Plan Review Details - Permit 08090238
Plan Review Stops For Permit 08090238
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-12-09 Cont ID  
Sent By lmartine Date 2008-12-09 Time 17:03 Rev Time 0.00
Received By lmartine Date 2008-12-09 Time 17:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-11-07 Cont ID  
Sent By lmartine Date 2008-11-07 Time 09:09 Rev Time 0.00
Received By lmartine Date 2008-11-06 Time 15:48 Sent To  
Notes
2008-11-07 09:56:13BUILDING REVIEW COMMENTS
  
  
 1)
 YOUR RESPONSE TO THE INCREASE OF THE CONSTRUCTION VALUE
 IS NOT APPROVED AND THE ADDITIONAL PERMIT FEES WILL
 REMAIN UNTIL PERMIT ISSUE. PLEASE SEE COPY PROVIDED,
 WPB AMENDMENTS SECTION 108.3.
  
 2)
 WALL SECTION PROVIDED IS INCOMPLETE, PLEASE INCLUDE
 FASTENING METHOD AND THE FINISH MATERIAL. PLEASE
 EXPLAIN NOTE #2 OF YOUR EXHIBIT E-8, A AND B TIE-INS ?
  
 3)
 WALL DETAIL PROVIDED IS ACCEPTABLE, FIELD INSPECTOR TO
 VERIFY FASTENERS.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-09 Cont ID  
Sent By lmartine Date 2008-10-09 Time 08:06 Rev Time 0.00
Received By lmartine Date 2008-10-09 Time 08:06 Sent To Z
Notes
2008-10-09 09:41:53BUILDING REVIEW COMMENTS
  
  
 1)
 AFTER REVIEW OF SPECIFICATIONS AND PICTURES PROVIDED BY
 INSPECTOR THE CONSTRUCTION VALUE IS NOW INCREASED TO
 $30'000, ADDITIONAL PERMIT FEES WILL BE ASSESSED.
  
 2)
 PROVIDE A WALL SECTION DETAIL FOR NEW INTERIOR WALLS.
  
 3)
 SPECIFY STRUCTURAL SUPPORTS FOR ANY EXTERIOR WALL
 REPAIRS.
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-09-15 Cont ID  
Sent By kconrad Date 2008-09-15 Time 15:48 Rev Time 0.00
Received By kconrad Date 2008-09-15 Time 15:47 Sent To  
Notes
2008-09-15 15:48:14PRE-INSPECT PERFORMED BY DR: REQUIRE PLAN REVIEW AND
 POSSIBLE ENGINEERING DETAILS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-27 Cont ID  
Sent By mcruz Date 2008-10-29 Time 14:54 Rev Time 0.00
Received By btrobaug Date 2008-10-27 Time 11:02 Sent To P
Notes
2008-10-17 14:18:44 
  
 THIS SUBMITTAL 10/30/08 WAS FOR A BLDG REVIEW ONLY,
 ROUTED TO TRADES IN ERROR./WRT.
2008-10-17 14:05:43 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By btrobaug Date 2008-10-02 Time 11:35 Rev Time 0.00
Received By btrobaug Date 2008-10-02 Time 10:11 Sent To P
Notes
2008-10-02 10:29:21 
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-11-17 Cont ID  
Sent By adarroug Date 2008-11-17 Time 14:46 Rev Time 0.00
Received By adarroug Date 2008-11-17 Time 14:46 Sent To Z
Notes
2008-11-17 14:46:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-23 Cont ID  
Sent By adarroug Date 2008-10-23 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-10-23 Time 10:56 Sent To Z
Notes
2008-10-23 10:56:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-17 Cont ID  
Sent By lmartine Date 2008-10-17 Time 17:17 Rev Time 0.00
Received By lmartine Date 2008-10-02 Time 09:27 Sent To  
Notes
2008-10-02 09:27:50TO "BTROBAUG" DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-10-02 Cont ID  
Sent By tgordon Date 2008-10-02 Time 16:12 Rev Time 0.25
Received By tgordon Date 2008-10-02 Time 16:12 Sent To B
Notes
2008-10-02 16:14:04SENT TO LUIS MARTINEZ.
  
 ** NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-11-03 Cont ID  
Sent By mperson Date 2008-11-03 Time 10:43 Rev Time 0.45
Received By mperson Date 2008-11-03 Time 10:43 Sent To B
Notes
2008-11-03 10:50:47****************PROVISO****************
 PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-10-02 Cont ID  
Sent By mperson Date 2008-10-02 Time 15:25 Rev Time 1.30
Received By mperson Date 2008-10-02 Time 15:25 Sent To M
Notes
2008-10-02 15:39:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A
 PLUMBING PERMIT IS BEING APPLIED FOR. PLEASE PROVIDE
 THE FOLLOWING INFORMATION IF IT PERTAINS TO YOUR JOB.
  
 A} IF PLUMBING FLOOR PLAN LAYOUT IS THE SAME AND THE
 PLUMBING FIXTURES ARE TO BE CHANGED, PLEASE INDICATE ON
 THE RESUBMITTED DRAWINGS. "EXACT FIXTURE CHANGEOUT
 ONLY" AND CLEARLY INDICATE WHAT FIXTURES ARE GOING TO
 BE CHANGED ON THE PLANS.
  
