Plan Review Details - Permit 08090247
Plan Review Stops For Permit 08090247
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-16 Time 14:08 Rev Time 0.00
Received By jwitmer Date 2009-12-16 Time 13:45 Sent To  
Notes
2009-12-16 13:45:29MASTER:08090247
 REVISION: 09120104
  
 REVISION# 5 11-02-09 THE REMOVAL OF THE 2ND STORY
 BUILD-OUT FROM SCOPE OF PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2009-10-28 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 16:15 Rev Time 1.00
Received By jwitmer Date 2009-10-28 Time 16:15 Sent To  
Notes
2009-10-28 16:26:03BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
 OCT. 28/2009
  
 LETTER OF OCT 21/2009 IN REGARDS TO FOAM PLASTIC WALL
 INSULATION, PLEASE REFER TO SECTION :
 2004 FBC- BUILDING 2603.5.2 THERMAL BARRIER.
 ANY FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 BUILDING INTERIOR BY A THERMAL BARRIER MEETING THE
 PROVISIONS OF SECTION 2603.4, UNLESS SPECIAL APPROVAL
 IS OBTAINED ON THE BASIS OF SECTION 2603.8.
  
  
 PLEASE REVIEW THE MECHANICAL PLANS THE AREA ABOVE THE
 CEILING IS CONSIDERED A PLENUM:
 2004 FBC MECHANICAL 602.2.1 MATERIALS EXPOSED WITHIN
 PLENUMS.
 EXCEPT AS REQUIRED BY SECTIONS 602.2.1.1 THROUGH
 602.2.1.5, MATERIALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2004 MECHANICAL 602.2.1.5 FOAM PLASTIC INSULATION.
 FOAM PLASTIC INSULATION USED AS WALL OR CEILING FINISH
 IN PLENUMS SHALL EXHIBIT A FLAME SPREAD INDEX OF 75 OR
 LESS AND A SMOKE-DEVELOPED INDEX OF 450 OR LESS WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 AND SHALL ALSO
 COMPLY WITH SECTION 602.2.1.5.1, 602.2.1.5.2 OR
 602.2.1.5.3.
 602.2.1.5.1 SEPARATION REQUIRED.
 THE FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 PLENUM BY A THERMAL BARRIER COMPLYING WITH SECTION
 2603.4 OF THE FLORIDA BUILDING CODE, BUILDING.
 602.2.1.5.2 APPROVAL.
 THE FOAM PLASTIC INSULATION SHALL BE APPROVED BASED ON
 TESTS CONDUCTED IN ACCORDANCE WITH SECTION 2603.8 OF
 THE FLORIDA BUILDING CODE, BUILDING .
 602.2.1.5.3 COVERING.
 THE FOAM PLASTIC INSULATION SHALL BE COVERED BY
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF NOT LESS THAN 0.0160 INCH (0.4 MM).
  
 2004 MECANICAL 603.8 CAVITIES OF THE BUILDING
 STRUCTURE.
 CAVITIES IN FRAMED SPACES, SUCH AS DROPPED SOFFITS AND
 WALLS, SHALL NOT BE USED TO DELIVER AIR FROM OR RETURN
 AIR TO THE CONDITIONING SYSTEM UNLESS THEY CONTAIN AN
 AIR DUCT INSERT WHICH IS INSULATED IN ACCORDANCE WITH
 TABLE 13-410.1.ABC.2.2 OR TABLE 13-610.1.ABC.2.1 OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE, BUILDING AND
 CONSTRUCTED AND SEALED IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 603.1 APPROPRIATE FOR THE DUCT
 MATERIALS USED.
 EXCEPTION: RETURN AIR PLENUMS.
 CAVITIES DESIGNED FOR AIR TRANSPORT SUCH AS MECHANICAL
 CLOSETS, CHASES, AIR SHAFTS, ETC. SHALL BE LINED WITH
 AN AIR BARRIER AND SEALED IN ACCORDANCE WITH SECTION
 603.9 AND SHALL BE INSULATED IN ACCORDANCE WITH TABLE
 13-410.1.ABC.2.2 OR TABLE 13-610.1.ABC.2.1 OF CHAPTER
 13 OF THE FLORIDA BUILDING CODE, BUILDING.
 BUILDING CAVITIES WHICH WILL BE USED AS RETURN AIR
 PLENUMS SHALL BE LINED WITH A CONTINUOUS AIR BARRIER
 MADE OF DURABLE NON-POROUS MATERIALS. ALL PENETRATIONS
 OF THE AIR BARRIER SHALL BE SEALED WITH A SUITABLE
 LONG-LIFE MASTIC MATERIAL.
 EXCEPTION: SURFACES BETWEEN THE PLENUM AND CONDITIONED
 SPACES FROM WHICH THE RETURN/MIXED AIR IS DRAWN.
 BUILDING CAVITIES BENEATH A ROOF DECK THAT WILL BE USED
 AS RETURN AIR PLENUMS SHALL HAVE AN INSULATED ROOF WITH
 THE INSULATION HAVING AN R-VALUE OF AT LEAST R-19.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-09-03 Cont ID  
Sent By jwitmer Date 2009-09-03 Time 13:59 Rev Time 0.70
Received By jwitmer Date 2009-09-03 Time 13:09 Sent To  
Notes
2009-09-03 13:31:01BLDG REV# 4 DATED 7-30-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-16 Cont ID  
Sent By jwitmer Date 2009-07-16 Time 08:29 Rev Time 2.22
Received By jwitmer Date 2009-07-16 Time 08:29 Sent To  
Notes
2009-07-16 08:46:07BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JUNE 16/09
 APPROVED WITH BUILDING PROVISO:
  
 PLEASE REVIEW ENGINEERINGS NOTE FOR AIR RIGHT EASEMENT,
 THERE ARE TWO DOORS THAT APPEAR TO CROSS THE PROPERTY
 LINE AS SHOWN, DOOR# 101-1 AND DOOR 102-1 A PAIR OF
 FRENCH DOORS.SECTION 3202.2 DOORS AND WINDOWS SHALL NOT
 OPEN OVER THE RIGHT OF WAY. PLEASE PROVIDE COMPLIANCE
 WITH AIR RIGHTS EASEMENT FOR OBJECTS WITHIN THE RIGHT
 OF WAY OR REVISE PLANS TO NOT HAVE SUCH VIOLATION. THE
 PAIR OF DOORS MAY BE WITHIN THE LEGAL LIMITS IF ONE
 DOOR IS INACTIVE AND THIS IS THE DOOR THAT WOULD HAVE
 CROSSED THE PROPERTY LINE THEN ONLY DOOR# 101-1 WOULD
 NEED TO SHOW COMPLIANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-01 Cont ID  
Sent By jwitmer Date 2009-04-01 Time 11:55 Rev Time 0.77
Received By jwitmer Date 2009-04-01 Time 11:55 Sent To  
Notes
2009-04-01 11:57:54BUILDING: PLANS READY FOR PERMIT
  
 ROOFING PRODUCT APPROVAL:
 GAF EVERGUARD TPO SINGLE PLY ROOFING SYSTEM OVER WOOD
 DECK
 NOA 04-0723.02
 DECK TYPE 1I WOOD INSULATED
 DECK DESCRIPTION 19/32
 ALL LAYERS OF INSULATION ARE ADHERED TO A MECHANICALLY
 ATTACHED ANCHOR SHEET. MEMBRANE FULLY OR PARTIALLY
 ADHERRED.
 MAXIMUM DESIGN PRESSURE: -60 PSF LIMITATION# 7.
 RAS 117 CALCULATIONS SUBMITTED!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-02-02 Cont ID  
Sent By jwitmer Date 2009-02-02 Time 15:40 Rev Time 0.00
Received By jwitmer Date 2009-02-02 Time 15:22 Sent To  
Notes
2009-02-02 15:40:28BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 DENIED.
  
 PLANS APPEAR TO BE CODE COMPLIANT SPOKE WITH AL
 PHILLIPS ABOUT THE ROOFING PRODUCT APPROVAL:
  
 GAF EVERGUARD TPO SINGLE PLY ROOFING SYSTEM OVER WOOD
 DECK
 NOA 04-0723.02
 DECK TYPE 1I WOOD INSULATED
 DECK DESCRIPTION 19/32
 ALL LAYERS OF INSULATION ARE ADHERED TO A MECHANICALLY
 ATTACHED ANCHOR SHEET. MEMBRANE FULLY OR PARTIALLY
 ADHERRED.
 MAXIMUM DESIGN PRESSURE: -60 PSF LIMITATION# 7.
  
