Plan Review Details - Permit 08090199
Plan Review Stops For Permit 08090199
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jwitmer Date 2008-11-04 Time 13:11 Rev Time 0.33
Received By jwitmer Date 2008-11-04 Time 13:11 Sent To  
Notes
2008-11-04 13:12:11PASSED SE -LIGHT POLES AND ACCESSIBLE PARKING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-09-30 Cont ID  
Sent By jwitmer Date 2008-09-29 Time 06:52 Rev Time 1.55
Received By jwitmer Date 2008-09-29 Time 06:52 Sent To  
Notes
2008-09-29 13:42:45PASSED SE- LIGHT POLES
 ACCESSIBILITY PARKING

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2009-04-16 Cont ID  
Sent By dpalmer Date 2009-04-16 Time 15:40 Rev Time 0.00
Received By dpalmer Date 2009-04-16 Time 15:40 Sent To PC
Notes
2009-04-16 15:41:46REVISED SITE HAS ALREADY BEEN SUBMITTED AND REVISED
 UNDER ALL OTHER PERMITS INCLUDING BATHROOMS, AND
 SHELTERS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 11:14 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 11:14 Sent To  
Notes
2008-10-31 11:14:29** REDLINED PLANS**
  
 1) NOTE: PLANS STILL DO NOT INDICATE THE ADDRESS
 LOCATION OF 150 CLEARWATER DR. THIS WAS HAND WRITTEN ON
 ELECTRICAL PLAN BY THIS REVIEWER IN ORDER TO PASS THE
 REVIEW.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 11:08 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 11:08 Sent To  
Notes
2008-09-30 11:08:47 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 ON ELECTRICAL PLANS AT A MINIMUM.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SHOW GROUNDING LOCATION AND SYSTEM FOR
 TRANSFORMER(S) PER 250.50,250.66,250.20,250.30.
  
 3) NOTE: DISCONNECTS AT SHELTERS AND AT RESTROOM
 BUILDING. RESTROOM BUILDING SHOWS A MAIN LUG ONLY
 PANEL. PER 225.31-225.39
  
 4) NOTE: PLEASE SEE 250.32,250.50 FOR GROUNDING AT
 SHELTERS AND AT RESTROOM BUILDING.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 LEVELS/CALCULATIONS FOR LIGHTING PER FBC
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR
 WORST CASE FOR SERVICE FEEDERS AND BRANCH CIRCUITS PER
 FBC 13-413.1.ABC.1.1, .1.2.
  
 7) NOTE: PLEASE INDICATE WHERE CONTINUOUS LOADS ARE
 FIGURED OR SHOWN. 215.3,230.42 ETC
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2009-04-09 Cont ID  
Sent By mgonzale Date 2009-04-09 Time 13:58 Rev Time 1.00
Received By mgonzale Date 2009-04-09 Time 13:57 Sent To  
Notes
2009-04-09 13:58:37PLANS ACCEPTED BY ENGINEERING DEPT. 04/09/09
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-11-25 Cont ID  
Sent By dlauderm Date 2008-11-25 Time 14:10 Rev Time 0.00
Received By dlauderm Date 2008-11-25 Time 14:09 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-09-23 Cont ID  
Sent By rchokshi Date 2008-09-23 Time 14:20 Rev Time 0.00
Received By rchokshi Date 2008-09-23 Time 14:15 Sent To  
Notes
2008-09-23 14:20:01FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B), EFFECTIVE
 MAY 1, 2003
  
 2. PLEASE PROVIDE A COPY OF BOND FOR ORDINANCE NO.
 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3.PLEASE SHOW ON DRAWINGS DUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, & LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 4. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 5. PLEASE SHOW ON DRAINAGE DRAWING THE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREA YOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASE MAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CAN SEE THE LAYOUT OF STORM WATER PIPES FROM ALL
 OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST, AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 8. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, GEO-TECH
 REPORT & STORM WATER QUALITY CALCULATIONS TO 1000 45TH
 STREET FOR THEIR APPROVAL BEFORE WE ISSUE A PERMIT.
  
 9. WATER & SEWER PLANS MUST BE APPROVED FROM MANNY G.
 OF 1000 45TH STREET BEFORE WE ISSUE A PERMIT.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI 805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By mwennerg Date 2008-10-31 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2008-10-31 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-03 Cont ID  
Sent By mwennerg Date 2008-10-03 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2008-10-03 Time 13:45 Sent To  
Notes
2008-10-03 13:49:54***DENIED***
  
 1) SHEET SP-1 ILLUSTRATES AN ACCESS GATE FOR EMERGENCY
 VEHICLES. PROVIDE INFORMATION REGARDING GATE OPERATION
 TO INCLUDE MANUFACTURER SPECIFICATIONS IF APPLICABLE.
  
 2) INDICATE EXISTING AND NEW FIRE HYDRANT LOCATIONS
 PERTINENT TO THIS PROJECT.
  
