Plan Review Details - Permit 08090276
Plan Review Stops For Permit 08090276
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-12-18 Cont ID  
Sent By rmcdouga Date 2008-12-18 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2008-12-18 Time 08:08 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-25 Cont ID  
Sent By rmcdouga Date 2008-11-25 Time 08:51 Rev Time 0.00
Received By rmcdouga Date 2008-11-25 Time 08:51 Sent To P
Notes
2008-11-25 08:54:092004 FBC W/2007 REVISIONS
 NSFD
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS713
  
 2) SHOW COMPLIANCE WITH FBC R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.PROJECTIONS EXTENDING
 INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL
 HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION
 ON THE UNDERSIDE. THE ABOVE PROVISIONS SHALL NOT APPLY
 TO WALLS WHICH ARE PERPENDICULAR TO A LINE EXTENDING
 FROM THE POINT FROM WHICH THE SEPARATION DISTANCE HAS
 BEEN MEASURED RUNNING AND PARALLEL TO THE PROPERTY
 LINE. THE DISTANCE FROM SOME OF THE STRUCTURE'S WALLS
 TO THE PROPERTY LINES ARE LESS THAN SIX FEET. SUBMIT 2
 SURVEYS OR SITE PLANS THAT SPECIFY THE DISTANCES TO
 STRUCTURES ON ADJACENT PROPERTIES AT THESE LOCATIONS.
  
 3) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND LISTING
 INFORMATION FOR THE VENTLESS LOG GAS HEATER ON THE
 LANAI. A SEPARATE GAS PERMIT WILL BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By btrobaug Date 2008-09-26 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2008-09-25 Time 15:16 Sent To  
Notes
2008-09-26 13:50:172004 FBC W/2007 REVISIONS
 NSFD
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS713
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY 'C'
 PER FBC R301.2.1.4. THE BUILDING IS DIRECTLY ADJACENT
 TO OPEN AREAS OF EXPOSURE C TYPE TERRAIN FOR A DISTANCE
 OF MORE THAN 600 FEET. PLEASE REVISE PLANS. SEE SHEETS
 T1, A4 AND A5.
  
 3) SHOW COMPLIANCE WITH FBC R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.PROJECTIONS EXTENDING
 INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL
 HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION
 ON THE UNDERSIDE. THE ABOVE PROVISIONS SHALL NOT APPLY
 TO WALLS WHICH ARE PERPENDICULAR TO A LINE EXTENDING
 FROM THE POINT FROM WHICH THE SEPARATION DISTANCE HAS
 BEEN MEASURED RUNNING AND PARALLEL TO THE PROPERTY
 LINE. THE DISTANCE FROM SOME OF THE STRUCTURE'S WALLS
 TO THE PROPERTY LINES ARE LESS THAN SIX FEET. SUBMIT 2
 SURVEYS OR SITE PLANS THAT SPECIFY THE DISTANCES TO
 STRUCTURES ON ADJACENT PROPERTIES AT THESE LOCATIONS.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
  
 5) PLEASE REVISE THE WINDOW AND DOOR OPENING PRESSURES
 LISTED ON SHEETS A4 AND A5 TO EXPOSURE C. FBC R 301.2.1
  
 6) THE PLANS SPECIFY CONCRETE ROOF TILE ON SHEET A4 AND
 THE SECTION ON A6 SPECIFIES CLAY ROOF TILE. PLEASE
 CORRECT.
  
 7) SUBMIT 2 COPIES OF THE PRODUCT APPROVALS FOR THE
 ROOF COVERING THAT WILL BE INSTALLED. FAC RULE 9B-72
  
 8) SHEET A2 OF THE PLANS SPECIFIES 2" X 6" X 1/8" MULLS
 AT THE LIVING ROOM WINDOWS. THE PRODUCT APPROVALS THAT
 WERE SUBMITTED ARE FOR 2" X 6" X .250" (1/4") MULLIONS.
 PLEASE REVISE PLANS.
  
 9) SHEET A2 OF THE PLANS SPECIFIES 1" X 4" X 1/8" MULLS
 AT THE BREAKFAST ROOM WINDOWS. THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR 1" X 4" X .375" (3/8")
 MULLIONS. PLEASE REVISE PLANS.
  
 10) THE PRODUCT APPROVALS FOR THE 1X HEAVY WALL
 MULLIONS ARE MISSING THE UPPER PART OF THE INSTALLATION
 DRAWINGS AND TABLES. PLEASE SUBMIT COMPLETE DRAWINGS.
 FAC RULE 9B-72.
  
