Plan Review Details - Permit 08090228
Plan Review Stops For Permit 08090228
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-07 Cont ID  
Sent By shill Date 2008-10-07 Time 17:28 Rev Time 0.00
Received By shill Date 2008-10-07 Time 17:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-10-01 Cont ID  
Sent By shill Date 2008-10-01 Time 15:58 Rev Time 0.00
Received By shill Date 2008-10-01 Time 15:58 Sent To  
Notes
2008-10-01 16:07:58****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 2. SHOW ALL EXIT DOORS ON THE FLOOR PLAN. EXITS CANNOT
 BE BLOCKED WITH STORM PANELS, FBC1003.6.
  
 SEE FBC1003.6, MEANS OF EGRESS CONTINUITY; THE PATH OF
 EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT
 OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN
 CHAPTER 10 OF THE FLORIDA BUILDING CODE. SEE ALSO
 FBC1008.1.3.5 AND FBC1008.1.3.6; TEMPORARY INSTALLATION
 OR CLOSURE OF STORM SHUTTERS IS PERMITTED IN R
 OCCUPANCIES ONLY. THIS IS NOT PERMITTED IN OCCUPANCIES
 OTHER THAN RESIDENTIAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-18 Cont ID  
Sent By shill Date 2008-09-18 Time 14:53 Rev Time 0.00
Received By shill Date 2008-09-18 Time 14:53 Sent To  
Notes
2008-09-18 15:07:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE INFORMATION REGARDING THE BUILDING LOCATION
 TO CLARIFY USE OF EXPOSURE B. SEE FBC1609.4; NOTE THAT
 THE DEFINITION FOR EXPOSURE C HAS CHANGED EFFECTIVE
 JULY 1, 2007.
  
 2. SHOW ALL EXIT DOORS ON THE FLOOR PLAN. EXITS CANNOT
 BE BLOCKED WITH STORM PANELS, FBC1003.6.
  
 3. OPENING 1, A DESIGN PRESSURE OF -34.9 REQUIRES USE
 OF THE ROW -44.2, SEE PAGE 4. SEE ANCHOR NOTES, PAGE 6,
 ITEM2 - "ENTER ANCHOR SCHEDULE BASED ON THE EXISTING
 STRUCTURE MATERIAL ANCHOR TYPE AND EDGE DISTANCE.
 SELECT DESIGN LOAD GREATER THAN OR EQUAL TO NEGATIVE
 DESIGN LOAD ON SHUTTER." A DESIGN PRESSURE OF -34.9 IS
 CONSIDERED A GREATER NEGATIVE DESIGN PRESSURE THAN -33.
 THIS COMMENT APPLIES TO OTHER OPENINGS (INCORRECT ROW
 USED; ALL PRESSURES FOR THIS JOB ARE GREATER THAN
 -33PSF). FBC R301.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 09:08 Sent To B
Notes
2008-10-06 09:08:28TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 11:28 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 11:28 Sent To B
Notes
2008-09-24 11:29:04TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-18 Cont ID  
Sent By shill Date 2008-09-18 Time 15:07 Rev Time 0.00
Received By shill Date 2008-09-11 Time 12:32 Sent To  
Notes
2008-09-11 12:33:16TO "MISC" BOX#1