 | | ADD: 1610 PALM BEACH LAKES | | CONT: CFR COASTAL | | TEL: (954) 868-9692 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | WEDNESDAY SEPTEMBER 02/2009 | | 3RD REVIEW | | ACTION: DENIED | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS, | | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL | | REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD | | BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE | | REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004 | | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE | | CODE. | | | | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER | | BUILDING DATA DOES NOT PROVIDE AS TO WHAT CODE (YEAR) | | THIS PROJECT WAS DESIGNED. | | | | 1E) PLEASE CORRECT. STRUCTURAL SHEET S.02 ALSO NEEDS TO | | BE UPDATED TO THE 2007 SUPPLEMENTS CURRENTLY READS 2006 | | SUPPLEMENTS.. | | | | 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING | | INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE | | 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING | | INFORMATION IN REGUARDS TO THE 2004 FBC: | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) TYPE OF OCCUPANCY, SHEET SP.01 INDICATE A A2 | | OCCUPANCY, SECTION 303.1 INDICATES AN A2 OCCUPANCY IS | | RESTARAUNT, NIGHTCLUBS, BANQUET HALL, BARS AND | | NIGHTCLUBS PLEASE SEE A3 OCCUPANCY OF COMMUNITY HALLS, | | CHURCHES &AND COURT ROOMS, PLEASE REVISE. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, | | CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE | | THIS TO BE A TYPE V-B / A-3 ASSEMBLY WITH 115373 SQ FT | | A TYPE V-B BUILDING WITH AREA INCREASESAND SPRINKLER | | THE MAXIMUM IS 28,500 SQ FT.. PLEASE CORRECT. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | H) SP.01- REFRENCES A 4 HR FIRE SEPERATION WALL WITH 3 | | HR OPENING PROTECTIVES IS THIS AN ADDITION OR IS THIS A | | TRUE 4 HR FIRE WALL CREATING 2 SEPERATE BUILDINGS? I | | BELIEVE THE ELECTRICAL PLAN REVIEWERR HAD BROUGHT UP | | MANY PROBLEMS IN THE ELECTRICAL DESIGN IF THIS WAS TO | | BE CONSIDERED A SEPERATE BUILDING? | | . | | 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S. | | S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING | | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | 500 PERSONS. | | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR | | AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 | | W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR | | THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY | | FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM | | INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD | | MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT | | (561)805-6666 FOR FURTHER INFORMATION | | BEFORE THE PERMIT MAY BE ISSUED. | | | | 2C) COMPLIED. | | | | 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS | | REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR | | WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR | | RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE | | 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN | | THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY | | SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING | | AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING | | BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE. | | LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK | | INTO THE BUILDING, PLEASE PROVIDE RATIONAL . | | | | 3B) COMPLIED. | | | | 3C) COMMENT 3A) COVERS THIS OPENING. | | | | 4) BUILDING PROVISO: | | 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | OF THE FINAL INSPECTION. | | | | 5) BUIULDING PROVISO: | | 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL | | FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE | | UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A | | HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE | | WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION | | MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED | | FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER | | AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO | | PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO | | FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION | | MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A | | HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A | | FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A | | LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE | | SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS | | CHAPTER. | | | | 6) COMPLIED. | | | | 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR | | OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS | | FOLLOWS: | | 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 & | | A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE | | OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK. | | | | | | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | 9-15 ) COMPLIED. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2009-01-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2009-01-12 |
Time |
11:28 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2009-01-12 |
Time |
11:28 |
Sent To |
|
|
Notes |
2009-01-12 14:44:50 | BUILDING PLAN REVIEW | | PERMIT: 08090412 | | ADD: 1610 PALM BEACH LAKES | | CONT: CFR COASTAL | | TEL: (954) 868-9692 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | MONDAY JAN.12,2009 | | 2ND REVIEW | | ACTION: DENIED | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS, | | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL | | REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD | | BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE | | REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004 | | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE | | CODE. | | | | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER | | BUILDING DATA DOES NOT PROVIDE AS TO | | WHAT CODE (YEAR) THIS PROJECT WAS DESIGNED. | | | | 1E) SP.01 BUILDING DATA, THE PLANS ALSO NEGLECT TO | | IDENTIFY THE 2004 FBC, EXISTING BUILDING CODE, CHAPTER | | 9 THAT DEALS WITH ADDITIONS, PLEASE CORRECT. STRUCTURAL | | SHEET S.01& S.02 ALSO NEEDS TO BE UPDATED TO THE 2007 | | SUPPLEMENTS. | | | | 1F) 2ND REQUEST, SP.01 CALCULATIONS THE BUILDING | | INFORMATION AND CODE SECTIONS ARE NOT TAKEN FROM THE | | 2004 FBC PLEASE PROVIDE THE FOLLOWING BUILDING | | INFORMATION IN REGUARDS TO THE 2004 FBC: | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) COMPLIED. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, | | CHAPTER 6, & TABLE 601, SP.01 CALCULATIONS INDICATE | | THIS TO BE A TYPE IV OR HEAVY TIMBER STRUCTURE, PLEASE | | CORRECT. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | | | H) SP.01- REFRENCES A TABLE 704.1 FIRE SEPERATION BY | | OCCUPANCY PLEASE UPDATE CODE SECTION THIS IS A 2001 FBC | | REFERENCE. | | . | | 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S. | | S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING | | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | 500 PERSONS. | | 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A | | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON | | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL | | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE | | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE | | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING | | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. | | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO | | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO | | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR | | COMPLIANCE WITH THE PERMITTED DOCUMENTS. | | | | 2B) SUBMIT:SEMI-COMPLIED, SUBMITTED SPECIAL INSPECTOR | | AGREEMENT. THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 | | W.P.B. CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR | | THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY | | FL S S 553.79(5) FLORIDA STATUTES TO THE MINIMUM | | INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN CONRAD | | MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT | | (561)805-6666 FOR FURTHER INFORMATION | | BEFORE THE PERMIT MAY BE ISSUED. | | | | 2C) REQUIRED STATEMENT ON PLANS: THRESHOLD BLDG, W.P.B. | | AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | FLORIDA STATUTE. | | | | 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS | | REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR | | WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR | | RATED OPENING. THERE IS A SECOND SWING DOOR WITHIN THE | | 4 HR RATED WALL AND A NOTE INDICATING ALL DOORS WITHIN | | THE HALLWAY TO BE 45 MINUTE RATED DOORS. THE OCCUPANCY | | SEPERATION INDICATED IN TABLE 302.3.2 A 3HR FIRE RATING | | AND 3 HR OPENING PROTECTIVES TABLE 715.3. THE EXISTING | | BREAK ROOM DOOR SHOULD READ 3 HR OPENING PROTECTIVE. | | LS.01 ALSO INDICATES AN EXIT LIGHT THAT LEADS YOU BACK | | INTO THE BUILDING, PLEASE PROVIDE RATIONAL . | | | | 3B) COMPLIED. | | | | 3C) COMMENT 3A) COVERS THIS OPENING. | | | | 4) BUILDING PROVISO: | | 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | OF THE FINAL INSPECTION. | | | | 5) BUIULDING PROVISO: | | 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE UNLAWFUL | | FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED MATERIALS | | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR OTHERWISE | | UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. AFTER