 REQUIRES INHANCED FASTENING IN ZONE# 3 TO -89.
  
 NAT HEALY TO BRING IN INHANCED FASTENING BEFORE THE END
 OF THIS PLAN REVIEW CYCLE, THEN I CAN PASS AND STAMP
 SHEETS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 MEMBER OF BOAF, THE BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA: PROTECTING LIVES AND PROPERTY SINCE 1953.
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. UNDER FLORIDA STATE STATUTE SB 80, E-MAIL
 ADDRESSES ARE PUBLIC RECORDS.WRITTEN COMMUNICATIONS TO
 OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE
 PUBLIC RECORD, AVAILABLE TO THE PUBLIC UPON REQUEST.
 YOUR E-MAIL COMMUNICATIONS ARE THEREFORE SUBJECT TO
 PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By kstevens Date 2008-10-02 Time 10:28 Rev Time 8.55
Received By jwitmer Date 2008-10-02 Time 10:28 Sent To  
Notes
2008-10-02 12:14:18BUILDING PLAN REVIEW
 PERMIT: 08090247
 ADD: 501 N ROSEMARY AVE
 CONT: NUJAK DEVELOPMENT
 TEL: (863)686-1565
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) SHEET A0.00 CODE ANALYSIS INDICATES THIS BUILDING IS
 TO BE A TYPE III-B BUILDING AND A LEVEL III ALTERATION,
 MIXED OCCUPANCY WITH A BUSINESS OCCUPANCY FIRST FLOOR
 AND R-2 RESIDENCY SECOND FLOOR.
 SHEET A-1.01 ALSO INDICATES THE PROPERTY LINE ON THE
 WEST SIDE OF THE PROPERTY TO BE APPROXIMATELY 3'-0"
 AWAY. THE SURVEY PROVIDES A DIMENSION AT THE NORTHWEST
 CORNER OF THE BUILDING INDICATING
 A DISTANCE OF 2.90' AWAY FROM THE PROPERTY LINE. LEVEL
 III ALTERATIONS SECTION 705.1 THE MEANS OF EGRESS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 605 EXCEPT AS
 MODIFIED IN SECTIONS 705.2 AND 705.3. UNDER LEVEL II
 SECTION 605.1 THE REQUIREMENTS OF THIS SECTION SHALL BE
 LIMITED TO WORK AREAS THAT INCLUDE EXITS OR CORRIDORS
 SHARED BY MORE THAN ONE TENANT WITHIN THE WORK AREA IN
 WHICH LEVEL 2 ALTERATIONS ARE BEING PREFORMED, AND
 WHERE SPECIFIED THEY SHALL APPLY THROUGHOUT THE FLOOR
 ON WHICH THE WORK AREAS ARE LOCATED OR OTHERWISE BEYOND
 THE WORK AREA.
  
 2A) WITH THIS BEING A LEVEL III ALTERATION THE EXTERIOR
 STAIRWAY BEING REPAIRED AND RELOCATED BASICALLY IN THE
 SAME LOCATION , PLEASE PROVIDE COMPLIANCE WITH 1022.5 .
 EXTERIOR EXIT STAIRWAYS SHALL BE LOCATED IN ACCORDANCE
 WITH SECTION 1023.3.
 1023.3 EXIT DISCHARGE LOCATION.
 EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE
 LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT
 LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS
 THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE
 PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE
 SEPARATION DISTANCE.
  
 2B) THE SECOND ISSUE WITH NOT KNOWING THE DISTANCE FROM
 THE PROPERTY LINE AT THE SECOND FLOOR DOOR OPENING IS
 IN TABLE 704.8 FOR UNPROTECTED OPENINGS 0-3-0? ZERO
 OPENINGS IN THE WALL LINE.
  
 2C) SHEET A-1.03 INDICATE A 5?X5? DOWNSPOUT, THE SITE
 PLAN INDICATES A 6?-0? HIGH SECURITY FENCE ALONG THE
 SAME PROPERTY LINE AND THE SURVEY INDICATES FROM THE
 BUILDING TO PROPERTY LINE A DISTANCE OF 2.90?. HOW WILL
 SECTION 1009.1EXCEPTION# 1 REQUIRING A 36? WIDE STAIR?
  
 2D) THE OTHER ISSUE IS WITH THE 5?X5? DOWNSPOUT, HOW
 WILL SECTION 1009.11.7 PROJECTIONS INTO THE REQUIRED
 WIDTH AT EACH HANDRAIL SHALL NOT EXCEED 4.5 INCHES AT
 OR BELOW THE HANDRAIL HEIGHT. NOTE HANDRAILS ARE TO BE
 CONTINUOUS SEE 1009.11.4 CONTINUITY.
  
 2E) THE PLANS FAIL TO INDICATE HANDRAILS AT EACH SIDE
 OF THE STAIRS. 1009.11.
  
 3) SHEET A-1.01 DOOR# 115-1 MACHINE ROOM, AGAIN THIS
 NEW ADDITION WALL LINES UP WITH THE EXISTING WALL THAT
 IS 2.90? FROM THE PROPERTY LINE. TABLE 704.8 THAT DOES
 NOT ALLOW OPENINGS UNTIL GRATER THAN 5.0? FROM THE
 PROPERTY LINE FOR UNPROTECTED OPENINGS. ALSO NOTE THIS
 DOOR NEEDS TO BE A 1-HR RATED DOOR AS TO 3006.4. THE
 ONE HR RATING WOULD ALLOW UNDER PROTECTED OPENINGS 15%
 ALLOWABLE OPENINGS AT DISTANCES OF 3?-0? AND GREATER.
 THE OTHER ISSUE IS THE DOOR SWING IS OVER THE ALLOWABLE
 EGRESS PATH. 1008.1.8.8.
  
 4) SHEET A-1.02 WINDOW OPENING 18A IS UNPROTECTED, IS
 AGAIN LESS THAN 5?-0? FROM THE PROPERTY LINE AND NOT
 ALLOWED TABLE 704.8.
  
 5) SHEET A-3.01 WEST ELEVATION INDICATES A LOUVERS ON
 THIS ELEVATION AGAIN UNPROTECTED OPENINGS WOULD NOT BE
 ALLOWED WITH UNPROTECTED OPENINGS, PLEASE SEE TABLE
 704.8 FOR UNPROTECTED OPENINGS AND FOR PROTECTED
 OPENINGS.
  
 6) THIS BUILDING DOES NOT PROVIDE ANY INFORMATION AS TO
 FIRE SPRINKLERS, SO IT IS ASSUMED TO BE AN
 UN-SPRINKLERED BUILDING. WITH THE R-2 OCCUPANCY AND THE
 ADDITION OF THE ELEVATOR THE REQUIREMENT FOR A AREA OF
 RESCUE ASSISTANCE NECESSARY. PLEASE REVIEW ALL THE
 REQUIREMENTS OF 11-4.3.11(1-3).
  
 6A) PLEASE INDICATE IF THE AREA OF RESCUE ASSISTANCE
 WILL BE LOCATED ON THE INTERIOR OF THE BUILDING OR IF
 IT WILL BE LOCATED ON THE EXTERIOR 2ND FLOOR LANDING OF
 THE BUILDING, AND NEEDING TO HAVE FIRE RATED WINDOWS
 AND DOORS. IN EITHER CASE PLEASE PROVIDE THE REQUIRED
 CLEAR FLOOR SPACE REQUIRED FOR THE AREA OF RESCUE
 ASSISTANCE AND THE MEANS OF EGRESS
  
 6B) PLEASE ALSO TAKE NOTE OF THE REQUIRED 48? CLEAR
 BETWEEN HANDRAILS,
 11-4.3.11.3.
  
 7) SHEET A-1.02 THE SECOND STORY LANDING INDICATES A
 SCUPPER LOCATED AT FLOOR LEVEL TO DRAIN WATER FROM THE
 LANDING. THE WATER THAT DRAINS FROM THE SCUPPER LANDS
 DIRECTLY ON TO THE STAIRS BELOW, PLEASE PROVIDE
 COMPLIANCE WITH 1009.5.2 OUTDOOR CONDITIONS.
  
