2008-09-19 16:42:17 | BUILDING PLAN REVIEW |
| PERMIT: 08090392 |
| ADD: 801 S. OLIVE AVE #1510 |
| CONT: THE CARPENTERS SON INC. |
| TEL: (561)452-2191 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 9-19-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE INDICATE |
| THIS INFORMATION ON THE PLANS. |
| |
| 3) STATE THE LEVEL OF ALTERATION ON THE PLANS PER 2004 |
| FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN OWNER |
| MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION |
| PURSUANT TO SECTIONS 303, 304 AND 305 OF THIS CODE. |
| |
| 4) THE DRAWINGS NEED TO INDICATE THE TYPE OF BUILDING |
| PER TABLE 601, THE USE AND OCCUPANCY PER CHAPTER 3 AND |
| THE HEIGHT OF THE BUILDING PER TABLE 503. |
| |
| 5) PROVIDE DRAWINGS CLEARLY SHOWING THE EXISTING FLOOR |
| PLAN AND A PROPOSED FLOOR PLAN WITH ALL THE CHANGES. |
| THE DRAWINGS SHALL INDICATE THE CORRECT ADDRESS OF THE |
| PROJECT. THE APPLICATION SHOWS UNIT 1510 AND THE FOUR |
| SHEETS OF THE PLANS SUBMITTED SHOW UNIT 1110. THE |
| SHEETS SUBMITTED ALSO SHOW TWO DIFFERENT UNIT NUMBERS; |
| ONE SET HAS UNIT 01 AND THE OTHER HAS UNIT 0, WHICH |
| UNIT IS IT? THE DRAWINGS SHALL CONTAIN A WALL LEGEND |
| WITH SYMBOLS TO IDENTIFY THE NEW WALLS AND THE EXISTING |
| WALLS TO AVOID CONFUSION. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISION OF THE |
| CODE. FBC 106.1.1 NOTE: THE PLANS DO NOT CLEARLY SHOW |
| ANY OPENING INTO THE DEN AREA, PLEASE CLARIFY. |
| |
| 6) FBC 106- THE PERSON TAKING RESPONSIBILITY FOR THE |
| DRAWINGS SHALL SIGN AND PRINT HIS/HER NAME ON EACH |
| SHEET OF THE DRAWINGS. IF THE PERSON IS A REGISTERED |
| ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS |
| OF THIS STATE, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS AS |
| REQUIRED PER FLORIDA STATUTES CHAPTER 471.025 AND |
| 481.221. |
| |
| 7) IF THE SPACE HAS A SPRINKLER SYSTEM, SHOW ON THE |
| CEILING PLANS HOW THE NEW WALLS AFFECT THE SYSTEM. IF |
| THE HEADS HAVE TO BE RELOCATED, SPRINKLER DRAWINGS MAY |
| BE REQUIRED. IF THERE IS NO CHANGE PLEASE INDICATE ON |
| THE PLANS. FBC 106.3.5.1.1(5) FS 553.79(2). |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| [email protected] |
| |