A | | HURRICANE WATCH HAS BEEN ISSUED UNTIL THE HURRICANE | | WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH CONSTRUCTION | | MATERIALS, EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED | | FROM THE CONSTRUCTION SITE OR SECURED IN SUCH A MANNER | | AS TO MINIMIZE THE DANGER OF SUCH CONSTRUCTION | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING DAMAGE TO | | PERSONS OR PROPERTY FROM HIGH WINDS. ANY PERSONS WHO | | FAILS TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION | | MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A | | HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A | | FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A | | LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE | | SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS | | CHAPTER. | | | | 6) 2ND REQUEST, 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | PROVIDE 2 COPIES, | | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING | | REPORTS, MISSING REPORTS ARE AS FOLLOWS: | | 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 & | | A.06 DETAIL# 1DOES NOT PROVIDE INFORMATION AS TO TYPE | | OF ROOFING ASSEMBLIES TO BE APPLIED TO THE FLAT DECK. | | | | | | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | 9) COMPLIED. | | | | 10) SHEET S.02 NOTE # 5 FOR WIND INFORMATION IS | | MISSING: | | 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | BUILDING: | | 1. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7-02. | | | | 2. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | 3. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | PROFESSIONAL. | | | | 11) 2ND REQUEST, SHEET PA.01 PARKING GARAGE PLEASE | | PROVIDE THE FOLLOWING INFORMATION IN REGUARDS TO THE | | 2004 FBC: | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, | | CHAPTER 6, & TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | | | 12) COMPLIED. | | | | 13-14) COMPLIED. | | | | 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-10-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-10-08 |
Time |
14:28 |
Rev Time |
6.65 |
Received By |
jwitmer |
Date |
2008-10-08 |
Time |
14:28 |
Sent To |
|
|
Notes |
2008-10-08 16:57:18 | BUILDING PLAN REVIEW | | PERMIT: 08090412 | | ADD: 1610 PALM BEACH LAKES | | CONT: CFR COASTAL | | TEL: (954) 868-9692 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW | | ACTION: DENIED | | | | 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | 1B) INFORMATIONAL: PLEASE SUBMIT SURVEYS, PLANS, | | REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | SUBMITTALS FOR REVIEW FOR PERMIT. YOUR PROJECT WILL | | REQUIRE A THRESHLD INSPECTOR BEING A THRESHOLD | | BUILDING, (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE | | REQUIRED FOR PERMIT ISSUANCE. 106.1* / 109.3.6, 2004 | | SUBMITTAL DOCUMENTS WEST PALM BEACH ADMINISTRATIVE | | CODE. | | | | 1C) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 1D) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | BUILDING WITH THE 2007 SUPPLEMENTS.SHEET SP.01 UNDER | | BUILDING DATA DOES NOT PROVIDE AS TO | | WHAT CODE (YEAR) THIS PROJECT WAS DESIGNED. | | | | 1E) SP.01 BUILDING DATA, THE PLANS ALSO NEGLECT TO | | IDENTIFY THE 2004 FBC, EXISTING BUILDING CODE, CHAPTER | | 9 THAT DEALS WITH ADDITIONS, PLEASE CORRECT. STRUCTURAL | | SHEET S.01 ALSO NEEDS TO BE UPDATED TO THE 2007 | | SUPPLEMENTS. | | | | 1F) SP.01 CALCULATIONS THE BUILDING INFORMATION AND | | CODE SECTIONS ARE NOT TAKEN FROM THE 2004 FBC PLEASE | | PROVIDE THE FOLLOWING BUILDING INFORMATION IN REGUARDS | | TO THE 2004 FBC: | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, | | CHAPTER 6, & TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | . | | 2) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD | | BUILDING BY DEFINTION; THRESHOLD INSPECTION PLAN FL S. | | S. 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING | | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, | | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS | | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 | | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN | | 500 PERSONS. | | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | WITH THE PERMITTED DOCUMENTS. | | | | 2B) SUBMIT: THRESHOLD INSPECTOR: WPB AMENDMENT | | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT | | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS | | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE | | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN | | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT | | (561)805-6666 FOR FURTHER INFORMATION | | BEFORE THE PERMIT MAY BE ISSUED. | | | | 2C) REQUIRED STATEMENT ON PLANS: THRESHOLD BLDG, W.P.B. | | AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH | | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT | | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE | | BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE | | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE | | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL | | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 | | FLORIDA STATUTE. | | | | 3A) LS.01 NO BLDG TYPE INFORMATION HAS BEEN PROVIDED AS | | REQUESTED UNDER (1F). THE PLAN INDICATES THE EXTERIROR | | WALL AS A 4 HR FIRE RATED WALL WITH AN OVERHEAD 3 HR | | RATED OPENING. IS THE INTENT TO MAKE | | THIS KITCHEN NOT AN DDITION BUT A SPERATE SINGLE STORY | | BUILDING THAT WOULD NOT MEET THE THRESHOLD | | REQUIREMENTS? | | | | 3B) LS.01 THIS PLAN INDICATES ON THE EXISTING BUILDING | | A PARTIAL BREAK ROOM, AND THE DOOR# 5 FROM THE BREAK | | ROOM INTO THE NEW HALLWAY NOT PART OF A REQUIRED | | EGRESS. SHEET A.01 PROVIDES ENOUGH | | WALLS TO CALCULATE THE AREA OF THE BREAK ROOM AS 827 SQ | | FT/ /15 = 56 AS AN OCCUPANT LOAD. THIS WOULD REQUIRE | | TWO MEANS OF EGRESS PLEASE PROVIDE DETAILS ENOUGH ON | | THE EXISTING BREAK ROOM PROVIDING | | 2 EGRESS PATHS. TABLE 1014.1. | | | | 3C) LS.01 THIS DOOR# 5 IT WOULD ALSO APPEAR TO NEED 3 | | HR OPENING PROTECTION IF THE OVERHEAD DOOR WITHIN THE | | SAME BREAK ROOM REQUIRES IT? ADDITIONAL INFORMATION | | REQUIRED. | | | | 4) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION | | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A | | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF | | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO | | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE | | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS | | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS | | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, | | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE | | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION | | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE | | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY | | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH | | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS | | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, | | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL | | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, | | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING | | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ | | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A | | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED | | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS | | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A | | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE | | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL | | OF THE FINAL INSPECTION. | | | | 5) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE | | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED | | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR | | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. | | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE | | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE | | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN | | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH | | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY | | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE | | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 | | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE | | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO | | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS | | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO | | SECTION 113 OF THIS CHAPTER. | | | | 6) 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | 7) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, | | PROVIDE 2 COPIES, | | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING | | REPORTS, MISSING REPORTS ARE AS FOLLOWS: | | 3A) ROOF DECK OVER THE NEW KITHEN SHEET A.03 DETAIL 2 | | DOES NOT PROVIDE INFORMATION AS TO TYPE OF ROOFING | | ASSEMBLIES. | | 3B) METAL ROOF DECK PARKING GARAGE | | | | 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | 9) A.01 THE KITCHEN EXTERIOR WALLS INDICATE | | WATERPROOFING TO BE APPLIED, PLEASE PROVIDE PRODUCT | | INFORMATION . 1807.3.2.1 & 1807.3.2. | | | | 10) SHEET S.02 NOTE # 5 FOR WIND INFORMATION IS | | MISSING: | | 1603.1.4 WIND DESIGN DATA. | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | BUILDING: | | 1. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7-02. | | | | 2. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | 3. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | SPECIFICALLY DESIGNED BY THE REGISTERED | | DESIGN PROFESSIONAL. | | | | 11) SHEET PA.01 PARKING GARAGE PLEASE PROVIDE THE | | FOLLOWING INFORMATION IN REGUARDS TO THE 2004 FBC: | | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT | | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS | | DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE | | PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED IN TABLE 503, | | CHAPTER 6, & TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE | | BUILDING PERMIT | | | | 12) PA.02 INDICATES RAMPED DRIVE TO BACK UP AGAINST | | BACK WALL OF OPEN PARKING GARAGE, PLEASE PROVIDE | | WATERPROOFING DETAILS 1807.3.2.1 & 1807.3.2. | | | | 13) PA.02 / PS.02 OPEN WALL SECTION INDICATES THE METAL | | DECKING TO BE FASTENED TO METAL TRUSSES PER | | MANUFACTURERS SPEC, PLEASE PROVIDE | | 1609.6.2.2.COMPONENTS AND CLADDING. | | | | 14) PA.02/ PS.02 OPEN WALL SECTION DOES NOT PROVIDE | | METAL HI-HAT CONNECTION TO THE METAL TRUSS, PLEASE | | PROVIDE 1609.2.2 COMPONENTS AND CLADDING. | | | | 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | INFORMATION. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2009-10-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-10-20 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-10-20 |