 8) SHEET A-1.03 ROOF PLAN INDICATES ?GAF LIBERTY OR
 APPROVED EQUAL?, 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 9) SHEET A-4.01 S-3.02 BOTH INDICATE A NEW SECOND STORY
 EPICORE CONCRETE PRE-ENGINEERED FLOOR SYSTEM, PLEASE
 PROVIDE ADDITIONAL INFORMATION ARE SHOP DRAWINGS BEING
 CREATED, INDICATING OF SPANS, LOADS TO BE IMPOSED,
 REINFORCING AND SHORING. 1905, 1907.
  
 10) PLEASE PROVIDE HOURLY RATING FOR THE EPICORE
 CONCRETE FLOOR SYSTEM, A 2HR FIRE RATING WILL BE
 REQUIRED BETWEEN THE R-2 OCCUPANCY AND BUSINESS
 OCCUPANCY BELOW. SEE TABLE 302.3.2& 712.4, ALSO PROVIDE
 FIRE RESISTANCE RATED ASSEMBLIES FOR THE PENETRATION OF
 THE SECOND STORY FLOOR ASSEMBLIES, 712.4.1.
  
 11) PLANS FAIL TO PROVIDE FLOOR/CEILING ASSEMBLIES
 SOUND RATING AS REQUIRED BY 1207.3. STRUCTURE-BORNE
 SOUND. FLOOR/ CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL
 HAVE AN IMPACT INSULATION CLASS RATING OF NOT LESS THAN
 50(45IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 12) SHEET A-1.02 WALL TYPE# 8 FAILS TO PROVIDE A STC
 RATING OF 50, 1207.2 AIR-BORNE SOUND.
  
 13) SHEET A-2.01 SECOND STORY CORRIDOR REFLECTED
 CEILING PLAN DOES NOT INDICATE THE EXIT SIGNS , 1006.3.
  
 14) PLANS S-1.01 INDICATE THE USE OF HELICAL PIER UNDER
 PINNING OF FOUNDATION, PLEASE PROVIDE SOILS REPORT .
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 15) SHEET S-0.01 IS USING THE WRONG VERSION OF THE
 ASCE-7-05.
 2004 FBC 1609.1.1 & CHAPTER 35 REFERENCED STANDARDS
 RECOGNIZES ASCE 7-02 . ALSO 1603.1.4 WIND DESIGN DATA.
  
 16) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:\
 16A) SINGLE HUNG WINDOWS
 16B) FIXED, STOREFRONT
 16C) MULLIONS
 16D) EXTERIOR GLAZED DOORS
 16E) EXTERIOR METAL DOORS
 16F) EXTERIOR LOUVER DOORS
 16G) WALL LOUVERS
 16H) LINTELS
 16I) ROOFING ASSEMBLIES, FLAT ROOF, UNDERLAYMENT?S,
 TILE AND ADHESIVES
  
 17) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 19) THE INPUT DATA REPORT FROM THE ENERGY CALCS DOES
 NOT MATCH THE PLANS, THE COUNT ON THE WINDOWS AND THE
 SQUARE FOOTAGE ARE OFF AND THE DOOR TYPE AND DOOR COUNT
 DOES NOT MATCH THAT OF THE PLANS. THERE ARE A TOTAL OF
 5 DOORS THAT LEAD INTO THE BUSINESS OFFICE PLEASE
 CORRECT. MISSING NORTH DOOR 101-2 AND PAIR OF DOORS
 102-1.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-04-03 Cont ID  
Sent By dpalmer Date 2009-04-03 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2009-04-03 Time 08:41 Sent To  
Notes
2009-04-03 08:43:16PLANS REMOVED FROM ANA APPONTE'S OFFICE, REVIEWED AND
 STAMPED ELECTRICAL SHEETS. PLANS TAKEN BACK TO ANA'S
 OFFICE AND PLACED BACK ON ANA'S CHAIR. E-MAILED SENT TO
 CONFIRM THE REMOVAL AND RETURN OF PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-03-29 Cont ID  
Sent By dpalmer Date 2009-03-29 Time 10:56 Rev Time 0.00
Received By dpalmer Date 2009-03-29 Time 10:08 Sent To  
Notes
2009-03-29 10:56:34** DENIED REVIEW **
 3RD REVIEW
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW, THE SYSTEM PER
 FBC 3006.2 IS NOT ON ELECTRICAL PLANS. THE RESPONSE
 LETTER MENTIONS TO SEE NOTE #1 IN LETTER HOWEVER THAT
 NOTE #1 WAS SPECIFIC TO CIRCUIT H-8 FROM PREVIOUS
 REVIEW.
 THIS HAS BEEN NOTED IN THE LAST THREE REVIEWS. WHERE IS
 THE DEDICATED CIRCUITING? WHERE THESE ON THE PANEL ARE
 SCHEDULES AS DEDICATED CIRCUITS?
 THE ONLY REVISION TO THIS NOW IS CIRCUIT H-38 WHICH IS
 NOT DEDICATED FOR THE FAN. IT CAN NOT BE ON WITH ANY
 OTHER DEVICES.
 THE SYSTEM NEEDS TO BE INDEPENDENT.
  
 ** A SEPARATE INFORMATIONAL; PLEASE TAKE A LOOK AT 2004
 ASME-17 FOR ELEVATOR CODE REQUIREMENTS. THERE ARE
 SUBSTANTIAL CHANGES WHICH WILL AFFECT THIS PROJECT.
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT
 COMPLETE WITH ALL ELECTRICAL ITEMS ON PLANS IN THE
 INPUT DATA REPORT. MANY EXAMPLES WERE GIVEN ON PREVIOUS
 REVIEWS HOWEVER THE IDR IS STILL MISSING ELECTRICAL
 ITEMS.
 AN EXAMPLE: THERE IS A 12KW ELECTRIC WATER HEATER ON
 PLANS YET THE IDR IS BLANK. ANOTHER WOULD BE THE HW
 PIPING WHICH GOES ALONG WITH THIS.
 THESE ARE MINIMUMS IN THE CODE.
 PLEASE CORRELATE.
 13-412.1.ABC.4, 13-412, 13-400.B.3 ETC
  
 *** KEEP IN MIND THERE MAY BE OTHER BUILDING COMPONENTS
 WHICH ARE NOT IN THE IDR WHICH MAY BE NOTED BY OTHER
 TRADES.
  
 3) NOTE: SERVICE HAS BEEN REVISED. NEED TO SHOW LOAD
 CALCULATIONS TO BE SHOWN FOR THE NEW 800AMP MAIN.
 PLEASE ALSO INCLUDE LOAD ON THE HOUSE METER. THE
 ELEVATOR IS SHOWN BEING TAPPED FROM THE 400AMP METER
 ALONG WITH THE HOUSE PANEL. THE ONLY LOAD SHOWN FOR THE
 HOUSE METER IS THE LOAD ON THE HOUSE PANEL.
 NEC220
  
 4) NOTE: PLEASE BE SURE WHEN SEALING THE PLANS ( SEE
 NEW SHEETS) THE SEAL IS CLEAR AND VISIBLE. THE NEW
 SHEETS IN SETS ARE VERY FAINT AND SOME CAN NOT BE SEEN
 EVEN USING LEAD RUB.
 FS 471.0221.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-09 Cont ID  
Sent By dpalmer Date 2009-02-09 Time 09:49 Rev Time 0.00
Received By dpalmer Date 2009-02-06 Time 16:59 Sent To  
Notes
2009-02-09 09:50:04** DENIED 2ND REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
  
 1) NOTE: PLEASE SEE THE CIRCUITING IN THE ELEVATOR
 MACHINE ROOM AND ELEVATOR ARE SHOWN NOW ON THE SAME
 CIRCUIT FOR H-8. PANEL SCHEDULE STATES RECEPTS/LIGHTS
 FOR ELEVATOR PIT HOWEVER BASED ON THE PLANS THESE ARE
 BEING SHARD INTO OTHER AREAS WHICH IS NOT PERMITTED.
 PLEASE SEE 680.22-680.24. DEDICATED CIRCUITS ARE
 REQUIRED FOR EACH OF THE SPACES AS LISTED INCLUDING FOR
 THE ELEVATOR CAR ITSELF.
 PLEASE SEE THE NEXT COMMENT AS THIS IS AFFECT BY THE
 SAME NOTE.
  
 2) NOTE: PLEASE SEE FBC 3006.2 WITH THE REQUIRED
 INDEPENDENT SYSTEM FOR THE ELEVATOR MACHINE ROOM. THIS
 WOULD REQUIRE DEDICATED CIRCUITING AS NOTED ABOVE IN
 COMMENT #1. ( NOTED PREVIOUS REVIEW )
  
 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS
 NOT BEEN MET.
  