  
 ALTHOUGH NOT A REQUIREMENT, A RESPONSE LETTER
 INDICATING HOW AND WHERE ON THE PLANS EACH COMMENT WAS
 ADDRESSED WOULD HELP TO EXPEDITE THE PLAN REVIEW
 PROCESS.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-06 Cont ID  
Sent By adarroug Date 2009-04-06 Time 11:36 Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 11:36 Sent To  
Notes
2009-04-06 11:36:37TO "C17"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-29 Cont ID  
Sent By adarroug Date 2008-10-29 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-10-29 Time 11:46 Sent To  
Notes
2008-10-29 11:46:36TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-03 Cont ID  
Sent By mwennerg Date 2008-10-03 Time 14:10 Rev Time 0.00
Received By mwennerg Date 2008-09-10 Time 09:33 Sent To  
Notes
2008-09-10 09:33:16TO "COMM" BD#62

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-11-18 Cont ID  
Sent By kstevens Date 2008-11-18 Time 11:20 Rev Time 0.00
Received By kstevens Date 2008-11-18 Time 11:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-11-14 Cont ID  
Sent By kstevens Date 2008-11-14 Time 07:21 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 15:57 Sent To  
Notes
2008-11-14 07:26:19DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. MINIMUM 2 SETS OF PLANS REQUIRED WITH THE
 APPLICATION FOR PERMIT. THE SHEETS 41 THRU 45A
 INDICATED IN THE PLAN INDEX FOR LANDSCAPE AND
 IRRIGATION PLANS HAVE NOT BEEN SUBMITTED. PLEASE SUBMIT
 ALL SHEETS INDICATED IN THE INDEX ON THE COVER SHEET.
 SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2008-09-12 Cont ID  
Sent By kstevens Date 2008-09-12 Time 08:30 Rev Time 0.00
Received By kstevens Date 2008-09-11 Time 14:28 Sent To  
Notes
2008-09-12 08:35:58IRRIGATION OK -- PLANS FOR THE PUBLIC RESTROOM AND
 OTHER STRUCTURES SHALL BE SEPARATED FROM UTILITIES
 PLANS AND SUBMITTED UNDER A SEPARATE BLD-COM PERMIT
 WITH SEPARATE SUB PERMITS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-03 Cont ID  
Sent By mflis Date 2008-11-03 Time 08:44 Rev Time 0.00
Received By mflis Date 2008-11-03 Time 08:44 Sent To  
Notes
2008-11-03 08:45:42ZONING REVIEW: PASSED (INCLUDING LANDSCAPE)
  
 ** INTERMODAL FACILITY
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-15 Cont ID  
Sent By mflis Date 2008-09-15 Time 14:58 Rev Time 0.00
Received By mflis Date 2008-09-15 Time 14:58 Sent To  
Notes
2008-09-15 15:09:32ZONING REVIEW: FAILED
  
 ** GENERAL COMMENT: PLEASE COORDINATE LOCATION OF LIGHT
 FIXTURES WITH LANDSCAPE MATERIALS AND OTHER ELEMENTS TO
 AVOID CONFLICT **
 ** GENERAL COMMENT: LIGHT POLES SHOULD BE LOCATED TO
 THE BACK OR FRONT OF SIDEWALK CONSISTENTLY, BUT NEVER
 IN MIDDLE OF SIDEWALK **
 ** GENERAL COMMENT: DRAWING INDICATE "BID SET" - SHOULD
 THESE BE FINAL CONSTRUCTION DRAWINGS?
  
 - LP-2 - LIGHT POLE VERY CLOSE TO BIKE RACKS EAST OF
 BUS LOOP; MUST BE CLEARANCE FOR BIKES TO BE
 LOADED/REMOVED FROM RACKS (6'-0")
 - LP-2 - THREE POLES FURTHEST SOUTH APPEAR CLOSE TO
 SABALS; CONFIRM THEY WILL BE CLEAR OF PLANT MATERIAL,
 OR ADJUST LOCATION
 - LP-3 - AT PRIMARY CROSSWALK, LIGHT POLE INDICATED ON
 TOP OF FOXTAIL PALM; ADJUST POLE
 - LP-3 - WEST SIDE OF BUS LOOP, LIGHT POLES APPEAR TO
 CONFLICT WITH SABALS; PLEASE CONFIRM; ADJUST POLES TO
 BE IN CONSISTENT LOCATION IN RELATION TO SIDEWALK
 - LP-3 - NORTH OF "KISS-N-RIDE" BUS SHELTER, LIGHT POLE
 IN MILLE OF SIDEWALK AREA LEADING FROM DROP-OFF TO BUS
 LOOP; MOVE POLE OUT OF PEDESTRIAN CIRCULATION
 - LP-3 - AROUND PEDESTRIAN CIRCLE AND WALKWAY, CONFIRM
 POLES DO NOT CONFLICT WITH TALLER PLANT MATERIALS
 - LP-4 - LIGHT POLE SOUTHWEST CORNER OF BUS LOOP
 APPEARS IN MIDDLE OF SIDEWALK
 - LP-4 - LIGHT POLE NORTH END OF BUS LOOP AREAS TO
 CONFLICT WITH LIVE OAK TREE
 - LP-4 - LIGHT POLES ALONG CURVED SIDEWALK CONNECTING
 PARKING AND BUILDING SEEM TO CONFLICT WITH LIVE OAKS;
 ADJUST WHERE NECESSARY
 - NO ADDITIONAL LIGHT POLES APPEAR ALONG CLEARWATER; IS
 THIS CORRECT? CONFIRM NO ADDITIONAL LIGHTING IS
 NECESSARY ALONG THE STREET
  
 - LP-1 - 2 HOLLYS SOUTH END OF CLEARWATER SHOULD HAVE A
 CALL-OUT (IA)
 - LP-3 - LIVE OAKS/GRATES ALONG EAST SIDE OF BUS LOOP
 SEEM TO IMPINGE UPON EXISTING FENCE; PLEASE CONFIRM
 THIS IS CORRECT, OTHERWISE ADJUST LOCATIONS; TREES
 GENERALLY SHOULD ALIGN NORTH-TO-SOUTH WHERE POSSIBLE
 - TREE ALTERNATION PERMIT IS NECESSARY
 - BIKE RACKS SHOULD BE BLACK; INVERTED "U" MODEL RACKS
 ARE PREFERABLE
  
  
 MATT FLIS - 822-1445
  
  