Time |
09:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2009-09-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-09-15 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-09-15 |
Time |
14:51 |
Sent To |
|
|
Notes |
2009-09-15 14:51:16 | | | | | ** TEMPORARY DENIED PLANS ** | | | | | | 1) NOTE: THIRD SET IS MISSING ES.01. MISSING SHEET MAY | | BE BROUGHT IN. MUST SET UP TIME TO MEET WITH REVIEWER | | AND INSERT SHEETS. | | | | 2) NOTE: PRESCRIPTIVE METHOD C ON PLANS, ALTHOUGH | | METHOD A SUBMITTED IN FLA COM FORM VERSION. EITHER IS | | OK WITH ELECTRICAL HOWEVER MAY NOT USE BOTH. | | PLEASE CONTACT REVIEWER FOR OPTIONS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2009-01-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-01-14 |
Time |
11:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-01-14 |
Time |
11:42 |
Sent To |
|
|
Notes |
2009-01-14 11:42:59 | ** DENIED 2ND REVIEW ** | | | | | | ** UNTIL DATE OF REVIEW THERE WAS NO SPECIFIC CONTACT | | FOR ELECTRICAL. DURING REVIEW A CALL WAS PLACED TO JOHN | | VAUGHAN. ELECTRICAL ENGINEER JAMES MAKO CALLED TO GO | | OVER COMMENTS. | | SEVERAL ITEMS WERE GONE OVER HOWEVER AS THE REVIEW WAS | | NOT COMPLETE AT THE TIME OF THE CONVERSATION A FUTURE | | CALL MAY BE NEEDED ONCE ALL REVIEW NOTES ARE POSTED. | | SOME NOTES FROM PREVIOUS REVIEW WILL REMAIN ALONG WITH | | NEW COMMENTS BASED ON THE DOCUMENTS NOW PLACED ON THE | | PLANS AND SUBMITTED WITH THE DOCUMENTS. | | | | 1) NOTE: PLEASE BE AWARE THAT THE NOTICE OF | | COMMENCEMENT WHICH WAS RECORDED ON SEPTEMBER 15TH, 2008 | | HAS BECOME VOID. PLEASE SEE FS 713.13(2). | | WHEN WORK HAS NOT COMMENCED WITHIN 90DAYS OF RECORDING | | SUCH NOC THE NOC BECOMES VOIDED. THIS WOULD ONLY NEED | | TO BE RE-RECORDED. | | THIS COMMENT IS GIVEN AS INFORMATION ONLY TO HELP | | AVOIDED ANY DELAYS IN THE PERMITTING AND INSPECTION | | PROCESS FOR THE OWNER AND CONTRACTOR. | | | | 2) NOTE: PLEASE SEE FBC 13-101.1, 13-400.0. | | THE PREVIOUS REVIEW REQUESTED LIGHTING PERFORMANCE | | CALCULATIONS IN CONFORMANCE WITH THE FBC CHAPTER 13, | | 13-415.2. | | PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3. | | THE SUBMITTED METHOD *A* MAY BE USED WHEN YOU HAVE A | | WHOLE BUILDING OR AN ADDITION WHICH IS NOT INCLUDING | | ANY RENOVATION TO ANY EXISTING BUILDING AREAS. | | THE METHOD *A* SUBMITTED DOES NOT CONTAIN ANY | | SIGNATURE, OR DATE BY THE RESPONSIBLE DESIGNER. | | MUST CONTAIN THESE PER 13-103.1. PLEASE SEE DESIGNERS | | PERMITTED TO DO THIS UNDER FLORIDA STATUTES 471, 481 | | AND 489. | | THE METHOD *A* SUBMITTED CLEARLY STATES *RENOVATION TO | | EXISTING BUILDING*. IF THIS IS NOT AN ADDITION, OR | | WHOLE BUILDING NEW CONSTRUCTION THEN THIS METHOD MAY | | NOT BE USED. | | IN ANY CASE ALL INFORMATION ON ANY INPUT DATA REPORT | | NEEDS TO COORDINATE WITH ALL INFORMATION ON PLANS. | | THERE ARE SEVERAL ITEMS ON THE IDR AS SUBMITTED WHICH | | ARE EITHER NOT COMPLETE OR THESE ITEMS ARE NOT THE SAME | | AS ON PLANS. | | EXAMPLES: | | THE METHOD OF LIGHTING CONTROLS STATE *MANUAL ON/OFF*. | | THIS IS NOT THE CASE AS ANY NEW PRESCRIPTIVE LIGHTING | | CONTROLS IN A BUILDING GREATER THAN 5K SQ FT SHALL | | COMPLY WITH 13-415.1.ABC.1, .1.1, .1.2, .1.3 AND .1.4. | | SEE THE FOLLOWING COMMENT WITH RESPECT TO LIGHTING | | CONTROLS. | | EXAMPLE: | | THE EXTERIOR LIGHTING ON THE IDR IS COMPLETELY BLANK. | | THIS IS ONE ITEM WHICH THE PLANS CLEARLY CONTAIN | | EXTERIOR LIGHTING YET THERE ARE NO FIXTURES ON THE | | IDR.?? | | THE PLANS INDICATE SPACE BY SPACE FROM TABLE *B*. | | PLEASE SEE 13-415.2.ABC.1 WHICH CLEARLY STATES THAT IS | | NOTE PERMITTED TO USE MORE THAN ONE METHOD. | | THIS REVIEWER IS OK WITH USE OF SPACE BY SPACE FOR | | LIGHTING PERFORMANCE LEVELS HOWEVER WE WOULD STILL NEED | | EXTERIOR PER 13-415.2.ABC.1.3. | | | | | | 3) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND | | .1.4 FOR REQUIRED LIGHTING CONTROLS. | | ALL LIGHTING IN A BUILDING GREATER THAN 5K SQ FT SHALL | | CONTAIN SOME SORT OF AUTOMATED CONTROLS SO WHEN THE | | BUILDING IS NOT OCCUPIED THE LIGHTING. THERE ARE | | COUNTLESS ARTICLES ON THE ENERGY CODE IN THE STATE OF | | FLORIDA AS WELL AS THE REQUIREMENTS NATIONALLY IN THE | | IECC. | | THE FEDERAL CHANGES IN JULY OF 2004 IN THE INTEREST OF | | ENERGY CONSERVATION REQUIRED ALL STATES BY THEIR | | FOLLOWING CODE CYCLE TO ADOPT THE 1999 ASHAE 90.1 OR | | BETTER. SINCE OCTOBER 1ST, 2005 THE 2004 FBC HAS | | REQUIRED THIS. THIS HAS BEEN IN THE CODE FOR OVER 3 AND | | HALF YEARS. THERE HAVE ALSO BEEN SEVERAL REVISIONS TO | | THE 2004 FBC SINCE ADOPTED IN OCT.2005 | | THE RESPONSE LETTER CONTAINS RESPONSES TO ALL OTHER | | COMMENTS WITH THE EXCEPTION OF THIS PREVIOUS COMMENT. | | THE RESPONSE IS BLANK? | | ** PLEASE CALL TO GO OVER IF NEEDED. THIS IS NOT A | | SEPARATE BUILDING BY DEFINITION SMALLER THAN 5K SQ FT. | | THE SWITCHING SHOWN ON PLANS IS DONE BY STANDARD SINGLE | | POLE SWITCHES ALONG WITH STANDARD 3-WAY SWITCHES. THE | | INFORMATION ON SHEET E.04.11 IS NOT ENOUGH FOR | | COMPLIANCE. THE KITCHEN IS NOT AN AREA WHICH IS EXEMPT | | PER THE FBC. PLEASE CALL TO GO OVER. THERE ARE | | SUBSTANTIAL DIFFERENCES IN MOTION SENSORS COMPARED TO | | DUAL TECHNOLOGY DEVICES AND ALSO THESE SAME TYPE OF | | DEVICES USED FOR EGRESS WHICH WOULD BE FAIL SAFE | | OPERATION. | | | | 4) NOTE: PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO | | FBC 11-4.28.1, .2 AND .3 FOR ALL DEVICES FOR FA SYSTEM | | TO COMPLY WITH MINIMUM LEVELS, HEIGHTS ETC FOR ADA | | COMPLIANCE. | | THE RESPONSE MENTIONS TO SEE REVISED PLANS HOWEVER THE | | FA SHEET E.06 DOES NOT INDICATE THE MINIMUM LEVELS FOR | | STROBES AND SOUNDING DEVICES. | | PLEASE ALSO SEE THERE ARE SEVERAL NOTES WHICH THERE | | SEEMS TO HAVE BEEN SOME SORT OF MISHAP WITH THE | | PRINTING. SEE NOTES 17 UNDER FIRE ALARM NOTES, NOTES | | UNDER SEQUENCE OF OPERATION, NOTES UNDER THE SYMBOL | | LEGENDS WHICH HAS NOTES PRINTED OVER NOTES. MANY ITEMS | | CAN NOT BE READ. | | THESE HAVE BEEN HIGH-LIGHTED ON ONE OF THE SET OF | | PLANS. | | SHEET E.06.1 ALSO DOES NOT CONTAIN ANY OF THIS MONTHS | | | | 5) NOTE: THE FOLLOWING ITEMS WITH RESPECT TO RISER, | | PANELS, ETC STILL NEED COORDINATION. | | | | A) PLEASE SEE PANEL HU-2 WHICH INDICATES 125AMP OVER | | CURRENT PROTECTION TO A 100AMP DISCONNECT ON THE LINE | | SIDE OF TRANSFORMER | | B) PLEASE SEE TRANSFORMER EK. RISER AND PLANS NOTE THIS | | NEW 45KVA UNIT WILL BE REPLACING THE EXISTING 30 KVA | | TRANSFORMER. THIS IS OK, HOWEVER PLEASE SEE THE | | TRANSFORMER SCHEDULE ALONG WITH THE PRIMARY OVER | | CURRENT PROTECTION. | | THE SCHEDULE SHOWS A 45KVA TRANSFORMER HOWEVER ONLY | | WITH THE AMPERAGE RATING OF THE PREVIOUS 30KVA UNIT. | | 45KVA AT 480V IS 54.15AMPS NOT THE 36 AS LISTED ON | | SCHEDULE. THE 36 AS LISTED ON SCHEDULE WOULD BE A 30KVA | | UNIT AT 480V. | | THIS WILL AFFECT THE OVER CURRENT PROTECTION ON THE | | PRIMARY ALSO AS THIS IS NOTED AS 45AMPS. | | THESE ITEMS AFFECT THE POWER PANEL SCHEDULE SHEET AS | | WELL AS *BOTH* RISERS ON SHEET E.02. | | 110.3,110.14,450.3,240.4,310.16,408, 240.21 ETC | | | | 6) NOTE: PLEASE SEE 210.8B2 AS ALL 15/20AMP 120V | | RECEPTACLES IN KITCHEN AREAS SHALL BE GFCI/ OR GFCI | | PROTECTED. SEE CIRCUITS SUCH AS EK-9, EK-11 ARE TWO | | EXAMPLES IN WHICH NO PROTECTION IS SHOWN. THESE ARE NOT | | THE ONLY TWO. | | | | 7) NOTE: AS NO LIGHTING ETC IS SHOWN FOR A COMPLETE | | HOOD SYSTEM AND HOOD MAY BE UNDER SEPARATE PERMIT | | PLEASE KNOW THAT ALL LIGHTING AND ELECTRICAL PER | | NFPA-96 SHALL BE INTERCONNECTED AND SHUT DOWN UPON | | ACTIVATION OF SYSTEM FOR FIRE SUPPRESSION. | | NO INFORMATION NOTED AT THIS TIME AND WILL NEED TO BE | | NOTED UNDER SEPARATE PERMIT. | | | | 8) NOTE: SHEET E.05 CONTAINS SOME NOTES FOR POSSIBLE | | ACCESS CONTROL. THE SYMBOL LEGEND MAKES NOTE OF | | POSSIBLE MAG-LOCKS ETC. | | PLEASE SEE NFPA-101 CHAPTER 7 FOR EGRESS CONTROLS. NO | | DEVICES UNDER NORMAL OR EMERGENCY CONDITIONS SHALL | | IMPEDE THE EGRESS OUT OF ANY AREAS. SEE COMMENTS FROM | | FIRE MARSHAL. | | AS THE COMPLETE SYSTEM IS NOT DETAILED, THIS MAY BE | | UNDER SEPARATE PERMIT FOR LOW VOLTAGE ACCESS CONTROLS. | | FBC 105.1. | | | | 9) NOTE: MANY OF THE FIXTURES ARE HALF SHADED AND | | SYMBOL LEGEND SEEMS TO INDICATE EMERGENCY POWER. THE | | FIXTURE LEGEND HOWEVER DOES NOT LIST ANY BATTERY BACK | | UP BALLAST AS REQUIRED. | | PLEASE ADJUST. NFPA-101 7.8, 7.9, FBC 1006.1 | | PLEASE ALSO KNOW AS NOTED ABOVE, ANY EGRESS LIGHTING | | BEING CONTROL BY OCCUPANCY SENSOR TYPES DEVICES PER FBC | | 13-415.1.ABC.1, SHALL BE FAIL SAFE TYPE CONTROL DEVICES | | PER FBC 1006.1.2, NFPA-101 7.8.1.2.2. | | | | 10) NOTE: PLEASE COMPLETE ALL LIGHTING CIRCUITS ON | | PLANS AND COORDINATE WITH THE PANEL SCHEDULES. | | BE SURE TO SEE 7..12F FOR CIRCUITING FOR EMERGENCY AND | | EXIT LIGHTS. | | 408.4, FBC 106.1.1, 106.5. | | | | | | ** IMPORTANT ** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-10-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-08 |