 A) THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS
 SUBMITTED DO NOT COORDINATE.
  
 B) THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION
 FOR SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX
 METHODS OF CALCULATIONS. PLEASE SEE 13-415.2.ABC.1
  
 C) PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT
 ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE
 INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER
 OF THIS COMMENT.
 THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE
 NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT
 COORDINATE.
  
 FOR EXAMPLE: PLEASE SEE THE COUNT ON THE EXTERIOR
 LIGHTS, WATTAGES DO NOT COORDINATE. THE IDR ONLY
 INDICATE 2-500WATT FIXTURES AND 8-46 WATT FIXTURES.
 THERE ARE ACTUALLY MORE FIXTURES ON PLANS BY COUNT AND
 WATTAGE.
  
 FOR EXAMPLE: INTERIOR LIGHT FIXTURES SHALL INCLUDE ALL
 AREAS. BASED ON THE IDR, IT ONLY LIST TWO DIFFERENT
 TYPE OF FIXTURES. BASED ON THE PLANS AND THE FIXTURE
 LEGEND THIS IS NOT THE CASE.
  
 FOR EXAMPLE: FIXTURES NEED TO BE SPECIFIC. MOST
 FIXTURES STATE *TBD* WHICH THE VA RATING CAN NOT BE
 VERIFIED. PLEASE SELECT SPECIFIC FIXTURES. THESE MAY
 ALWAYS BE REVISED AT A LATER DATE IF A PRODUCT CHANGES.
 THE GOAL IS AT LEAST TO MEET THE MINIMUM CODES.
 *D* FIXTURES ARE SHOWN ON PLANS HOWEVER HAVE DIFFERENT
 SYMBOLS. WHEN LOOKING AT THE SYMBOL LEGEND YOU WILL SEE
 EACH OF THESE ARE ACTUALLY DIFFERENT. ONE IS 58VA AND
 THE OTHER 29 VA.
  
  
 *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO
 HELP. THESE MAY NOT BE ALL ITEMS. IT IS IMPORTANT TO
 FIGURE HOW CALCULATIONS WILL BE DONE FOR EACH SPACE OR
 AS PART OF THE BUILDING.
 PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR
 QUESTIONS FOR COORDINATION.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SPACE CONTROLS
 REQUIRED FOR CONFERENCE ROOM. ( NOTED ON PREVIOUS
 REVIEW)
  
 5) NOTE: BASED ON A COMPLETE REVISED ELECTRICAL RISER,
 PLEASE SEE 230.70. THERE ARE UNPROTECTED CONDUCTORS
 INSIDE THE BUILDING WHICH IS NOT PERMITTED. THE CODE
 SECTION GIVEN DOES NOT GIVE AN AMOUNT PERMITTED.
 THE OLD PALM BEACH COUNTY AND CITY OF WEST PALM BEACH
 TECHNICAL AMENDMENTS PERMITTED UP TO 8FT, HOWEVER AS
 THE OLDER CODE CHANGED THE TECHNICAL AMENDMENTS WENT
 AWAY. SOME MUNICIPALITIES DO NOT PERMIT ANY UNPROTECTED
 CONDUCTORS INSIDE THE BUILDING.
 THE AMOUNT AS SHOWN ON PLANS IS OVER. PLEASE ADJUST
 DESIGN.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
2009-02-06 17:00:40REVIEW TO CONTINUE. REVIEW WILL GO INTO A FAILED STATUS
 ONCE COMPLETE. SOME NOTES FROM PREVIOUS REVIEW AND
 MEETING STILL NEED TO BE ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-06 Cont ID  
Sent By dpalmer Date 2008-10-06 Time 11:42 Rev Time 0.00
Received By dpalmer Date 2008-10-06 Time 11:42 Sent To  
Notes
2008-10-06 11:43:07 
 ** DENIED REVIEW **
  
 *** PLEASE SEE COVER SHEET OF PLANS CALL FOR PLANS
 BEING 95% COMPLETE. PLEASE SUBMIT 100% PLANS.
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED ENERGY COMPLIANCE
 CALCULATIONS PER 13-101.1, 13-415.2,
 13-415.2.ABC.1.1,.1.2, .1.3.
 PLEASE SEE THE METHOD *A* AS SUBMITTED IS FOR A WHOLE
 BUILDING WHICH THIS IS NOT BASED ON USE AND OCCUPANCY.
 PLEASE SEE DEFINITIONS IN SECTION 202 FOR SEPARATIONS
 ETC.
 PLEASE KNOW IN ANY CASE THE CALCULATIONS AS SUBMITTED
 ARE NOT COMPLETE AND DO NOT COORDINATE WITH THE
 SUBMITTED PLANS. SOME EXAMPLES WILL BE GIVEN. THE INPUT
 DATA REPORT WILL BE NOTED AS IDR BELOW.
  
 EXAMPLE: THERE IS NO EXTERIOR LIGHTING IN THE IDR YET
 THE PLANS CLEARLY SHOW EXTERIOR FIXTURES.
 EXAMPLE: THERE ARE NO WATER HEATERS IN THE IDR, YET
 PLANS INDICATE ELECTRIC WATER HEATER. ( OFFICE SPACE)
 EXAMPLE: THERE ARE OTHER COMPONENTS ON PLANS WHICH ARE
 NOT PART OF THE IDR. PLEASE SEE COMMENTS FROM OTHER
 TRADES.
 EXAMPLE: PLEASE SEE THE NUMBER, TYPE, WATTAGES OF THE
 INTERIOR LIGHTING BASED ON THE FIXTURE SON PLANS AND
 THE FIXTURE LEGEND DOES NOT COORDINATE.
 PLEASE BE SURE THE FIXTURE LEGEND IS SPECIFIC, COMPLETE
 AND COORDINATE ALL ON PLANS WITH THE IDR.
  
 2) NOTE: PLEASE SEE FBC 3006.2 FOR MISSING EQUIPMENT IN
 ELEVATOR MACHINE ROOM. THIS WILL AFFECT THE ELECTRICAL
 PLANS.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 FOR SEPARATE
 SPACES WHICH DO REQUIRED AUTOMATED LIGHTING CONTROLS.
 THE IDR INDICATES OCCUPANCY SENSORS YET THE PLANS DO
 NOT SEEM TO INDICATE ANY.
 PLEASE COMPLETE PLANS FOR MISSING DEVICES AS REQUIRED.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR REQUIRED
 EXTERIOR LIGHTING CONTROLS. THERE ARE TWO METHODS FOR
 CONTROLLING EXTERIOR LIGHTING. THE CONTROLS ON SHEET
 E-301 DOES NOT COMPLETE ALL THAT IS REQUIRED. PLEASE
 KEEP IN MIND IF USING AN OVER RIDE AS SHOWN THIS DEVICE
 MUST HAVE AN OVER RIDE OF SOME KIND WHICH WILL NOT
 PERMIT THE LIGHTING TO BE ON DURING DAY LIGHT HOURS.
  
 5) NOTE: PLEASE VERIFY THE SIGN CIRCUIT REQUIRED PER
 600.5
  
 6) NOTE: PLEASE SEE NFPA-72 DEFINITIONS. THE PLANS CALL
 FOR A *S* AND THE *S* ON THE SYMBOL LEGEND INDICATES A
 SMOKE DETECTOR INSIDE AND OUTSIDE EACH SLEEPING ROOM. A
 SMOKE DETECTOR BY DEFINITION IS A DEVICE WHICH WILL
 DETECT AND NOT SOUND AN ALARM. A SMOKE ALARM IS A
 DEVICE WHICH WILL DETECT AND SOUND THE ALARM. THE
 SYMBOL LEGEND SEEMS TO LEND TO A SMOKE ALARM BY THE
 DESCRIPTION. PLEASE VERIFY AND ADJUST.
 IF INSTALLING SMOKE DETECTORS, PLEASE COMPLETE PLANS
 WITH THE SYSTEM. (PANEL, SOUNDING DEVICES ETC).
  