 B} IF THE NEW PROPOSED PLUMBING FLOOR PLAN LAYOUT IS
 DIFFERENT FROM THE EXISTING FLOOR PLAN PLEASE SUBMIT
 THE FOLLOWING ON SEPERATE DRAWINGS.
 A) EXISTING FLOOR PLAN LAYOUT.
 B) NEW PROPOSED FLOOR PLAN LAYOUT AND PLEASE FOLLOW
 WHAT IS REQUIRED IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1 (W.P.B. AS AMENDED), SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) (9)
 PLUMBING. PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC
 RISER DIAGRAM INDICATING ALL PROPOSED WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-11-26 Cont ID  
Sent By mcruz Date 2008-11-26 Time 15:20 Rev Time 0.00
Received By mcruz Date 2008-11-26 Time 15:17 Sent To B
Notes
2008-11-26 15:20:16PRIVOSO AS NOTED ON EXHIBIT E-1, LAYOUT OF REAR UNIT
 THE KITCHEN ON EAST SIDE SHALL BE REMOVED.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-29 Cont ID  
Sent By mcruz Date 2008-10-30 Time 12:50 Rev Time 0.00
Received By mcruz Date 2008-10-29 Time 14:53 Sent To P
Notes
2008-10-30 13:04:49***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. BASED ON THE CITY OF WEST PALM BEACH RECORDS, THE
 ORIGINAL LAYOUT OF THE BUILDINGS AS DEPICTED ON THE
 "GREEN CARD" (COPY ATTACHED) SHOWS TWO (2) RESIDENCES
 WITH AN ATTACHED GARAGE IN THE REAR. THE CURRENT LAYOUT
 PROVIDED INDICATES THREE (3) DWELLING UNITS. THE
 DEFINITION OF A DWELLING UNIT MAY BE FOUND IN THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-611: DEFINITIONS.
  
 PLEASE PROVIDE VERIFICATION (I.E. BUILDING PERMIT) OF
 THE CONVERSION OF THE REAR GARAGE TO A DWELLING UNIT.
 PURSUANT TO THE ZLDR, SECTION 94-72: SINGLE-FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT AND SECTION 94-272,
 PERMITTED USE TABLE LINE ITEM 133: SINGLE FAMILY
 DETACHED, ONLY ALLOWS ONE (1) DWELLING UNIT PER
 PROPERTY. THEREFORE, THE REAR DWELLING UNIT IS
 CONSIDERED A MINOR USE NON-CONFORMITY WITH NO ADVERSE
 IMPACTS.
  
 3. PROVIDE THE SCOPE OF WORK AND VALUATION FOR EACH
 BUILDING ON THE PROPERTY. PURSUANT TO THE ZLDR SECTION
 94-513(B)(1)(D): NONCONFORMING USES WITH NO ADVERSE
 IMPACTS PROVIDED THE COSTS INCURRED WITHIN ANY 12-MONTH
 PERIOD SHALL NOT EXCEED 50 PERCENT OF THE VALUE OF THE
 STRUCTURE OR BUILDING PRIOR TO THE COMMENCEMENT
 THEREOF.
  
 4. BASED ON THE ADDITIONAL VALUATION OF $4,000 FOR A
 SEPARATE PLUMBING PERMIT (PERMIT # 08080068), THE TOTAL
 VALUATION (INCLUDING THE MASTER PERMIT # 08090238) IS
 $34,000, WHICH EXCEEDS THE 50 PERCENT RULE FOR
 LANDSCAPING. PURSUANT TO THE ZLDR, SECTION
 94-441(C)(2): AS THE VALUE OF THE PROPOSED WORK EXCEEDS
 50 PERCENT OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 REPEAT COMMENT:
  
 PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 NOTE: FOR PRIOR BUILDING PERMIT RECORDS, CONTACT APRIL
 PICARILLO (561.805.6662) WITH SURVEYS AND PLANS FOR A
 RESEARCH REQUEST FORM.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-10-17 Cont ID  
Sent By mcruz Date 2008-10-17 Time 11:59 Rev Time 0.00
Received By mcruz Date 2008-10-17 Time 11:17 Sent To E
Notes
2008-10-17 11:59:15***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE IF THE PROPOSED PROJECT WILL RESULT IN AN
 INCREASE IN SQUARE FOOTAGE OF THE HOME. IF YES, PLEASE
 INDICATE THE SETBACK DIMENSIONS OF ALL EXTERIOR
 IMPROVEMENTS TO ALL ADJACENT PROPERTY LINES. NOTE: CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-72: SINGLE FAMILY LOW
 DENSITY (SF7) RESIDENTIAL DISTRICT - MINIMUM SETBACKS
 FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. AS PER SECTION 94-305(B) OF THE ZLDRS:
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
 5. IF APPLICABLE, INDICATE SETBACK DIMENSIONS FROM
 PROPOSED AND/OR RELOCATED A/C EQUIPMENT TO ALL PROPERTY
 LINES. AS PER SECTION 94-305(B)(4) OF THE ZLDRS:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  