Time |
08:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-08 |
Time |
08:39 |
Sent To |
|
|
Notes |
2008-10-08 08:39:58 | | | ** DENIED ** | | | | 1) NOTE: PLEASE SEE THERE IS A LIST OF *EXPIRED* | | PERMITS BASED ON PRIME PERMIT APPLIED FOR THIS SCOPE OF | | WORK FROM 2005. THE BASE PERMIT IS 05041896. | | THERE ARE ITEMS ON PLANS WHICH DO NOT SHOW UP ON RECORD | | PLANS SUBMITTED IN LAST 10YEARS. THE EXPIRED APPLIED | | SCOPE OF WORK AS MENTIONED SHOWS SOME OF THIS WORK TO | | BE DONE HOWEVER NO RECORD OF PERMITTING. A FIELD | | PRE-INSPECTION MAY BE NEEDED TO VERIFY ALL PERMITTED | | SCOPE OF WORK. | | | | 2) NOTE: PLEASE SEE COMMENTS WHICH WILL BE FROM OTHER | | TRADES WHICH WILL HAVE AN AFFECT ON THE ELECTRICAL | | PLANS. | | PLEASE BE SURE THESE ARE ALL COORDINATED. | | PLEASE SUBMIT COMPLETED PLANS. SEE NOTES BELOW AS THERE | | ARE SEVERAL ITEMS WHICH WERE EITHER NOT SHOWN ON NOT IN | | DESIGN AT THIS TIME. THERE MAY VERY WELL BE NEW | | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE | | AT THIS TIME. | | | | 3) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE ON | | PLANS. | | 2004 FBC W/ 2007 REVISIONS. | | | | 4) NOTE: THE PLANS SUBMITTED DO NOT INCLUDE ANY | | ELECTRICAL FOR THE NEW DETACHED PARKING STRUCTURE. | | PLEASE BE SURE TO SEE 225.31-225.39, AND 250.32, 250.50 | | | | 5) NOTE: PLEASE PROVIDE MINIMUM LOCATIONS AND LEVELS | | FOR ALL HORN/STROBE DEVICES FOR FIRE ALARM SYSTEM | | MEETING FS 633, NFPA-72 AND FBC 11-4.28.1, 2 AND .3. | | PLEASE BE SURE TO SHOW ALL LOCATIONS AND MINIMUM LEVELS | | OF DEVICES. | | | | 6) NOTE: PLEASE SEE RISER AND PANEL SCHEDULES AS THERE | | ARE SEVERAL INCONSISTENCIES. BELOW ARE SOME EXAMPLES | | HOWEVER THESE ARE ARE NOT ALL. | | | | EXAMPLE: PLEASE SEE MAIN DISTRIBUTION PANEL AS THIS | | INDICATES A FEED TO DP1 THROUGH A TRANSFORMER HOWEVER | | THE RISER DOES NOT INDICATE ANY TRANSFORMER AND BOTH | | MAIN SWITCH BOARD AND DP1 IS 277/480. PLEASE CORRECT. | | | | EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL EK AS | | EXISTING YET THE SCHEDULE SHOWS THIS AS NEW. | | | | EXAMPLE: PLEASE SEE RISER WHICH INDICATES PANEL K AS | | EXISTING YET THE SCHEDULE SUBMITTED SHOWS THIS AS NEW. | | | | EXAMPLE: NOTES ON RISER SHEETS MENTIONS SOME | | TRANSFORMER WILL BE CHANGED TO 75 KVA YET THE RISER | | SHOWS BOTH OF THEM AS 45KVA. | | | | EXAMPLE: PLEASE SEE HU2 ON RISER WHICH INDICATES AS | | 80AMP BREAKER TO THE TRANSFORMER YET THE PANEL SCHEDULE | | INDICATES 90AMP BREAKER. | | | | THESE ARE SOME EXAMPLES ONLY WHICH ELECTRICAL RISER AND | | PANELS NEED SOME COORDINATION. | | | | NEC 230,215,240,408,220, ETC | | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION, | | CLARITY AND COORDINATION. | | | | 7) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH | | THE PANEL SCHEDULE. THERE ARE SEVERAL INCONSISTENCIES | | WITH WHAT IS SHOWN ON THE PLANS WITH CIRCUITS WHICH ARE | | SHOWN ON SCHEDULES. SOME CIRCUITS ON PANELS WHICH ARE | | ON PLANS ARE BLANK, SOME ARE SPARES, AND MANY ARE NOTED | | FOR ELECTRICAL EQUIPMENT AND CIRCUITS WHICH ARE NOT THE | | SAME ON PLANS. BELOW ARE SOME EXAMPLES AND IS IN NO WAY | | ALL ITEMS. | | | | EXAMPLE: PLEASE SEE PLANS AS SOME CIRCUITS ARE LABELED | | WITH AN *XXX-XX* ETC | | | | EXAMPLE: PLEASE SEE CIRCUIT K-23 ON PLANS AS THIS IS | | BLANK ON SCHEDULE. | | | | EXAMPLE: PLEASE SEE K 16, AND 18 AS THESE ARE NOTED AS | | THE DISHWASHERS ON PLANS YET THE PANEL SCHEDULE | | INDICATES THESE ARE MICROWAVES. | | | | EXAMPLE: PLEASE SEE EK-23,25,27 ON PLAN AS ALL OF THESE | | ARE BLANK ON THE PANEL SCHEDULE. | | | | EXAMPLE: PLEASE SEE EK-14, 12 WHICH ARE SHOWN ON PLAN | | FOR REFRIGERATOR/FREEZER EQUIPMENT YET THE PANEL | | SCHEDULES INDICATES A BREAKER FOR LIGHTING AND THE | | OTHER IS SHOWN AS A SPARE. | | | | EXAMPLE: PLEASE SEE K-29 WHICH IS SHOWN ON PLANS | | FEEDING GFI RECEPTACLES FOR BATH ROOM ETC YET THE PANEL | | SCHEDULE INDICATES THIS AS LIGHTING. | | | | EXAMPLE: PLEASE SEE CIRCUITS EK 4, AND 6 WHICH IS SHOWN | | AS REFRIGERATOR EQUIPMENT YET THE PANEL SCHEDULE | | INDICATES A 3-POLE BREAKER FOR SUMP PUMPS. | | | | *** THESE ARE ONLY SOME OF THE EXAMPLES IN WHICH | | COORDINATION IS NEEDED. THERE ARE OTHERS HOWEVER THIS | | REVIEW IS GIVING SOME EXAMPLES AS BENEFIT TO THE | | DESIGNER OF RECORD. | | PLEASE SEE THE SECTION OF 408.4 WHICH WAS EXTRACTED | | FROM THE 2005 NEC. | | | | 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION | | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL | | BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON | | THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | PANELBOARD, AND LOCATED AT EACH SWITCH ON A | | SWITCHBOARD. | | THE REQUIREMENT TO PROVIDE AN UP-TO-DATE, ACCURATE, AND | | LEGIBLE CIRCUIT DIRECTORY APPLIES TO PANELBOARDS AND | | SWITCHBOARDS COVERED IN ARTICLE 408. THE CIRCUIT | | DIRECTORY IS AN IMPORTANT FEATURE FOR THE SAFE | | OPERATION OF AN ELECTRICAL SYSTEM UNDER NORMAL AND | | EMERGENCY CONDITIONS. THE PURPOSE OF AN ACCURATE AND | | LEGIBLE CIRCUIT DIRECTORY IN THESE TYPES OF EQUIPMENT | | IS TO PROVIDE CLEAR IDENTIFICATION OF CIRCUIT BREAKERS | | AND SWITCHES THAT MAY NEED TO BE OPERATED BY SERVICE | | PERSONNEL OR THOSE WHO NEED TO OPERATE A SWITCH OR | | CIRCUIT BREAKER IN AN EMERGENCY. THIS REQUIREMENT IS | | SPECIFIC TO SWITCHBOARDS AND PANELBOARDS; HOWEVER, THE | | IDENTIFICATION REQUIREMENTS OF 110.22 APPLY TO ALL | | DISCONNECTING MEANS. | | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE | | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A | | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE | | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. | | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED | | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE | | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, | | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE | | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT | | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS | | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR | | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT | | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE | | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT | | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION. | | | | NEC 408.4, 310.16,240.4 ETC | | FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION, | | COORDINATION AND CLARITY OF PLANS. | | | | 8) NOTE: PLEASE SEE 450.3 AS THE OVER CURRENT | | PROTECTION ON RISER FOR TRANSFORMER FEEDING PANEL *K* | | IS TOO HIGH. THE RISER DOES CONTAIN A SCHEDULE WHICH | | NOTES OVER CURRENT PROTECTION AT THE MAXIMUM OF 125%. | | HOWEVER THE RISER STILL ALSO SHOWS THIS SAME | | TRANSFORMER AS A 45KVA UNIT. IF THIS UNIT IS REVISED TO | | 75KVA THEN THE 90AMP OCP WOULD BE OK. | | | | 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1,.1.2, .1.3 AND | | .1.4 FOR MISSING LIGHTING CONTROLS FOR ALL NEW LIGHTING | | BEING INSTALLED. AS NO DEVICES OR SYSTEM IS BEING SHOWN | | AT THIS TIME NO REVIEW OF THESE CAN BE DONE. | | | | 10) NOTE: PLEASE COMPLETE A FIXTURE LEGEND FOR SPECIFIC | | FIXTURES. PLEASE SUBMIT LIGHTING PERFORMANCE | | CALCULATIONS FOR ALL AREAS IN SCOPE OF WORK. PLEASE SEE | | FBC 13-415.2, 13-415.2.ABC.1.1,.1.2 AND .1.3. | | PLEASE KNOW AS NO PERFORMANCE CALCULATIONS WERE | | SUBMITTED IT IS NOT POSSIBLE TO SUPPLY ANY REVIEW | | COMMENTS ON THOSE ITEMS. | | | | 11) NOTE: PLEASE KNOW ANY LOW VOLTAGE FOR SOUND, ACCESS | | CONTROL WILL BE REQUIRED TO BE UNDER SEPARATE PERMIT, | | WITH PLANS AND FEES BASED ON THAT SCOPE OF WORK. | | | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
4 |
Status |
P |
Date |
2009-10-22 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2009-10-22 |
Time |
11:35 |
Rev Time |
4.00 |
Received By |
mgonzale |
Date |
2009-10-22 |
Time |
11:32 |
Sent To |
|
|
Notes |
2009-10-22 11:35:29 | PASSED WITH PROVISOS | | | | #1 PROJECT HAS COMPLIED WITH DOCUMENTATION ASKED BY | | ENGINEERING DEPT. | | #2 SITE IS UNDER AN ACRE HOWEVER PROJECT HAS COMPLIED | | WITH SFWMD AND CITY STORMWATER ENG REVIEW 10-16-09 | | #3 PROJECT IS STILL SUBJECT TO NDPES REQUIREMENTS AS TO | | POLLUTION PREVENTION PLANS | | #4 PROVIDE AS-BUILTS TO ENGINEERING DIV FOR FINAL | | APPROVAL. | | | | MANUEL JULIAN GONZALEZ | | CS ENGINEERING REVIEWER | | 401 CLEMATIS STREET | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
3 |
Status |
F |
Date |
2009-09-29 |
|
|
Cont ID |
|
Sent By |
mgonzale |
Date |
2009-09-29 |
Time |
11:26 |
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2009-09-29 |
Time |
11:26 |
Sent To |
|
|
Notes |