 7) NOTE: PLEASE SEE UNIT *C* WHICH WILL REQUIRE ARC
 FAULT FOR ALL CIRCUITS IN AREA USED FOR SLEEPING AND
 LIVING ROOM. AS THESE ARE ONE IN THE SAME AFCI
 PROTECTION IS REQUIRED. 210.12
  
 8) NOTE: PLEASE SEE UNITS A AND B AS THESE ARE MISSING
 RECEPTACLES PER 210.52B1, 210.11C1, 210.52C3, 4. (ROOMS
 206,211
  
 9) NOTE: PLEASE SEE UNITS A AND B FOR MISSING WALL
 RECEPTACLES PER 210.52. THESE ARE ABOUT THE SAME AREAS
 AS NOTED ABOVE IN NOTE #8.
  
 10) NOTE: PLEASE SEE 422.13 AS WATER HEATERS ARE NOW
 CONSIDERED CONTINUOUS LOADS UNDER THE 2005 NEC. PLEASE
 ADJUST LOAD CALCULATIONS FOR THESE LOADS AT 125%.
  
 11) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 EGRESS PATHS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1,.2.2
 STAIRS REQUIRE A MINIMUM OF 10FT CANDLES UNDER NORMAL
 AND IS PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY
 POWER.
 PLEASE PROVIDE LEVELS FOR ALL EGRESS AREAS.
 FAC 61G15-33.004
 FBC 106.1.1, FOR ADDITIONAL INFORMATION.
  
 12) NOTE: PLEASE INDICATE THE SIZE OF THE GUTTER SO
 COMPLIANCE WITH FILL CAN BE VERIFIED.
 366.22
  
 13) NOTE: BASED ON THE SITE PLANS AND SURVEY SUBMITTED
 THE ELECTRICAL SERVICE MAY NOT BE LOCATED ON THE SIDE
 OF THE BUILDING AS SHOWN. THE OVER HEAD SERVICE DOES
 MEET MINIMUM CLEARANCE FROM OPENINGS PER 23.24.
 THE ELECTRICAL SERVICE LOCATION DOES NOT MEET 110.26
 FOR WORKING CLEARANCES REQUIRED.
  
 14) NOTE: BASED ON MANY ASPECTS OF THE SCOPE OF WORK
 STILL IN NEED FOR CODE COMPLIANCE FROM THIS TRADE AS
 WELL AS OTHER TRADES THER MAY VERY WELL BE NEW COMMENTS
 ON THE NEXT REVIEW.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2009-09-22 Cont ID  
Sent By mgonzale Date 2009-09-22 Time   Rev Time 1.00
Received By mgonzale Date 2009-09-22 Time   Sent To  
Notes
2009-09-22 10:00:35PREVIOUS COMMENTS FROM ENGINEERING ARE STILL APPLICABLE
 (DATED 07-08-09)
  
 REVISIONS ON THIS PLAN WHERE NOT RELATED TO ENGINEERING
 COMMENTS.
  
 [email protected]
 (561) 494-1085

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2009-07-08 Cont ID  
Sent By dlauderm Date 2009-07-08 Time 12:24 Rev Time 0.00
Received By dlauderm Date 2009-07-08 Time 12:24 Sent To  
Notes
2009-07-08 13:00:49APPROVED WITH PROVISOS:
 DEAN S. LAUDERMILK, PROJECT COORDINATOR, CONTACT NUMBER
 494-1083 (ENGINEERING) 805-6716 (CONSTRUCTION SERVICES)
 1. IF AN AIR RIGHTS EASEMENT HAS BEEN APPLIED FOR THIS
 COMMENT IS NO LONGER VALID. IF AN AIR RIGHTS EASEMENT
 HAS NOT BEEN APPLIED FOR THEN ONE NEEDS TO BE APPLIED
 FOR AND APPROVED PRIOR TO GETTING A CO. NO PERMANENT
 STRUCTURES ARE ALLOWED IN CITY ROW (BALCONY ABOVE
 ENTRANCE DOOR).
 2. DOORS ARE NOT ALLOWED TO OPEN OUT INTO A SIDEWALK
 AND OR ROW. THE ENTRANCE DOOR ON RODSEMARY TO THE
 RECEPTION AREA NEEDS TO BE RECESSED OR REDESIGNED TO
 OPEN IN.
 3. IRRIGATION PLAN NEEDS TO BE MODIFIED. THE
 ENGINEERING REVIEW INVOLVES THE SIZE OF METERS TO BE
 USED.
 A) IRRIGATION SYSTEM ZONES, GALLON PER MINUTE (GPM)
 FLOWS MUST BE SHOWN (PER SHEET IR-1 THE 4 ZONES ARE
 CALLED OUT). THE VALVE INFORMATION DETAIL ON IR-2
 SHOWS, THE ZONE NUMBER, GALLONS PER MINUTE OF EACH ZONE
 AND SIZE OF VALVE FOR EACH ZONE NEEDS TO BE CALLED OUT,
 THEY ARE NOT. THEN SEE NOTE IR-B.
 B) A 5/8" WATER METER IS CALLED OUT FOR IRRIGATION
 USAGE ON IR-1 IN THE NOTES SECTION. A 5/8" WATER METER
 WILL ONLY GIVE 10 GPM (SAFE OPERATING FLOW). IF ANY
 ZONE IS LARGER THAN THIS THE METER SIZE SHALL NEED TO
 BE INCREASED. A 3/4" WATER METER WILL GIVE 15 GPM AND A
 1" WATER METER WILL GIVE 25 GPM. IF ANY ZONE IS OVER 10
 GPM THEN REDESIGN THE IRRIGATION SYSTEM OR INCREASE THE
 METER SIZE ACCORDANTLY.
 4. IF THE STORMWATER PRE AND POST SQUARE FOOTAGE HAS
 BEEN GIVEN TO ENGINEERING THIS NOTE IS NO LONGER VALID.
 IF THE INFORMATION HAS NOT BE RECIEVED THEN FORWARD THE
 PRE AND POST PERVIOUS AND IMPERVIOUS SQ. FOOTAGE TO
 ENGINEERING. THIS WILL BE CHECKED AND CAN HOLD UP THE
 CO ON THE BUILDING.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-04-03 Cont ID  
Sent By efabian Date 2009-04-03 Time 12:13 Rev Time 0.00
Received By efabian Date 2009-04-03 Time 12:13 Sent To Z
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2009-03-02 Cont ID  
Sent By mgonzale Date 2009-03-02 Time 12:51 Rev Time 1.00
Received By mgonzale Date 2009-03-02 Time 12:50 Sent To ENG
Notes
2009-03-02 12:51:52*** NOT PASSED ***
  
 ENGINEERING IS STILL REVIEWING PLANS. DEAN L 561
 644-7338

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By rchokshi Date 2008-09-24 Time 09:21 Rev Time 0.00
Received By rchokshi Date 2008-09-24 Time 09:15 Sent To  
Notes
2008-09-24 09:21:48FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE TURBIDITY DETAILS OF
 POLLUTION PREVENTION . PLEASE SHOW ON DRAWINGS THE
 TURBIDITY AROUND CATCH BASINS DURING CONSTRUCTION AND
 ALL DEMOLITION PHASE. HEIGHT OF TURBIDITY BARRIER FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST PARTICLES.
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 5. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 8. PLEASE PROVIDE A COPY OF GEO-TECH REPORT & STORM
 WATER QUALITY CALCULATIONS TO 1000 45TH STREET FOR
 THEIR APPROVAL BEFORE WE ISSUE A PERMIT.
  