 11) PRODUCT APPROVALS FOR A MASONITE INTERNATIONAL DOOR
 FL# 4940 WERE SUBMITTED. PLEASE SPECIFY WHERE THIS DOOR
 WILL BE LOCATED. FBC R301.2.1
  
 12) THE PRODUCT APPROVAL NOA # 05-1129.11 FOR THE PGT
 C-740 CASEMENT WINDOWS IS EXPIRED. PLEASE SUBMIT THE
 NEW ONE, NOA# 08-0117.11. FAC RULE 9B-72
  
 13) THE PRODUCT APPROVAL NOA # 06-0807.07 FOR THE PGT
 FD101 OUTSWING FRENCH DOOR IS EXPIRED. PLEASE SUBMIT
 THE NEW ONE, NOA# 07-0629.10. FAC RULE 9B-72
  
 NOTE: IN ORDER TO AVOID ANY DELAYS IN GETTING THE
 PERMIT ISSUED, PLEASE REVIEW DESIGN PRESSURES OF ALL
 PRODUCTS REQUIRING PRODUCT APPROVAL TO MAKE SURE THEY
 WILL BE ADEQUATE FOR THE HIGHER COMPONENT AND CLADDING
 PRESSURES OF EXPOSURE CATEGORY C.
 NOTE: PLEASE RESUBMIT THE SHEETS FROM THE OLD PLANS
 WITH THE IMPACT FEE STAMPS ON THEM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-20 Cont ID  
Sent By btrobaug Date 2008-11-20 Time 09:09 Rev Time 0.00
Received By btrobaug Date 2008-11-20 Time 08:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-18 Cont ID  
Sent By btrobaug Date 2008-09-18 Time 10:03 Rev Time 0.00
Received By btrobaug Date 2008-09-17 Time 15:47 Sent To Z
Notes
2008-09-17 15:53:07 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 2} THE A/C CONDENSERS LOCATIONS ON SHEET A7 DO NOT
 MATCH THE LOCATIONS ON SHEET M-1. PLEASE CORRELATE.
  
 3} ON THE PANEL SCHEDULE, SHEET A7, THE MAXIMUM OCP FOR
 AHU'S #1 AND #3, EXCEEDS THE MAXIMUM RECOMMENDED BY THE
 MANUFACTURER ON SHEET M-1, ALSO THOSE AIR HANDLERS HEAT
 STRIPS ARE SPECIFIED @7500 WATTS AND ARE LISTED ON THE
 PANEL SCHEDULE AS 10000WATTS, CORRELATE WITH THE
 MECHANICAL MANUFACTURERS SPEC'S.
  
 4} CONDENSING UNIT #4 MUST HAVE A RECEPTACLE FOR
 SERVICING PER 210.63.
  
 5} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (2) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (3) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY?NEW 11-18-07 LOCATE DETECTORS ON THE PLAN.
 NOTE: MAY BE COMBINATION SMOKE/CARBON MONOXIDE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-12-11 Cont ID  
Sent By adarroug Date 2008-12-11 Time 10:38 Rev Time 0.00
Received By adarroug Date 2008-12-11 Time 10:38 Sent To Z
Notes
2008-12-11 10:38:32TO "Z" BOX/RESUB--LANDSCAPE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 15:48 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 15:48 Sent To Z
Notes
2008-11-06 15:48:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-26 Cont ID  
Sent By rmcdouga Date 2008-09-26 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2008-09-12 Time 15:02 Sent To  
Notes
2008-09-12 15:03:07TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-12-12 Cont ID  
Sent By rkussner Date 2008-12-12 Time 13:55 Rev Time 0.00
Received By rkussner Date 2008-12-12 Time 13:55 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-11-14 Cont ID  
Sent By rkussner Date 2008-11-14 Time 17:07 Rev Time 0.00
Received By rkussner Date 2008-11-14 Time 17:07 Sent To PC
Notes
2008-11-14 17:38:41***LANDSCAPE REVIEW FAILED***
  
 1. PROVIDE THE LOCATION OF THE STREET TREES ON THE
 LANDSCAPE PLAN. IF NONE EXIST, THEY SHALL BE ADDED.
  
 2. THE LANDSCAPE CALCULATIONS INDICATE THAT (9) TREES
 HAVE BEEN PROVIDED BUT ONLY (8) ARE SHOWN.
  
 3. FIVE POINTS FOR THE DESIGN OPTIONS HAVE BEEN TAKEN
 FOR A MOISTURE SENSING CONTROLLER. IN ORDER TO TAKE
 CREDIT FOR THIS, YOU MUST IDENTIFY THE EQUIPMENT TO BE
 USED.
  