2009-09-29 11:37:13 | FAILED: | | | | THE CITY NEEDS A SEPERATE SUBMITTAL FROM YOUR CIVIL | | ENGINEER TO CITY OF WEST PALM BEACH ENGINEERING. | | | | IT'S IMPORTANT TO UPDATE YOUR PERVIOUS AND IMPERVIOUS | | GROUND AREAS SO THAT WE CAN UPDATE YOUR STORMWATER | | ACCOUNT WITH THE CITY. | | | | FLORIDA STATE LEGISLATURE CREATED WATER MANAGEMENT | | DISTRICTS TO CONTROL WATER FLOWS FOR FLOOD PROTECTION | | AND PRESERVE WATER RESOURCES. THE SOUTH FLORIDA WATER | | MANAGEMENT DISTRICT IS ONE OF 5 DISTRICTS WHICH WERE | | CREATED, AND ENCOMPASSES THE SOUTHEAST COAST OF | | FLORIDA. CHAPTER 373 OF THE FLORIDA STATUTES (F.S.) | | (THE FLORIDA WATER RESOURCES ACT OF 1972), GIVES | | AUTHORITY TO THE SFWMD TO CARRY OUT ITS REGULATORY | | DUTIES, THE ENVIRONMENTAL RESOURCE PERMIT INFORMATION | | MANUAL VOLUME IV UPDATED IN DECEMBER 2003, IS THE | | LATEST EDITION. | | | | WATER QUALITY CRITERIA MUST BE IN PLACE AS RUNOFF SHALL | | BE DISCHARGED FROM IMPERVIOUS SURFACES THROUGH | | RETENTION AREAS, DETENTION DEVICES, FILTERING AND | | CLEANSING DEVICES, OR SUBJECT TO SOME OTHER TYPE OF | | BEST MANAGEMENT PRACTICE (BMP) PRIOR TO DISCHARGE FROM | | THE PROJECT SITE. PROJECTS WHICH INCLUDE SUBSTANTIAL | | PAVED AREAS, SUCH AS, SHOPPING CENTERS, LARGE HIGHWAY | | INTERSECTIONS WITH FREQUENT STOPPED TRAFFIC, AND HIGH | | DENSITY DEVELOPMENTS, PROVISIONS SHALL BE MADE FOR THE | | REMOVAL OF OIL, GREASE, AND SEDIMENT FROM STORMWATER | | DISCHARGES. | | | | OFF-SITE DISCHARGES ARE LIMITED TO RATES NOT CAUSING | | ADVERSE IMPACTS, AND: A) HISTORIC DISCHARGE RATES, OR, | | B) RATES DETERMINED IN PREVIOUS DISTRICT PERMIT | | ACTIONS, OR; C) RATES SPECIFIED IN DISTRICT CRITERIA. | | | | OTHER ELEMENTS THAT MUST BE CONSIDERED ARE FLOOD | | PROTECTION OF BUILDING FLOORS AND FLOOD PROTECTION OF | | ROADS AND PARKING LOTS. | | | | STORMWATER BEST MANAGEMENT PRACTICES (BMPS) ARE METHODS | | FOUND TO BE EFFECTIVE WAYS TO PREVENT POLLUTION FROM | | ENTERING WATERWAYS THROUGH STORMWATER RUNOFF. THE | | SECTION CONSIDERS BOTH STRUCTURAL BMPS, AS WELL AS, AN | | EXPLORATION OF NON-STRUCTURAL SOURCE CONTROLS. | | STRUCTURAL BMPS ARE ENGINEERED AND CONSTRUCTED TO | | REDUCE, CAPTURE, AND TREAT POLLUTION GENERATED BY | | STORMWATER RUNOFF. GENERALLY, STRUCTURAL BMPS REQUIRE | | ADDITIONAL LEVELS OF MAINTENANCE TO REMAIN OPERATIONAL | | AND EFFECTIVE. NON-STRUCTURAL BMPS INCLUDE GENERAL | | PRACTICES AND POSSIBLY RULES AND REGULATIONS TO CONTROL | | POLLUTANTS BEFORE THEY ENTER THE STORMWATER SYSTEM. | | | | SEDIMENTS, OILS, GREASES, HYDROCARBON RESIDUE, HEAVY | | METALS, AND ORGANIC NUTRIENTS ARE TYPICAL TYPES OF | | POLLUTION GENERATED BY AN URBAN ENVIRONMENT. IN | | ADDITION, FERTILIZERS AND PESTICIDES CAN CONTRIBUTE TO | | POLLUTANT LOADINGS. | | | | PLEASE CONSIDER THE FOLLOWING AND RESPOND TO CITY OF | | WPB ENGINEERING DEPT. 4TH FLOOR ATTENTION BRIAN MOREE, | | ENGINEERING CONTRUCTION SUPERVISOR. THANK YOU FOR YOUR | | ATTENTION. | | THE WEB LINK BELOW CAN PROVIDE YOU THE "DEVELOPMENT | | PERMIT PACKAGE" FOR YOUR SUBMITTAL . | | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP | | | | PLAN SPECIFIC COMMENTS: | | SHEET C-2 DOES NOT CALL OUT ONE OF THE CATCH BASINS AS | | EXISTING NOR PROPOSED | | OUTFALL IS NOT CLEARLY SHOWN. | | C-1 AND C-2 COULD BE COMBINES INTO ONE SHOWING ALL | | DRAINAGE IMPROVEMENTS. | | IDENTIFY ALL DRAINAGE EASEMENTS AND OUTFALLS ON THE | | PLAN. | | NO POLLUTION PREVENETION PLAN SHOWN. | | | | PROVIDE WRITTEN RESPONSE TO PREVIOUS COMMENTS BY | | RCHOKSI AND EFABIAN. (PREVIOUS ENGINEERING REVIEW | | COMMENTS) | | | | MANUEL JULIAN GONZALEZ | | CS ENGINEERING REVIEW | | 401 CLEMATIS STREET, 1TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | DIRECT: (561) 494-1085 | | FAX: (561) 494-1116 | | MOBILE: (561) 644-7301 | | EMAIL: [email protected] | | WWW.WPB.ORG/ENGINEERING |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
F |
Date |
2009-01-13 |
|
|
Cont ID |
|
Sent By |
efabian |
Date |
2009-01-13 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
efabian |
Date |
2009-01-13 |
Time |
11:06 |
Sent To |
|
|
Notes |
2009-01-13 11:05:39 | DUMPSTER ENCLOSURE SHOWN ON SHEET C.02 IS SMALLER THAN | | THE DETAIL OF IT ON SHEET C.03 AND SHOULD MATCH THE | | DIMENSIONS OF THE DETAIL. THE ENCLOSURE SHOULD BE | | RECONFIGURED TO ALLOW A 5 FOOT PERIMETER LANDSCAPE | | BUFFER. |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
F |
Date |
2008-09-24 |
|
|
Cont ID |
|
Sent By |
rchokshi |
Date |
2008-09-24 |
Time |
08:53 |
Rev Time |
0.00 |
Received By |
rchokshi |
Date |
2008-09-24 |
Time |
08:49 |
Sent To |
|
|
Notes |
2008-09-24 08:52:56 | FAILED FOR FOLLOWING REASONS: | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | NOI. | | YOU CAN GET NOI INFO FROM | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), EFFECTIVE | | MAY 1, 2003 | | | | 2. PLEASE SHOW ON DRAWINGS THE SILT FENCE DETAILS & | | TURBIDITY DETAILS OF POLLUTION PREVENTION . PLEASE SHOW | | ON DRAWINGS THE SILT FENCE AROUND THE WHOLE SITE, & | | TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND | | ALL DEMOLITION PHASE. HEIGHT OF FENCE SHOULD BE HIGH | | ENOUGH PER FDEP TO STOP DUST PARTICLES. | | | | 3. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO. | | 4060-07: | | | | ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH | | EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY | | APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE | | FOLLOWING: | | | | 1. EROSION CONTROL, AND | | 2. LAND STABILIZATION | | | | THE AMOUNT OF THE EROSION CONTROL AND LAND | | STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER | | OF RECORD USING THE CURRENT CITY COST SCHEDULE AND | | VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT. | | PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION | | SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION. | | | | UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN | | FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL | | TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE | | MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS. | | | | A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM | | THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR. | | | | 4. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR | | SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP | | PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL | | CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING | | SERVICES, PHONE# 494-1040 | | | | 5. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE | | DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | | 6. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED | | FLOOD ZONE AREA, & 5,10, 25, 50, 100 YEAR FLOOD | | CRITERIA AND CROWN OF THE ROAD WHEN YOU DETERMINE THE | | FIRST FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE | | ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD. | | | | 7. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA, | | GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU | | ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE | | THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH | | AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE | | PROVIDE A COPY OF THESE CALCULATIONS. | | | | 8. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL | | OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL | | THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL | | ENVRONMENTAL REPORT. | | | | 9. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND | | YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET | | FLOODED AND HAVE ENOUGH DRAINS. | | | | 10. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH | | REPORT & STORM WATER QUALITY CALCULATIONS TO 1000 45TH | | STREET FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT. | | | | 11. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G. | | OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT. | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | PERMITTING PROCESS | | | | RASIK CHOKSHI 805-6723 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2009-10-27 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-10-27 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-10-27 |
Time |
12:26 |
Sent To |
|
|
Notes |
2009-10-27 12:51:51 | *****APPROVED***** | | | | PLAN SHEETS LS.01, LS.02, AND LS.03 WERE STAMPED, | | INITIALED, AND DATED. PLAN SHEETS A.02, E.04, E.06, | | E.06.1, AND FP.01 WERE PREVIOUSLY FIRE-STAMPED ON | | 09/22/2009. | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2009-09-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-09-22 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-09-22 |
Time |
10:36 |
Sent To |
|
|
Notes |
2009-09-22 10:38:58 | *****PARTIAL APPROVAL***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED. PLAN SHEETS A.02, E.04, E.06, E.06.1, | | AND FP.01 WERE STAMPED, INITIALED, AND DATED; HOWEVER | | SHEETS LS.01, LS.02, AND LS.03 ARE TO BE FIRE-STAMPED | | WHEN THE BUILDING EXAMINER'S COMMENTS HAVE BEEN | | SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2009-02-09 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2009-02-09 |
Time |
15:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2009-02-09 |
Time |
14:42 |
Sent To |
|
|
Notes |