 9. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-12-22 Cont ID  
Sent By mawillia Date 2009-12-22 Time 14:33 Rev Time 0.00
Received By mawillia Date 2009-12-22 Time 14:19 Sent To  
Notes
2009-12-22 14:25:41******REVISION APPROVED*****
  
 SEE REVISION TRACKING PERMIT NUMBER 09120104
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-09-17 Cont ID  
Sent By mawillia Date 2009-09-17 Time 11:49 Rev Time 0.00
Received By mawillia Date 2009-09-17 Time 11:17 Sent To  
Notes
2009-09-17 11:49:52*****REVISION #4, DATED 7/30/09, APPROVED*****
  
 REVISED SHEET A-1.01 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-01 Cont ID  
Sent By mawillia Date 2009-04-01 Time 15:17 Rev Time 0.00
Received By mawillia Date 2009-04-01 Time 14:45 Sent To  
Notes
2009-04-01 15:17:46*****APPROVED*****
  
 A-0.00, AD-1.01,A-2.01, A-3.02, A-4.11, A-6.01, AND
 E-202 WERE STAMPED, INITIALED, AND DATED; SHEET E-101
 TO BE FIRE-STAMPED WHEN THE ELECTRICAL EXAMINER'S
 COMMENTS HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-02-20 Cont ID  
Sent By mawillia Date 2009-02-20 Time 11:33 Rev Time 0.00
Received By mawillia Date 2009-02-20 Time 09:47 Sent To  
Notes
2009-02-20 11:08:53*****UNSAT*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS WILL
 BE FIRE-STAMPED WHEN THE BELOW NEW COMMENT AND THE
 OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED
  
  
 *NEW COMMENT
  
 AA. CIVIL DRAWINGS (C-1, C-2, C-3,) WHICH WERE INCLUDE
 IN THE ORIGINAL PLAN SUBMITTAL ARE NOT INCLUDED IN THIS
 PLAN SET (ALTHOUGH THE COVER SHEET HAS THEM INCLUDED IN
 THE DRAWING INDEX). PLEASE EXPLAIN.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-17 Cont ID  
Sent By mawillia Date 2008-10-17 Time 13:44 Rev Time 0.00
Received By mawillia Date 2008-10-17 Time 10:50 Sent To  
Notes
2008-10-17 13:44:23*****DENIED*****
  
 01. THE COMPLETE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET. BE ADVISED THAT THIS IS
 NORTH ROSEMARY AVENUE, NOT JUST ROSEMARY AVENUE AS
 SHOWN ON THE SUBMITTED SHEETS.
  
 02. ON SHEET L-1.01 PICTORIAL CAPTION 1 AND SHEET
 C-0.01, C-0.03, A-0.01, AD-3.01 (EAST ELEVATION) &
 A-3.02 (EAST ELEVATION), ROSEMARY IS IS INCORRECTLY
 LABELED AS A STREET AND NOT AN AVENUE.
  
 03. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04. THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE
 VICINITY THEREOF (INCLUDING ROADS, ALLEYS, FIRE LANES)
 .
  
 05. ON SHEET A-0.00, THE PHONE NUMBER FOR WEST PALM
 BEACH FIRE RESCUE IS 561-804-4700.
  
 06. EXPLAIN THE PURPOSE OF THE EXIT SIGN LIGHTS SHOWN
 ON SHEET A0.00 IN AREAS MARKED 107-1 & 107-2 AS
 INDICATED ON SHEET A-1.01.
  
 07. PROVIDE THE PRESCRIPTIVE STRENGTHS FOR THE
 GUARDRAILS/HANDRAILS.
  
 08. STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES. IT
 APPEARS THAT THE WEST ELEVATION STAIRS HAVE HANDRAILS
 ON ONE SIDE.
  
 09. OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED BE TO
 MINIMIZE WATER ACCUMULATION ON THEIR SURFACES.
  
 10. THE WIDTH OF STAIRS SHALL COMPY WITH NFPA 101 -
 7.2.2.2.1 - 2003 EDITION.
  
 11. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 EXPLAIN WHY THE MECHANICAL ROOM (#111-1) AND STORAGE
 ROOM (#113-1) DOORS ARE NOT FIRE RATED.
  
 12. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 WHY IS EXTERIOR HALLWAY DOOR 204-1 FIRE-RATED BUT NOT
 204-2 ?
  
 13. IN THE DOOR SCHEDULE AND DETAILS (SHEET A-6.01),
 WHY ARE INTERIOR HALLWAY (COMMON CORRIDOR) DOORS 205-1
 AND 210-1 NOT FIRE RATED.
  
 14. DOORS AND WINDOWS REQUIRED TO HAVE A FIRE RATING
 SHALL COMPLY WITH NFPA 80.
  
 15. IT IS SHOWN THAT THIS BUILDING WILL HAVE A FIRE
 ALARM SYSTEM. EXPLAIN WHAT SMOKE SENSORS ARE IN
 RELATION TO SMOKE DETECTORS AND/OR SMOKE ALARMS. BE
 ADVISE THAT SMOKE DETECTORS (SD) ARE TIED INTO THE
 BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE ALARMS (SA)
 ALERT THE OCCUPANT(S) OF THE DWELLING UNIT ONLY.
  
 16. IF THE BUILDING IS TO BE EQUIPPED WITH A FIRE ALARM
 SYSTEM, SMOKE DETECTORS (SD) ARE REQUIRED IN THE 2ND
 FLOOR HALLWAY (COMMON CORRIDOR) .
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE ITEMS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-12-07 Cont ID  
Sent By jgomez Date 2009-12-07 Time 08:27 Rev Time 0.00
Received By jgomez Date 2009-12-07 Time 08:21 Sent To  
Notes
2009-12-07 08:28:11SENT TO C8.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-28 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2009-10-28 Time 12:25 Sent To  
Notes
2009-10-28 12:26:25INCOMING TO: J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 10:50 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 10:50 Sent To  
Notes
2009-09-21 14:27:26C-19

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-24 Cont ID  
Sent By shill Date 2009-06-24 Time 15:22 Rev Time 0.00
Received By shill Date 2009-06-24 Time 15:22 Sent To  
Notes
2009-06-24 15:22:29C29
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-03-30 Cont ID  
Sent By adarroug Date 2009-03-30 Time 14:05 Rev Time 0.00
Received By adarroug Date 2009-03-30 Time 14:05 Sent To  
Notes
2009-03-30 14:05:25TO "C33"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-01-21 Cont ID  
Sent By adarroug Date 2009-01-21 Time 09:16 Rev Time 0.00
Received By adarroug Date 2009-01-21 Time 09:16 Sent To  
Notes
2009-01-21 09:18:58TO "COMM" BD#63

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-17 Cont ID  
Sent By mawillia Date 2008-10-17 Time 10:50 Rev Time 0.00
Received By mawillia Date 2008-09-12 Time 10:39 Sent To  
Notes
2008-09-12 10:49:13TO "COMM" BD#20

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-09-08 Cont ID  
Sent By rkussner Date 2009-09-08 Time 12:32 Rev Time 0.00
Received By rkussner Date 2009-09-08 Time 12:32 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-03-31 Cont ID  
Sent By rregueir Date 2009-03-31 Time 15:39 Rev Time 0.00
Received By rregueir Date 2009-03-31 Time 15:22 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-02-21 Cont ID  
Sent By rregueir Date 2009-02-21 Time 15:43 Rev Time 0.00
Received By rregueir Date 2009-02-21 Time 15:24 Sent To  
Notes
2009-02-21 15:40:13ALL PREVIOUS COMMENTS ADDRESSED. HOWEVER, NO ENERGY
 CALCULATIONS COULD BE FOUND IN THIS SUBMISSION FOR THE
 RESIDENTIAL UNITS. REVIEW WILL REMAIN IN FAIL STATUS
 PENDING SUBMISSION OF ENERGY CALCULATIONS AND COOLING
 LOAD CALCULATIONS FOR THE RESIDENTIAL UNITS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-29 Cont ID  
Sent By rregueir Date 2008-09-29 Time 08:26 Rev Time 0.00
Received By rregueir Date 2008-09-24 Time 15:53 Sent To  
Notes
2008-09-29 08:26:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1.01: TOILET ROOM 113 EXHAUST DUCT FROM TEF-1
 IS SHOWN ROUTED THROUGH THE RETURN AIR PLENUM CEILING.
 EXHAUST DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND
 INTO OR PASS THROUGH DUCTS OR PLENUMS IN ACCORDANCE
 WITH FBCM 601.3.
  
 2. PAGE M-1.01: AHU-1 SHALL BE PROVIDED WITH DUCT SMOKE
 DETECTOR FOR FAN SHUT-DOWN IN ACCORDANCE WITH FBCM
 606.2.1. DUCT DETECTOR SHALL BE TIED TO BUILDING FIRE
 ALARM SYSTEM (IF ONE IS PRESENT) OR BE PROVIDED WITH
 AUDIBLE/VISIBLE NOTIFICATION APPLIANCE (SUCH AS A
 HORN/STROBE) IN ACCORDANCE WITH FBCM 606.4.
  
 3. PAGE M-1.02: EF SCHEDULE INDICATES TEF-1 ON 1ST
 FLOOR IS TO BE CONTROLLED WITH LIGHT SWITCH. THIS FAN
 SHALL BE INTERLOCKED WITH AHU-1 IN ACCORDANCE WITH FBCM
 403.2.1(3).
  