 4. IN KEEPING WITH XERISCAPE PRINCIPLES, STAFF
 RECOMMENDS THAT THE SOD BETWEEN THE DRIVEWAY AND FRONT
 ENTRANCE SHALL BE ELIMINATED. THE AREA SHALL BE PLANTED
 WITH SHRUBS AND GROUND COVER.
  
 IF YOU HAVE QUESTIONS REGARDING THESE COMMENTS, PLEASE
 CONTACT ROBERT KUSSNER @ (561) 822-1462,

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-12-18 Cont ID  
Sent By rmcdouga Date 2008-12-18 Time 08:30 Rev Time 0.00
Received By rmcdouga Date 2008-12-18 Time 08:30 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-11-22 Cont ID  
Sent By rregueir Date 2008-11-22 Time 10:13 Rev Time 0.00
Received By rregueir Date 2008-11-22 Time 09:49 Sent To B
Notes
2008-11-22 10:13:10MECH REVIEW STATUS CHANGED TO FAIL.
  
 NOTE: EVEN THOUGH MECH PLANS PASSED PREVIOUS REVIEW,
 THEY ARE NOW IN FAIL STATUS. THE HOUSE ARCHITECTURAL
 FLOOR PLAN HAS BEEN REVISED TO SHOW THE GUEST ROOM AS
 ACCESSIBLE FROM THE MAIN HOUSE WITH ONE BATHROOM IN
 THIS AREA. PAGE M1 STILL SHOWS THEM SEPARATED WITH TWO
 BATHROOMS, TWO EXHAUST FANS AND THE RETURN GRILL IS
 SHOWN IN A LOCATION THAT WOULD BE OUTSIDE THE HOUSE
 ACCORDING TO ARCHITECTURAL PLANS. PLEASE COORDINATE
 MECHANICAL AND ARCHITECTURAL PLANS, SHOWING ANY CHANGES
 TO THE MECHANICAL SYSTEMS WHICH ARE NEEDED AS A RESULT
 OF THE RE-DESIGN OF THIS AREA AND RESUBMIT FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-11-22 Cont ID  
Sent By tgordon Date 2008-09-15 Time 11:48 Rev Time 1.30
Received By rregueir Date 2008-09-15 Time 11:48 Sent To Z
Notes
2008-11-22 10:16:00THIS REVIEW ORIGINALLY PASSED BY TOM GORDON. STAUS HAS
 BEEN CHANGED TO FAIL DUE TO CHANGES IN ARCHITECTURAL
 PLANS BETWEEN FIRST AND 2ND REVIEWS. SEE COMMENTS ON
 2ND MECHANICAL REVIEW DATED 11/22/08.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-12-03 Cont ID  
Sent By kstevens Date 2008-12-03 Time 12:19 Rev Time 0.00
Received By kstevens Date 2008-12-03 Time 12:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By mperson Date 2008-09-17 Time 11:21 Rev Time 0.00
Received By mperson Date 2008-09-17 Time 11:21 Sent To Z
Notes
2008-09-17 12:00:25PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A6, SANITARY PLUMBING RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A2. AT A MINIMUM THE
 SANITARY RISER SHOULD REFLECT THE FLOOR PLAN. PLEASE
 CORRECT THE FOLLOWING PER THE FBC-2004 PLUMBING CODE
 SECTION 701.1 SCOPE.
  
 A} UTIL. WASHING MACHINE AND LAUNDRY TRAY ARE BEING
 INDICATED IN THE WRONG PLACE.
  
 B} BATH 3, LAVATORY IS MISSING FROM THE SANITARY RISER.
  
 C} POWDER ROOM BATH IS BEING SHOWN IN THE WRONG PLACE
 DUE TO THE LOCATION OF ITS BRANCH FITTING OFF THE MAIN.
 CLEARLY INDICATE THE REQUIRED OFFSET TO THE POWDER ROOM
 DUE TO ITS BRANCH FITTING LOCATION.
  
 D} HER BATH, LAVATORY IS BEING INDICATED IN THE WRONG
 PLACE.
  
 E} MORNING BAR SINK BY THE GUEST SUITE IS MISSING FROM
 THE SANITARY RISER.
  