2009-02-09 15:36:01 | *****DENIED***** | | | | THE FOLLOWING COMMENTS (NOT MARKED OK) TAKEN FROM THE | | PREVIOUS FIRE REVIEW STILL NEED TO BE ADDRESSED: | | | | 1. LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | ADD TO CODE ANALYSIS DATA SECTION OF THE SUBMITTED PLAN | | | | 2. OK | | | | 3. IN ADDITION TO 2A-10BC RATED, "K" RATED FIRE | | EXTINGUISHERIS REQUIRED FOR SMALL GREASE FIRE | | PROTECTION. COULD NOT LOCATE THE "K" EXTINGUISHER ON | | SHEET LS-1 AS INDICATED IN YOUR RESPONSE LETTER | | | | 4. | | | | 5. OK | | | | 6. OK | | | | 7. SHEET E.05 INDICATES CARD READERS AND KEYPADS. | | ACCESS CONTROL SYSTEMS SHALL COMPLY WITH NFPA 101, | | SEC.7.2.1.6.2. ADD COMMENT TO THE APPROPIATE PLAN SHEET | | | | 8. OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2008-10-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-10-23 |
Time |
13:19 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-10-23 |
Time |
13:19 |
Sent To |
|
|
Notes |
2008-10-23 13:30:04 | ***DENIED*** | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | 2) RAMPS TO COMPLY WITH 101, SEC. 7.2.5. PROVIDE | | PRESCRIPTIVE STRENGTH REQUIREMENTS FOR HANDRAILS AND | | GUARDRAILS. | | | | 3) IN ADDITION TO 2A-10 B,C RATED, "K" RATED FIRE | | EXTINGUISHER IS REQUIRED IN KITCHEN FOR SMALL GREASE | | FIRE PROTECTION. | | | | 4) IT DOES NOT APPEAR THAT ENOUGH AUDIBLE FIRE ALARM | | EQUIPMENT IS ILLUSTRATED IN KITCHEN AND SURROUNDING | | AREA. | | | | 5) IS THE KITCHEN AREA CONSIDERED A SEPARATE STRUCTURE | | AS A RESULT OF THE EXISTING (4) HOUR RATED FIRE WALL? | | | | 6) HOOD/SUPPRESSION SYSTEM TO COMPLY WITH THE | | REQUIREMENTS OF NFPA 96 AND SHALL BE TIED INTO THE | | BUILDING FIRE ALARM SYSTEM. SEPARATE SHOP DRAWINGS AND | | PERMITS ARE REQUIRED FOR HOOD/SUPPRESSION SYSTEM. | | | | 7) SHEET E.05 INDICATES CARD READERS. ACCESS CONTROL | | SYSTEMS SHALL COMPLY WITH 101, SEC. 7.2.1.6.2. SEPARATE | | SHOP DRAWINGS AND PERMIT REQUIRED PRIOR TO INSTALLATION | | OF EQUIPMENT. | | | | 8) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
P |
Date |
2009-08-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-08-27 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-08-27 |
Time |
16:53 |
Sent To |
|
|
Notes |
2009-08-27 16:54:52 | PASSED/PROVISO: | | | | REVISION REQUIRED SHOWING THE CORRECT PIPE SIZES ON THE | | GAS RISER DIAGRAM. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2009-01-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-28 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-28 |
Time |
16:18 |
Sent To |
|
|
Notes |
2009-01-28 16:36:08 | DENIED | | REFERENCE: | | FBC-2004 FUEL GAS | | | | ****FROM PREVIOUS REVIEW: | | | | 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT | | THE FOLLOWING INFORMATION: | | | | A. OK | | B. OK | | C. OK | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | ****RESPONSE NOTED, BUT DELEVERY PRESSURE IS NOT | | INDICATED. | | | | E. OK | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE GAS | | WATER HEATER HAVE NOT BEEN SUBMITTED. | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ****RESPONSE, NOTED, BUT THE MANUAL SHUT OFF VALVE AND | | THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE | | EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER | | HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? | | PLEASE CLARIFY. | | | | 2. OK | | 3. OK | | 4. OK | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2009-01-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-22 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-22 |
Time |
16:15 |
Sent To |
|
|
Notes |
2009-01-28 16:18:00 | DENIED | | REFERENCE: | | FBC-2004 FUEL GAS | | | | 1. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT | | THE FOLLOWING INFORMATION: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. LENGHTS NOT SHOWN. | | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000. | | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304. FOR WATER HEATER. | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | E. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | 2. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE | | FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES | | NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE | | RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES | | ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 & | | 402. | | | | 3. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION | | OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS | | 408.2 & 408.4. | | | | 4. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING | | BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH | | SHEET. FAC 61B15-23.002(2) & FS 471.025. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2009-10-19 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-10-19 |
Time |
16:12 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-10-19 |
Time |
16:12 |
Sent To |
|
|
Notes |
2009-10-19 16:12:47 | TO C27 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2009-08-27 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2009-08-27 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2009-08-27 |
Time |
08:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2008-12-23 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-23 |
Time |
16:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-10-23 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2008-10-23 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2008-09-19 |
Time |
09:19 |
Sent To |
|
|
Notes |
2008-09-19 09:19:34 | TO "COMM" BD#53 |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
P |
Date |
2009-09-04 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2009-09-04 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2009-09-04 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2009-09-09 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-09-09 |
Time |
11:09 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-09-09 |
Time |
10:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2009-02-01 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2009-02-01 |
Time |
13:05 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2009-02-01 |
Time |
11:44 |
Sent To |
|
|
Notes |
2009-02-01 13:05:17 | REVIEW #: 2ND | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | 1. THE SYMBOL LEGEND PROVIDES NO SYMBOL TO BE USED FOR | | FIRE DAMPERS. THE INDICATION IS THAT FIRE DAMPERS ARE | | TO BE IDENTIFIED WITH "FD" BUT THERE ARE NO LOCATIONS | | INDICATED BY USING THIS DESIGNATION ON FLOOR PLANS. | | PLEASE SHOW ON PLANS WHERE EACH FIRE DAMPER IS LOCATED | | WITH THE USE OF A CLEARLY IDENTIFIED AND RECOGNIZABLE | | SYMBOL OR INDICATOR IN ACCORDANCE WITH FBCM 607.8 AND | | FBCB 106.1.1. | | | | 2 THROUGH 9: OK | | | | 10. DESIGNER???S RESPONSE INDICATES THERE IS A CONCERN | | REGARDING THE LACK OF A RETURN AIR INTAKE IN THE | | KITCHEN FOR WHEN THE EXHAUST FAN IS NOT RUNNING. IF | | BALANCED RETURN CAN NOT BE ACHIEVED WITH THIS | | CONFIGURATION (AS REQUIRED IN ACCORDANCE WITH FBCM | | 601.4) THEN IT IS THE DESIGNER???S RESPONSIBILITY TO | | DESIGN A SYSTEM WHICH MEETS DESIGN REQUIREMENTS IN A | | CODE COMPLIANT MANNER. SOME SUGGESTED OPTIONS ARE: | | DESIGNING A RETURN FOR THIS AREA WITH A MOTORIZED OR | | BAROMETRIC DAMPER THAT WILL OPEN WHEN THE KITCHEN | | EXHAUST IS NOT OPERATIONAL. THERE MAY BE OTHER OPTIONS | | AVAILABLE AT THE DESIGNER???S DISCRETION. PLEASE CALL | | TO DISCUSS IF NECESSARY. | | | | 11. OK | | | | 12. NOTE ON FLOOR PLAN CLAIMS DUCTS OF 100 SQ. IN. OR | | LESS DO NOT REQUIRE FIRE DAMPERS. NO SUCH EXCEPTION | | COULD BE FOUND IN THE CODE. THERE IS A SIX-PART | | EXCEPTION FOR FIRE DAMPERS IN FIRE PARTITIONS (SEE FBCM | | 607.5.3 EXCEPTION #2), BUT ALL SIX CONDITIONS MUST BE | | MET TO UTILIZE THE EXCEPTION. ALSO, FLOOR PLAN SHOWS | | FLEX DUCTS PENETRATING A WALL IDENTIFIED AS FIRE RATED | | ON ARCHITECTURAL PLANS. FLEXIBLE DUCTS AND AIR | | CONNECTORS SHALL NOT PASS THROUGH ANY | | FIRE-RESISTANCE-RATED ASSEMBLY IN ACCORDANCE WITH FBCM | | 607.7. IN ANY CASE, DUCTS PENETRATING FIRE RATED | | ASSEMBLIES SHALL BE PROTECTED WITH FIRE DAMPERS OR A | | THROUGH-PENETRATION FIRESTOP SYSTEM IN ACCORDANCE WITH | | FBCM 607.1.1. IF AN EXCEPTION TO THE REQUIREMENT FOR | | FIRE DAMPERS IN DUCTS, PLEASE SEE EXCEPTION #1 UNDER | | FBCM 607.5.3 IF THIS IS A FULLY SPRINKLERED BUILDING. | | | | 13 THROUGH 15: OK | | | | 16. NOTE ???I??? ON M.02 IS IN CONFLICT WITH THE NOTE | | ON M.04 REGARDING DAMPER OPERATION. PLEASE COORDINATE | | NOTES SHOWING COMPLIANCE WITH FBCM 508.1. | | | | 17. DETAIL FOR FAN COIL UNIT NOW SHOWS A DUCT DETECTOR | | ON THE SUPPLY AS REQUIRED BY FBCM 606.2.1. HOWEVER, | | DETAIL #15 ON PAGE M.05 SHOWS THE DUCT DETECTOR | | INSTALLED ON THE RETURN. PLEASE CORRECT. | | | | NEW COMMENTS BASED ON NEW INFORMATION AND?OR DETAILS | | PROVIDED: | | | | 18. CONDENSATE DETAIL #8 ON PAGE M.05 CALLS FOR AN | | AUXILIARY DRAIN FROM AN AUXILIARY DRAIN PAN TO BE | | ROUTED TO THE "NEAREST WET COLUMN." THIS DOES NOT | | CORRESPOND WITH THE REQUIREMENTS FOR AUXILIARY DRAIN | | PROTECTION UNDER FBCM 607.2.3. PLEASE SHOW A MEANS OF | | AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH THIS | | SECTION. | | NOTE: THE DETAIL CALLS FOR A FLOAT SWITCH IN THE | | AUXILIARY DRAIN PAN. THIS WOULD BE COMPLIANT WITH NO | | AUXILIARY DRAIN LINE INSTALLED ON THE PAN. | | | | 19. DETAIL #6 ON M.05 SHOWS A LOUVER INSTALLATION. | | LOUVERS ARE DEFINED AS PANEL WALLS PER FAC RULE 9B-72 | | AND ARE SUBJECT TO THE FLORIDA PRODUCT APPROVAL SYSTEM. | | PROVIDE PRODUCT APPROVAL DOCUMENTATION FOR THE SPECIFIC | | LOUVERS TO BE INSTALLED WITH INSTALLATION INSTRUCTIONS. | | | | 20. ENERGY CALCULATIONS ARE NOT SIGNED AND SEALED BY | | THE DESIGNER OF RECORD AND/OR OWNER-AGENT AS REQUIRED | | BY FBCB 13-103.1.1 AND 13-103.2. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2008-09-30 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-09-30 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-09-29 |