 4. PROVIDE DETAIL FOR ATTACHMENT OF CU-1. CU-4 AND
 CU-5, SHOWING THEM ATTACHED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBCM 301.13. ALSO, PROVIDE
 DOCUMENTATION FROM THE A/C APPLIANCE MANUFACTURERS
 SHOWING HOW ALL APPLIANCES EXPOSED TO WIND ARE DESIGNED
 AND CONSTRUCTED TO RESIST WIND PRESSURES IN ACCORDANCE
 WITH THIS SECTION.
  
 5. 1ST FLOOR MECHANICAL PLAN SHOWS AN ABOVE-CEILING
 PLENUM RETURN SYSTEM. DETAILS ON ARCHITECTURAL PLANS
 SHOW INTERIOR FINISHES ON EXTERIOR WALLS, SUCH AS
 DRYWALL AND INSULATION ARE TO STOP AT THE CEILING LINE.
 EXPOSED CONCRETE BLOCK SHALL NOT BE USED AS A PLENUM
 AIR BARRIER. BUILDING CAVITIES WHICH WILL BE USED AS
 RETURN AIR PLENUMS SHALL BE LINED WITH A CONTINUOUS AIR
 BARRIER MADE OF DURABLE NON-POROUS MATERIALS IN
 ACCORDANCE WITH FBCM 603.8, SHALL BE SEALED IN
 ACCORDANCE WITH FBCM 603.9 AND INSULATED IN ACCORDANCE
 WITH FBCB TABLE 13-410.1.ABC.2.2. EXTERIOR WALLS USED
 AS PLENUM AIR BARRIERS SHALL BE INSULATED TO A MINIMUM
 OF R-8 PER THIS TABLE. THIS ALSO APPLIES TO THE
 EXTERIOR WALL IN MECHANICAL ROOM 111.
  
 6. COOLING LOAD CALCULATIONS FOR THE SPACES LISTED ON
 FORM 400A SHALL BE PROVIDED. THIS CALCULATION SHALL BE
 ATTACHED TO THE CODE COMPLIANCE FORM SUBMITTED TO THE
 BUILDING DEPARTMENT WHEN THE BUILDING IS PERMITTED IN
 ACCORDANCE WITH FBCM 13-407.1.ABC.1.
  
 7. PAGE M-1.01: OUTSIDE AIR INTAKE FOR AHU-1 SHALL BE
 PROVIDED WITH SHUTOFF DAMPER CONTROLS IN ACCORDANCE
 WITH FBCB 13-409.1.ABC.3.3.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING, WITH A
 DESCRIPTION OF HOW EACH COMMENT WAS ADDRESSED AND WHERE
 THE REQUIRED INFORMATION CAN BE FOUND. THIS WILL HELP
 TO FACILITATE A TIMELY REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2009-09-14 Cont ID  
Sent By kstevens Date 2009-09-14 Time 08:57 Rev Time 0.00
Received By kstevens Date 2009-09-14 Time 08:57 Sent To  
Notes
2009-09-14 08:58:41REVISION OK -- SHT IR-1. -- IR-2 RETURNED TO CONTRATOR
 AS NOT CHANGES/REVISIONS WERE FOUND.

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 10:51 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 10:51 Sent To  
Notes
2009-07-14 10:52:15REVISION OK -- NEW SHEETS IR-1 & IR-2. IRRIGATION
 PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-03-31 Cont ID  
Sent By kstevens Date 2009-03-31 Time 07:25 Rev Time 0.00
Received By kstevens Date 2009-03-31 Time 07:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-02 Cont ID  
Sent By kstevens Date 2009-03-02 Time 10:12 Rev Time 0.00
Received By kstevens Date 2009-03-02 Time 10:12 Sent To  
Notes
2009-03-02 10:24:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SUBMIT MANUF. SPECIFICTIONS FOR THE BUBBLER SHOWING
 CONFORMANCE WITH ASME A112.19.1M, ASME A112.19.2M OR
 ASME A112.19.9M AS WELL AS NSF61 SECTION 9. SECTION
 410.
 ****NO WRITTEN RESPONSE, COMMENT NOT ADDRESSED FOR THE
 ASME REQUIREMENT.
  
 3. SHT A-1.02 A WASH MACHINE CONNECTION IS REQUIRED IN
 THE UNIT WITH ROOMS 201, 202 & 203. TABLE 403.1.
 ****NO WRITTEN RESPONSE, COMMENT NOT ADDRESSED FOR THE
 UNIT WITH ROOM 201.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 **********NEW COMMENTS**********
  
 1B. SHT S-1.05 NOTE STATES: " RECONSTRUCT ROOF DRAINS
 AND ADD OVERFLOW SCUPPERS. (SEE ARCH. DRAWINGS SHT
 A-1.03)". THERE ARE NO OVERFLOW SCUPPERS INDICATED ON
 SHT A-1.03. PLEASE CORRELATE. -- SECONDARY ROOF
 DRAINS/SCUPPERS ARE REQUIRED PER SECTIONS 1107.1,
 1107.2 & 1107.3 AS WELL AS TABLE 1106.7. PLEASE SHOW
 REQUIRED OVERFLOW SCUPPERS. SUBMIT A DETAIL FOR THE
 SCUPPERS SHOWING THE HEIGHT & WIDTH AS WELL AS THE
 DISTANCE FROM THE ROOF TO THE FLOW LINE AS REQUIRED IN
 SECTION 1503.4.3 OF THE BUILDING CODE.
  
 2B. SHT P-1.02 DOMESTIC WATER SERVICE ISOMETRIC RISER
 AND THE SANITARY ISOMETRIC RISER INDICATE FUTURE WASH
 MACHINE CONNECTIONS FOR ONE UNIT. THIS IS NOT APPROVED
 AS WASH MACHINE CONNECTIONS ARE REQUIRED PER TABLE
 403.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE TO THE TRANSMITTAL LETTER INDICATING
 THE DESCRIPTION OF THE REVISION MADE TO CORRECT THE
 COMMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-15 Cont ID  
Sent By kstevens Date 2008-09-15 Time 12:10 Rev Time 0.00
Received By kstevens Date 2008-09-12 Time 16:41 Sent To  
Notes
2008-09-15 13:37:04DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 2. SUBMIT MANUF. SPECIFICTIONS FOR THE BUBBLER SHOWING
 CONFORMANCE WITH ASME A112.19.1M, ASME A112.19.2M OR
 ASME A112.19.9M AS WELL AS NSF61 SECTION 9. SECTION
 410.
  
 3. SHT A-1.02 A WASH MACHINE CONNECTION IS REQUIRED IN
 THE UNIT WITH ROOMS 201, 202 & 203. TABLE 403.1.
  
 4. SHT A-5.01 DETAIL (1), LAV SHALL BE MINIMUM 15" OFF
 THE WALL TO THE CENTERLINE OF THE FIXTURE TO BE
 CENTERED ON THE REQUIRED 30" WIDTH OF THE CLEAR FLOOR
 SPACE. SECTION 11-4.19.3 & FIGURE 32.
  
 5. SHT A-5.01 DETAIL (2), THE DISPENSER SHALL BE
 MINIMUM 19" OFF THE FLOOR TO THE CENTERLINE. DETAIL
 SHOWS 17" TO CENTERLINE. SECTION 11-4.19.6 & FIGURE
 29(B).
  
 6. SHT A-5.01 SHOW COMPLIANCE WITH SECTION 11-4.19.5
 FAUCETS.
  
 7. SHT A-5.01 DETAIL (4), INDICATES "OPTIONAL CUP
 HOLDER". IF THE CUP HOLDER IS NOT REQUIRED, THEN SHOW
 COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 8. SHT P-1.01 AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE TO THE BUSINESS OCCUPANCY. SECTION 608.13.3.
  
 9. SHT P-1.02 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE CLEANOUT SHOWN ON THE RISER
 DIAGRAM DOWNSTREAM OF THE LAST TWO 3" RISERS IS NOT
 SHOWN ON THE FLOOR PLAN. -- RISER DOES NOT SHOW THE
 VENT THRU THE ROOF FOR THE FIXTURES ON THE FIRST FLOOR.
 PLEASE CORRELATE. SECTIONS 106.1.1, 708.3.3 & 903.3.
  
 10. SHT P-1.02 NOTE FOR WATER HEATER AT THE TOP OF THE
 SHEET IS NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1.
  