 2. SHEET A6, SANITARY RISER: THE KITCHEN DOUBLE BOWL
 SINK WITH DISPOSAL AND DISHWASHER ARE BEING INDICATED
 WITH A WASTE ARM AND VENT THRU THE ROOF. PLEASE KNOW
 THAT PER TABLE 906.1, MAXIMUM DISTANCE OF FIXTURE TRAP
 FROM VENT WITH AN 1-1/2 TRAP AND 2" WASTE ARM CAN ONLY
 BE 6' FROM THE VENT. IT IS SUGGESTED THAT THE DOUBLE
 BOWL SINK WITH DISPOSAL AND DISHWASHER BE VENTED WITH
 AN AIR ADMITTANCE VALVE (STUDOR VENT) PER FBC-2004
 PLUMBING SECTION 917, AIR ADMITTANCE VALVES. ALSO
 PLEASE CLEARLY INDICATE THE DISHWASHER DRAIN TO
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER. PER FBC-2004 PLUMBING SECTION 802.1.6
 DOMESTIC DISHWASHING MACINES.
  
 3. SHEET A2 SANITARY PLUMBING RISER INDICATES BUILDING
 SEWER DISCHARGE TO A SEPTIC TANK. PLEASE DELETE "SEPTIC
 TANK" AND ADD IN ITS PLACE "SEWER SYSTEM". PER
 MUNICIPAL CODE SECTION 90-123 USE OF SANITARY
 SEWERS.(C) SEPTIC TANKS ARE PROHIBITED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-12-18 Cont ID  
Sent By lfranco Date 2008-12-18 Time 10:54 Rev Time 0.00
Received By lfranco Date 2008-12-18 Time 10:54 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-11-14 Cont ID  
Sent By rregueir Date 2008-11-22 Time 10:16 Rev Time 0.00
Received By lfranco Date 2008-11-14 Time 18:00 Sent To  
Notes
2008-11-14 18:01:11PLANNING AND ZONING: **** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PURSUANT TO SECTION 94-72 THE PROPERTY IS WITHIN THE
 IBIS RPD, WITH THE UNDERLYING SINGLE FAMILY LOW DENSITY
 (SF7) RESIDENTIAL ZONING DISTRICT. THEREFORE, PURSUANT
 TO SECTION 94-611- DWELLING UNIT - ALL ROOMS IN THE
 DWELLING UNIT MUST BE ACCESSIBLE FROM THE INTERIOR OF
 THE UNIT. THE GUEST ROOM DOES NOT COMPLY.
  
 RESUBMITTAL: SHEET M-1 STILL SHOWS OLD FLOOR PLAN FOOT
 PRINT WITH NO INTERIOR CONNECTION TO THE GUEST ROOM.
 REVISE ACCORDINGLY.
  
 3. ADDRESS LANDSCAPE COMMENTS FROM ROBERT KUSSNER.
  
 IF YOU HAVE ADDITIONAL QUESTIONS, PLEASE CONTACT ME AT
 THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By lfranco Date 2008-09-24 Time 11:49 Rev Time 0.00
Received By lfranco Date 2008-09-24 Time 11:49 Sent To  
Notes
2008-09-24 11:57:48PLANNING AND ZONING: **** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THIS LOT #25 IS NOT PART OF THE "MODIFIED ZERO" LOTS
 AS NOTED ON PB CASE NO. 993SSS MINOR PD AMENDMENT.
 THEREFORE, THE SINGLE FAMILY HOME SHALL MEET THE
 MINIMUM SETBACK REQUIREMENTS OF EIGHT (8) FEET ON THE
 NON-ZERO LOT LINE.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. AS PER SECTION
 94-305(B)(4) OF THE ZONING CODE ("ZLDR"): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 4. PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
  
 PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED
 OFF-STREET PARKING SPACES FOR LESS THAN FOUR
 RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE
 PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED
 PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE
 LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT
 YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN
 THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH,
 NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION
 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO
 PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE.
  
 PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE
 SURFACES (EXISTING AND PROPOSED) LOCATED WITHIN THE
 FRONT YARD (FROM FRONT PROPERTY LINE TO THE FRONT
 BUILDING FACADE).
  
 5. PURSUANT TO SECTION 94-72 THE PROPERTY IS WITHIN THE
 IBIS RPD, WITH THE UNDERLYING SINGLE FAMILY LOW DENSITY
 (SF7) RESIDENTIAL ZONING DISTRICT. THEREFORE, PURSUANT
 TO SECTION 94-611- DWELLING UNIT - ALL ROOMS IN THE
 DWELLING UNIT MUST BE ACCESSIBLE FROM THE INTERIOR OF
 THE UNIT. THE GUEST ROOM DOES NOT COMPLY.
  
 IF YOU HAVE ADDITIONAL QUESTIONS, PLEASE CONTACT ME AT
 THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  