Time |
14:26 |
Sent To |
|
|
Notes |
2008-09-30 16:53:27 | REVIEW #: | | ACTION: | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PAGE A.02: THERE ARE SEVERAL SYMBOLS ON THE | | REFLECTIVE CEILING PLAN WHICH DO NOT APPEAR ON THE | | SYMBOL LEGEND. PLEASE PROVIDE CLARIFICATION AND | | IDENTIFICATION OF EACH ITEM TO BE INSTALLED IN THE | | CEILING. THIS CEILING SPACE IS TO SERVE AS A RETURN AIR | | PLENUM AND ALL ITEMS IN THIS PLENUM MUST BE IDENTIFIED | | TO DEMONSTRATE COMPLIANCE WITH FBCM 602.2. | | | | 2. PAGE A.02: NOTE ON THIS PAGE INDICATES R-19 | | INSULATION TO BE INSTALLED ABOVE THE CEILING. THIS | | CEILING SERVES AS A PLENUM AND THEREFORE THE INSULATION | | AND THERMAL BARRIER MUST BE ABOVE THE PLENUM SPACE. | | CAVITIES BENEATH A ROOF DECK WHICH WILL BE USED AS | | SUPPLY OR RETURN PLENUMS SHALL HAVE AN INSULATED ROOF. | | THE INSULATION SHALL HAVE AN R-VALUE OF AT LEAST R-19 | | IN ACCORDANCE WITH FBCB 13-404.1.ABC.2. ALSO, ROOF | | INSULATION SHALL NOT BE INSTALLED ON A SUSPENDED | | CEILING WITH REMOVABLE CEILING PANELS IN ACCORDANCE | | WITH FBCB 13-404.1.ABC.1. | | | | 3. KITCHEN EXHAUST SYSTEM: THERE IS NOT ENOUGH | | INFORMATION PROVIDED WITH THIS SUBMITTAL TO DO A | | THOROUGH REVIEW OF THE COMMERCIAL KITCHEN GREASE | | EXHAUST SYSTEM. SEPARATE PLANS AND PERMIT APPLICATIONS | | WILL BE REQUIRED FOR THE HOOD AND HOOD SUPPRESSION | | SYSTEMS. HOWEVER, THE FOLLOWING CONDITIONS ARE EVIDENT | | ON THESE PLANS AND SHALL BE ADDRESSED PRIOR TO PERMIT | | ISSUANCE: | | | | 4. EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE | | THROUGH EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES, | | VAPORS, AND ODORS IN THE DISCHARGE FROM SUCH | | TERMINATIONS DO NOT CREATE A PUBLIC NUISANCE OR A FIRE | | HAZARD IN ACCORDANCE WITH FBCM 506.3.12.2. SINCE THIS | | FAN DOES NOT APPEAR TO BE IN A LOCATION ACCESSIBLE TO | | THE PUBLIC, FIRE HAZARD IS THE PRIMARY CONCERN HERE, | | ALTHOUGH GREASE ACCUMULATION ON WALKING SURFACES MAY | | ALSO CREATE A HAZARD. | | | | 5. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 | | FEET ABOVE THE ADJOINING GRADE LEVEL IN ACCORDANCE WITH | | FBCM 506.3.12.3. BASED ON THE HEIGHT OF THE BALCONY | | ABOVE IT DOES NOT APPEAR FEASIBLE TO INSTALL A FAN | | WHERE THE BOTTOM OF THE FAN WILL BE A MINIMUM OF 10 | | FEET ABOVE GRADE. | | | | 6. EXHAUST FANS SHALL BE POSITIONED SO THAT THE | | DISCHARGE WILL NOT IMPINGE ON THE ROOF, OTHER EQUIPMENT | | OR APPLIANCES OR PARTS OF THE STRUCTURE IN ACCORDANCE | | WITH FBCM 506.5.2. THE LOCATION OF THE FAN AS SHOWN ON | | THE PLANS WILL BE DIRECTLY ADJACENT TO THE ROOF/BALCONY | | ABOVE, PROMOTING GREASE ACCUMULATION ON THE STRUCTURE | | AND CREATING A FIRE HAZARD. SEE ALSO COMMENT 3A ABOVE. | | | | 7. EXHAUST AIR SHALL NOT BE DIRECTED ONTO WALKWAYS IN | | ACCORDANCE WITH FBCM 401.5.2. | | | | 8. DETAIL #9 ON PAGE M0.5 SHOWS THE KITCHEN EXHAUST | | DUCT SIZED AT 16X20. WITH A VOLUME OF 1930 CFM AS SHOWN | | ON THE EQUIPMENT SCHEDULE, THE VELOCITY OF THE EXHAUST | | AIR WITHIN THE GREASE DUCT WILL BE APPROXIMATELY 869 | | FPM. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE | | DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY | | WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER | | MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE IN | | ACCORDANCE WITH FBCM 506.3.4. | | | | 9. THE AIR BALANCE SCHEDULE DOES NOT CORRESPOND WITH | | THE INFORMATION ON FLOOR PLANS AND SCHEDULES. EXAMPLE: | | THERE IS NO INFORMATION ON THE PLANS REGARDING THE BATH | | EXHAUST, UTILITY EXHAUST OR WATER HEATER EXHAUST. THESE | | APPLIANCES SHALL BE LISTED IN THE EQUIPMENT SCHEDULE IN | | ACCORDANCE WITH FBCB 106.3.5 AND FBCM 301.1. | | | | 10. THE REFLECTIVE CEILING PLAN SHOWS A RETURN AIR | | GRILL IN THE KITCHEN ADJACENT TO THE KITCHEN HOOD. AS | | THIS UNIT PROVIDES AIR FOR STORAGE, OFFICE AND RESTROOM | | SPACES, IT IS NOT DEDICATED TO THE KITCHEN AREA | | EXCLUSIVELY. RETURN AIR INTAKE SHALL BE PROHIBITED IN | | NON-DEDICATED KITCHEN HVAC SYSTEMS IN ACCORDANCE WITH | | FBCM 407.1. | | | | 11. PAGE M0.4 FLOOR PLAN SHOWS CEILING MOUNTED EXHAUST | | FANS IN BATHROOM AND UTILITY ROOM. PLAN ALSO INDICATES | | A POWER VENT TYPE SYSTEM FOR THE WATER HEATER. THESE | | SYSTEMS CAN NOT BE INSTALLED IN A RETURN AIR PLENUM | | CEILING. EXHAUST DUCTS UNDER POSITIVE PRESSURE, | | CHIMNEYS, AND VENTS SHALL NOT EXTEND INTO OR PASS | | THROUGH PLENUMS IN ACCORDANCE WITH FBCM 601.3. | | | | 12. PLEASE IDENTIFY ON PLANS THE LOCATION OF EACH FIRE | | DAMPER AT EACH DUCT PENETRATION OR TRANSFER OPENING. | | THE SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH | | FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER SHALL BE | | SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING PLANS BY | | THE DESIGNER IN ACCORDANCE WITH FBCM 607.8. | | | | 13. MECHANICAL PLAN INDICATES GAS WATER HEATER IN THE | | UTILITY ROOM WITH POWER VENT. PLUMBING AND | | ARCHITECTURAL PLANS SHOW THIS WATER HEATER IN THE | | MECHANICAL ROOM WHICH SERVES AS A RETURN AIR PLENUM. | | WHICH IS CORRECT? COMBUSTION WATER HEATERS AND | | ATMOSPHERIC COMBUSTION FURNACES SHALL NOT BE LOCATED IN | | MECHANICAL CLOSETS USED AS RETURN AIR PLENUMS IN | | ACCORDANCE WITH FBCM 603.9. | | | | 14. PLEASE INDICATE ON PLANS THE TYPE OF WALL FINISHES | | TO BE USED ON THE TYPE 1 AND TYPE 2 WALLS AT THE | | MECHANICAL ROOM. THE WALL SCHEDULE INDICATES THE TYPE 1 | | WALLS FINISHED ON 1 SIDE AND THE TYPE 2 WALLS WITH NO | | FINISH. THIS ROOM IS BEING USED AS A PLENUM. THE PLENUM | | SHALL BE LINED WITH AN APPROVED AIR BARRIER AND | | INSULATED IN ACCORDANCE WITH FBCM 607.8, 607.9 AND FBCB | | TABLE 13-410.1.ABC.2.2. SEE FBCM 603.9.1 FOR A LIST OF | | APPROVED AIR BARRIERS. | | | | 15. COOLING LOAD CALCULATIONS: THESE CALCULATIONS | | INDICATE TOTAL OUTSIDE AIR OF 400 CFM WHILE THE PLANS | | INDICATE THAT A MINIMUM OF 1930 CFM IS REQUIRED FOR | | KITCHEN EXHAUST MAKEUP AIR. PLEASE CLARIFY. ALSO, PAGE | | A0.1 INDICATES REMOTE CONDENSERS FOR THE REFRIGERATORS | | AND FREEZERS ARE TO BE LOCATED IN THE CLOSET. THESE ARE | | HEAT PRODUCING APPLIANCES. ARE THEY ACCOUNTED FOR IN | | THE CALCULATIONS? ARE THESE CONDENSERS APPROVED FOR | | INSTALLATION IN A PLENUM? SEE FBCB 13-407.1.ABC.1 AND | | FBCM 602.2. | | | | 16. NOTE I ON FAN COIL SCHEDULE INDICATES THAT THE OA | | DAMPER IS ONLY TO BE OPEN DURING OCCUPIED HOURS AS SET | | BY THE BAS. THIS DAMPER, AND THE RELATED FAN COIL UNIT | | SHALL BE INTERLOCKED WITH THE KITCHEN HOOD EXHAUST | | SYSTEM TO ENSURE THAT THE DAMPER IS OPEN AND THE FAN | | COIL IS OPERATING DURING ALL COOKING OPERATIONS, | | REGARDLESS OF THE SETTINGS OF THE BAS. FOR MECHANICAL | | MAKEUP AIR SYSTEMS, THE EXHAUST AND MAKEUP AIR SYSTEMS | | SHALL BE ELECTRICALLY INTERLOCKED TO ENSURE THAT MAKEUP | | AIR IS PROVIDED WHENEVER THE EXHAUST SYSTEM IS IN | | OPERATION IN ACCORDANCE WITH FBCM 508.1. | | | | 17. THERE IS NO INDICATION ON MECHANICAL OR ELECTRICAL | | PLANS THAT THERE IS A DUCT SMOKE DETECTOR INSTALLED ON | | THE FAN COIL UNIT. FAN SHUT DOWN BY SMOKE DETECTOR IS | | REQUIRED IN ACCORDANCE WITH FBCM 606.2. DUCT SMOKE | | DETECTORS SHALL BE CONNECTED TO THE BUILDING FIRE ALARM | | SYSTEM IN ACCORDANCE WITH FBCM 606.4. | | | | PLEASE RESPOND TO EACH COMMENT IN WRITING WITH A | | DESCRIPTION OF HOW EACH COMMENT WAS ADDRESSED AND WHERE | | THE RELEVANT INFORMATION CAN BE FOUND. THIS WILL ASSIST | | IN FACILITATING A TIMELY REVIEW. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2009-08-27 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-08-27 |
Time |
16:55 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-08-27 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2009-01-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2009-01-28 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2009-01-28 |
Time |
16:36 |
Sent To |
|
|
Notes |
2009-01-28 16:46:10 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | CITY WPB MUNICIPAL CODE | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. OK | | | | 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT | | THE FOLLOWING INFORMATION: | | | | A. OK | | B. OK | | C. OK | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | ****RESPONSE NOTED, PRESSURE NOT INDICATED. | | | | E. OK | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | ****RESPONSE NOTED, BUT MANUF SHEETS FOR THE WATER | | HEATER NOT SUBMITTED. | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND | | THE UNION ARE NOT INDICATED ON THE RISER DIAGRAM. THE | | EMERGENCY SHUT OFF VALVE WILL ALSO SHUT OFF THE WATER | | HEATER. WAS THIS THE INTENT OF THE DESIGN PROFESSIONAL? | | PLEASE CLARIFY. | | | | 8. OK | | 9. OK | | 10. OK | | | | 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN. | | PLEASE CORRELATE. SECTIONS 106.1.1 & 604. | | ****RESPONSE NOTED. BUT THE PIPING TO THE P-6 SINK | | STILL DOES NOT REFLECT THE FLOOR PLAN AS INDICATED. | | PLEASE CORRELATE. ALSO THE WATER HAMMER ARRESTORS SHALL | | BE LOCATED NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", | | NOT IN THE CEILING AS SOME ARE SHOWN. PDI-WH 201. | | | | 12. OK | | 13. OK | | | | 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT | | MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX | | (561) 659-7458 - E-MAIL [email protected]. ARTICLE III | | SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON | | INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT. | | ****RESPONSE NOTED, BUT THE REQUIREMENT IS FOR A 1250 | | GAL INTERCEPTOR AND THE PLANS SHOW A 750 GAL | | INTERCEPTOR. PLEASE SHOW REQUIRED SIZE. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2008-09-22 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-09-22 |