 11. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS (REQD BY
 SECTION 604.9) ETC. SECTION 105.3.5.1.3 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2009-09-10 Cont ID  
Sent By aaponte Date 2009-09-10 Time 10:39 Rev Time 0.00
Received By aaponte Date 2009-09-10 Time 10:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2009-07-21 Cont ID  
Sent By aaponte Date 2009-07-21 Time 11:49 Rev Time 0.00
Received By aaponte Date 2009-07-21 Time 11:44 Sent To  
Notes
2009-07-21 11:48:411. C-00.1 DRAWING AND LANDSCAPE DRAWINGS ARE
 INCONSISTENT. PATH FROM PARKING AREA IS SHOWN IN
 DIFFERENT LOCATION, AND AC SCREENING WALL IS MISSING ON
 CIVIL DRAWINGS.
 2. PLEASE SHOW EXISTING TREE GRATES ON SIDEWALK.
 3. LANDSCAPE BUFFER ON WEST SIDE OF THE PROPERTY SHALL
 BE 5 FEET (PLANTING AREA). PLEASE REDUCE THE WIDTH OF
 THE PARKING SPACES TO 8'-6" TO PROVIDE FOR ADDITIONAL
 LANDSCAPE AREA REQUIRED.
 4. LANDSCAPE CALCULATIONS PRESENTED INDICATE A
 DEFICIENCY ON PLANTING MATERIAL. PLEASE CORRECT.
 5. PLEASE INDICATE WHERE THE TRASH RECEPTACLES WILL BE
 LOCATED.

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-06 Cont ID  
Sent By aaponte Date 2009-04-06 Time 08:35 Rev Time 0.00
Received By aaponte Date 2009-04-06 Time 08:35 Sent To  
Notes
2009-04-06 10:23:33PROVISO:
 LANDSCAPE DRAWINGS SHALL BE RESUBMITTED WITH THE
 FOLLOWING MODIFICATIONS:
 1. PURSUANT TO SECTION 94-442(A), LANDSCAPE PLANS SHALL
 BE PREPARED, SIGNED AND SEALED BY A REGISTERED
 LANDSCAPED ARCHITECT.
 2. PLEASE PROVIDE A TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
 3.PLEASE IDENTIFY ON THE LANDSCAPE PLAN ALL UTILITIES,
 EASEMENTS, SITE LIGHTING, OVERHEAD LINES, OVERHANGING
 TREE LIMBS FROM ADJACENT PROPERTIES AND ANYHTING ELSE
 THAT MAY INTERFERE WITH THE PROPOSED LANDSCAPING.
 4. PLEASE PROVIDE THE SCIENTIFIC AND COMMON NAMES AND
 THE SPACING OF ALL PROPOSED PLANT MATERIAL. PLANTING
 DETAILS SHALL BE PROVIDED. NOTES CONCERNING IRRIGATION
 COVERAGE, DEPTH AND TYPE OF MULCH, PLANT GRADES AND
 ERADICATION OF PROHIBITED PLANT SPECIES SHALL ALSO
 APPEAR ON THE LANDSCAPE PLAN.
 5. PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE AREAS
 SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NON-MOUNTABLE CONCRETE CURBING ON THE TYPE
 CHARACTERIZED AS "TYPE D".
 6. PURSUANT TO SECTION 94-443(C)(2) TABLE XIV-1, TREES
 SHALL BE PLANTED AT 30 FOOT INTERVALS AND HEDGES SHALL
 BE PLANTED AT TWO-FOOT INTERVALS ALONG EACH REQUIRED
 LANDSCAPE BUFFER. PLEASE PROVIDE TREES ALONG THE NORTH
 AND WEST SIDE OF THE SURFACE PARKING LOT.
 7. THE PROPOSED HEDGES ALONG THE NORTH AND WEST SIDE OF
 THE PARKING LOT SHALL BE PLANTED ALONG THE PROPERTY
 LINE TO AVOID CREATING A "DOG RUN" BETWEEN THE HEDGE
 AND THE FENCE.
 8. PURSUANT TO SECTION 94-445(4)(G)(3) AUTOMATIC
 IRRIGATION SYSTEMS SHALL BE USED FOR CULTIVATED
 LANDSCAPE AREAS FOR ALL PROPERTIES. THIS INCLUDES THE
 RIGHT-OF-WAY PLANITNGS.
 9.PURSUANT TO SECTION 94-444(B) GARBAGE OR TRASH
 RECEPTACLES AND ALL OTHER MECHANICAL EQUIPMENT SHALL
 NOT BEPERMITTED UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED OF BRICK,
 DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR
 COMPARABLY DURABLE WOOD AND STEEL. WALLS SHALL BE
 LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS. PLEASE IDENTIFY THE LOCATION OF THESE ITEMS
 AND INDICATE THE MANNER IN WHICH THESE ITEMS WILL BE
 SCREENED.
 10. PURSUANT TO SECTION 94-442(B)(2)(B)(1) AT LEAST ONE
 SHADE TREE SHALL BE PLANTED FOR EACH 1600 SQ FT. OF
 OPEN SPACE OR PORTION THEREOF. AT LEAST ONE FLOWERING
 TREE SHALL BE PLANTED FOR EACH 6,400 SQ.FT. OF OPEN
 SPACE OR PORTION THEREOF.
 11. PURSUANT TO SECTION 94-445(4)(A) SHADE AND
 FLOWERING TREES PLANTED PURSUANT TO THE PROVISIONS OF
 THIS SECTIONS SHALL BE A MINIMUM OF 8 FEET IN HEIGHT,
 AND POSESS A MINIMUM OF 5 FEET OF CLEAR TRUNK SPACE.
 THE PROPOSED PIGEON PLUM TREES DO NOT MEET THIS MINIMUM
 REQUIREMENT.
 12. PLEASE STUDY THE POSSIBILITY TO HAVE WINDOWS ON THE
 WEST ELEVATION. IF WINDOWS ARE NOT POSIBLE OTHER
 TECHNIQUES SHOULD BE USE TO ENHANCE THE QUALITY OF THE
 WEST ELEVATION.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-01-27 Cont ID  
Sent By aaponte Date 2009-01-27 Time 10:56 Rev Time 0.00
Received By aaponte Date 2009-01-27 Time 10:56 Sent To  
Notes
2009-01-27 11:25:071. A TREE ALTERATION PERMIT IS REQUIRED FOR THE REMOVAL
 OR RELOCATION OF EXISTING TREES ON SITE.
 2. A TREE SHALL BE INSTALLED ON EMPTY TREE GRATE ON
 SIDEWALK. SPECIE SHALL BE CONSISTENT WILL OTHER SPECIES
 ALONG ROSEMARY AVENUE.
 3. PLEASE REFLECT THE EXISTING TREE ALONG THE SOUTH
 SIDE OF THE PROPERTY (2).
 4. BUILDING ENCROACHMENTS, SUCH AS BALCONIES, SHALL NOT
 OCCUR WITHIN FOUR FEET OF THE BACK OF CURB. PROPOSED
 BALCONY ON SOUTH ELEVATION IS ONLY TWO FEET OF THE BACK
 OF CURB.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By aaponte Date 2008-09-23 Time 16:18 Rev Time 0.00
Received By aaponte Date 2008-09-23 Time 15:11 Sent To  
Notes
2008-09-23 15:21:101. PLEASE PROVIDE A TABLE WITH BUILDING TOTAL SQUARE
 FOOTAGE.
 2. PROPOSED CHAIN LINKE SHALL BE VINYL COATED.
 3. PROPOSED CHAIN LINK FENCE SHALL NOT EXCEED 4 FEET IN
 HEIGHT WHEN LOCATED WITHIN FRONT SETBACK (12' FROM BACK
 OF CURB ALONG ROSEMARY AVE, AND 17' FROM BACK OF CURB
 ALONG 4TH STREET)
 4. GARDEN WALL AND GATE SHALL NOT EXCEED 4 FEET ON
 MAXIMUM HEIGHT. A MAXIMUM 10% ADDITIONAL HEIGHT IS
 ALLOWED FOR DECORATIVE ELEMENTS SUCH AS BLOCK PIER.
 5. TWO BIKE RACKS SHALL BE PROVIDED WITHIN THE PROJECT.
 6. STAFF RECOMMENDS INCREASING THE AMOUNT OF GLAZING
 AREA PROVIDED ON THE FIRST FLOOR ALONG 4TH STREET.
 REGULATIONS FOR NEW STRUCTURES REQUIRE A MINIMUM OF 30%
 TRANSPARENCY.