Time |
14:23 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-09-19 |
Time |
15:59 |
Sent To |
|
|
Notes |
2008-09-22 15:31:02 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | CITY WPB MUNICIPAL CODE | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. PLANS ARE REVIEWED UNDER THE ADOPTED CODES WHICH ARE | | THE FBC-2004 W/2007 REVISIONS. PLEASE INDICATE CODES | | THE WORK IS DESIGNED UNDER ON THE PLANS. SECTION | | 106.1.1. | | | | 2. SHT A.01 FLOOR PLAN SHOWS A KITCHEN WITH PANTRY, A | | TOILET ROOM, AN OFFICE, A MECHANICAL ROOM AND UPPER | | LEVEL WORK AS WELL AS A COVERED PARKING STRUCTURE. THE | | APPLICATION INDICATES A KITCHEN ADDITION & A COVERED | | PARKING STRUCTURE. PER APPLICATION, PLEASE DESCRIBE THE | | PROJECT IN DETAIL. INDICATE ALL WORK TO BE DONE UNDER | | THIS PERMIT. SECTIONS 105.1 & 105.3. | | | | 3. SHT A.04 COLUMN LINE 37 INDICATES A RAIN WATER | | LEADER IN THE COLUMN. IS THIS A NEW RWL? IF SO PLEASE | | INDICATE WHERE IT TERMINATES, THE SIZE OF THE RWL, AND | | FROM WHERE DOES THE RWL ORIGINATE. SECTIONS 106.1.2, | | 1106 & 1107. | | | | 4. SHT A.05 SHOW COMPLIANCE WITH SECTIONS 11-4.16.5 | | FLUSH CONTROLS, 11-4.19.2 CLEARANCES, 11-4.19.4 EXPOSED | | PIPES & SURFACES & 11-4.19.5 FAUCETS. | | | | 5. SHT P.01 THE LOCATION OF THE GAS WATER HEATER DOES | | NOT CORRELATE WITH THE LOCATION OF THE WATER HEATER | | SHOWN ON THE FLOOR PLAN ON SHT A.01, NOR DOES THE GAS | | PIPING SHOWN ON THE FLOOR PLAN & GAS RISER REFLECT THE | | LOCATION OF THE WATER HEATER ON EITHER SHEET. PLEASE | | CORRELATE & CLARIFY. SECTIONS 106.1.1 & 402. | | | | 6. SHT P.01 FLOOR PLAN AND PLUMBING RISER. THE DISH | | WASHERS SHALL DISCHARGE INTO THE SANITARY SYSTEM, NOT | | THE GREASE SYSTEM. MUNICIPAL CODE, ARTICLE III SECTION | | 90-124(7)(B). | | | | 7. SHT P.01 SEPARATE GAS PERMIT REQUIRED. PLEASE SUBMIT | | THE FOLLOWING INFORMATION: | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. LENGHTS NOT SHOWN. | | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). TOTAL IS 510,000 BUT IS SHOWN AS 410,000. | | | | C. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304. FOR WATER HEATER. | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | E. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | G. EMERGENCY HOOD SHUT DOWN SHUT OFF | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | DOWN STREAM OF MANUAL VALVE. | | | | 8. SHT P.01 THE GAS RISER DIAGRAM DOES NOT REFLECT THE | | FLOOR PLAN. THE SOLENOID VALVE ON THE FLOOR PLAN DOES | | NOT APPEAR TO CONNECT TO THE PIPING AS INDICATED ON THE | | RISER DIAGRAM AND THERE APPEARS TO BE TWO SUPPLY LINES | | ON THE STEAM POT. PLEASE CLARIFY. SECTIONS 106.1.1 & | | 402. | | | | 9. SHT P.01 GAS RISER DIAGRAM. PLEASE SHOW THE LOCATION | | OF THE DRIPS/SEDIMENT TRAPS AS REQUIRED IN SECTIONS | | 408.2 & 408.4. | | | | 10. SHTS P.02 & P.03 THE ADDRESS OF THE ENGINEERING | | BUSINESS SHALL BE INDICATED IN THE TITLE BLOCK OF EACH | | SHEET. FAC 61B15-23.002(2) & FS 471.025. | | | | 11. SHT P.02 DETAIL 2 WATER RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN. ONE P-6 SINK IS NOT SHOWN. | | PLEASE CORRELATE. SECTIONS 106.1.1 & 604. | | | | 12. SHT P.02 WATER HEATER DETAIL. A VACUUM RELIEF VALVE | | IS REQUIRED FOR ALL BOTTOM FED WATER HEATERS PER | | SECTION 504.2. -- THE P/T RELIEF VALVE SHALL BE | | INSTALLED IN THE SHELL OF THE WATER HEATER TAN, PER | | SECTION 504.4.1. -- THERMAL EXPANSION CONTROL IS | | REQUIRED PER SECTION SECTION 607.3.2. PLEASE INDICATE | | METHOD. | | | | 13. SHT P.03 A VACUUM BREAKER IS REQUIRED ON THE HOSE | | BIBB INDICATED ON THE CAN WASH DETAIL. SECTION | | 608.15.4.2. | | | | 14. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE | | UTILITY DEPT., INDUSTRIAL PRETREATMENT. PLEASE CONTACT | | MR. WILLIAM ROBERTS, (561) 822-2200 EXT. 2272, - FAX | | (561) 659-7458 - E-MAIL [email protected]. ARTICLE III | | SECTION 90-124. PLEASE SUBMIT WRITTEN DETERMINATION ON | | INTERCEPTOR SIZE WHEN RESUBMITTING PLANS FOR PERMIT. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2009-10-26 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-10-26 |
Time |
17:09 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-10-26 |
Time |
17:09 |
Sent To |
|
|
Notes |
2009-10-26 17:12:10 | PASSED W/PROVISOS | | | | 1) THE POSTS/BOLLARDS SHOWN INSIDE THE DUMPSTER | | ENCLOSURE ARE NOT ALLOWED | | | | 2) SHEETS PA.01 THROUGH PA.03 SHALL BE USED FOR THE | | PARKING SPACES AND THE COVERED PARKING STRUCTURE ONLY. | | THE SHEET SP.1 AND LANDSCAPE PLANS SHALL GOVERN SITE | | WORK OUTSIDE OF THE COVERED PARKING STRUCTURE. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2009-09-04 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-09-04 |
Time |
11:34 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-09-04 |
Time |
11:34 |
Sent To |
|
|
Notes |
2009-09-04 11:56:56 | FAILED | | | | 1) SHEET C.03 MISSING FROM ONE SET OF PLANS. | | | | 2) WHEEL STOP DETAILS ON SHEETS SP.01 AND C.03 ARE NOT | | THE SAME. | | | | 3) SHEET C.02 DOES NOT MATCH APPROVED SITE PLAN LAYOUT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2009-01-02 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2009-01-02 |
Time |
10:34 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2009-01-02 |
Time |
10:34 |
Sent To |
|
|
Notes |
2009-01-02 10:45:54 | FAILED | | | | PROVIDE RESPONSES IN WRITING: | | | | 1) AS STATED IN THE 1ST REVIEW, THIS PERMIT REQUIRES A | | MINOR PD AMENDMENT AND FORMAL SITE PLAN APPROVAL PRIOR | | TO ZONING PASSING THE PERMIT. NEITHER OF THESE HAVE | | BEEN GRANTED. | | | | 2) ZONING COMMENTS: | | | | A. PARKING DETAILS MEETING CITY OF WEST PALM BEACH | | STANDARDS ARE REQUIRED ON THE PLANS. SPECIFIC ISSUE - | | WHEEL STOP LOCATION NOT TWO (2) FEET FROM THE HEAD OF | | THE SPACE. NOTE THE DETAIL DIMENSIONS DO NOT MATCH THE | | DIMENSIONS ON THE PLAN. | | B. THE NEW DUMPSTER ENCLOSURE SHOW ON THE PLANS DOES | | NOT MEET CITY SIZE OR LANDSCAPE STANDARDS. NOTE THE | | DETAIL DIMENSIONS DO NOT MATCH THE DIMENSIONS ON THE | | PLAN. | | C. D-TYPE CURBING SHALL BE USED TO PROTECT THE | | LANDSCAPE AREAS FROM VEHICULAR ENCROACHMENT ALONG THE | | DRIVE AISLES. THIS IS NOT INDICATED ON THE PLANS. | | D. THE SITE AND THE LANDSCAPE PLANS DO NOT MATCH. | | SPECIFICALLY IN THE NORTHWEST CORNER OF THE LIMITS OF | | WORK. | | E. THE AMERICANS WITH DISABILITIES ACT (ADA) REQUIRES | | THAT IF COVERED PARKING IS PROVIDED, THEN COVERED ADA | | PARKING SHALL BE PROVIDED AS WELL. EITHER SHOW WHERE | | THERE CURRENTLY EXISTS COVERED ADA PARKING ON THE | | CHRISTIAN CONVENTION CENTER CAMPUS, OR PROVIDE A | | COVERED ADA SPACE IN THE NEW COVERED PARKING AREA. IF | | ADA SPACE IS REQUIRED, THE DETAILS SHALL BE PROVIDED. | | F. WHAT ARE THE DOTS SHOWN IN THE DRIVE AISLE? ARE | | THESE COLUMNS OR STRAY MARKS. COLUMNS ARE NOT ALLOWED, | | STRAY MARKS SHALL BE REMOVED. | | | | 3) LANDSCAPE COMMENTS: | | | | A. SHEETS LA.01 AND SP.01 WITH THE LATEST REVISION DATE | | OF 10/31/08 ARE INCONSISTENT. THERE IS AN APPARENT | | WALKWAY SHOWN ON ONE PLAN AND A RETAINING WALL ON THE | | OTHER. | | B. SHEET LA.01 THAT WAS SUBMITTED WITH THE ?TREE | | ALTERATION PERMIT? IS DIFFERENT FROM SHEET LA.01 THAT | | WAS MOST RECENTLY SUBMITTED AND YET SHARES THE SAME | | REVISION DATE. THERE WERE TWO (2) ALEXANDER PALMS SHOWN | | ON THE TREE ALTERATION PERMIT SET THAT WERE TO BE | | RELOCATED AND THEN REPLANTED AFTER CONSTRUCTION. THESE | | TWO (2) PALMS WERE NOT SHOWN ON THE MOST RECENT | | SUBMITTAL AND THREE (3) UNIDENTIFIED UNDERSTORY TREES | | WERE SHOWN. A PALM PLANTING DETAIL SHOWN ON THE | | ORIGINAL SET OF PLANS WAS MISSING FROM THE MOST RECENT | | SET. | | C. PURSUANT TO SECTION 94-444(B), WALLS OF THE DUMPSTER | | ENCLOSURE SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES | | PLANTED AT TWO FOOT INTERVALS. A HEDGE WAS SHOWN ON | | ONLY ONE SIDE OF THE PROPOSED ENCLOSURE. IT IS REQUIRED | | ON THREE (3) SIDES. | | D. ALL PROPOSED LIGHTING SHALL BE SHOWN ON THE | | LANDSCAPE PLAN TO AVOID CONFLICTS. | | E. PURSUANT TO SECTION 94-442(G), IN KEEPING WITH | | XERISCAPE GUIDELINES, THE PALMS THAT SURROUND THE PLAZA | | SHOULD BE UNDER PLANTED AND CONTAINED WITHIN A PLANT | | BED. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-09-23 |
|
|
Cont ID |
|
Sent By |
adavila |
Date |
2008-09-23 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
adavila |
Date |
2008-09-23 |
Time |
13:46 |
Sent To |
|
|
Notes |
2008-09-23 13:52:04 | PLANNING AND ZONING DEPARTMENT | | | | ***FAILED*** | | | | 1. APPROVAL OF A MINOR PD AMENDMENT TO THE WEST PALM | | BEACH CHRISTIAN CONVENTION CENTER COMMUNITY SERVICE | | PLANNED DEVELOPMENT (CSPD), AND OF A FORMAL SITE PLAN | | REVIEW ARE REQUIRED FOR THE PROPOSED ADDITION AND SITE | | WORK PRIOR TO OBTAINING A BUILDING PERMIT. AN | | APPLICATION SHALL BE SUBMITTED TO THE PLANNING AND | | ZONING DEPARTMENT. THE APPLICATION MAY BE OBTAINED FROM | | THE PLANNING AND ZONING DEPARTMENT'S WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN. | | | | COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC | | SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435. | | |
|
|
|