Plan Review Details - Permit 08090174
Plan Review Stops For Permit 08090174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-11-18 Cont ID  
Sent By jwitmer Date 2008-11-18 Time 07:35 Rev Time 0.77
Received By jwitmer Date 2008-11-18 Time 07:35 Sent To  
Notes
2008-11-18 07:49:52BUILDING PROVISO:
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By jwitmer Date 2008-09-26 Time 15:30 Rev Time 1.33
Received By jwitmer Date 2008-09-26 Time 15:30 Sent To  
Notes
2008-09-26 15:43:18BUILDING PLAN REVIEW
 PERMIT: 08090174
 ADD: 2050N CONGRESS AVE
 CONT: ENGINEERED ENVIROMENTS INC
 TEL: (561)282-4111
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) COVER SHEET INDICATES THE WIND DESIGN TO ASCE 7-98,
 PLEASE CORRECT. 2004 FBC 1609.1.1 & CHAPTER 35
 REFERENECED STANDARDS RECOGNIZES ASCE 7-02 . ALSO
 1603.1.4 WIND DESIGN DATA.
  
 3) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4) PLANS INDICATE THE NEW ANTENNAS ARE BEING INSTALLED
 ON THE EXTERIOR OF THE VERTICAL EXIT ENCLOSURE. PLANS
 DO NOT INDICATE THE ROUTING OR INSTALLATION OF CABLES
 TO UNMANNED ATT CABINERTRY.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-11-06 Cont ID  
Sent By dpalmer Date 2008-11-06 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2008-11-06 Time 11:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By dpalmer Date 2008-09-17 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2008-09-17 Time 16:32 Sent To  
Notes
2008-09-17 16:32:31** DENIED REVIEW **
  
  
 1) NOTE: PLEASE INDICATE COMPLIANCE FOR NEW OR EXISTING
 WHICH MEETS FEDERAL CODE OF REGULATIONS TITLE 47 PART
 12.2 FOR BACK UP POWER OF 8HOURS MINIMUM.
  
 2) NOTE: ELECTRICAL SYSTEMS MAY OR MAY NOT BE COMPLETE
 AT THIS TIME. NEC 2005 AND AS NOTED ABOVE.
  
 3) NOTE: PLEASE SEE THE LATEST EDITION OF NFPA-70 MAY
 NOT BE STATED. PLEASE SEE FS 553.73 WHICH REQUIRES 2005
 NFPA-70
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-11-14 Cont ID  
Sent By mwennerg Date 2008-11-14 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2008-11-14 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-07 Cont ID  
Sent By mwennerg Date 2008-10-07 Time 11:36 Rev Time 0.00
Received By mwennerg Date 2008-10-07 Time 11:36 Sent To  
Notes
2008-10-07 11:41:28***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES, LIFE
 SAFETY SHALL COMPLY WITH NFPA 101, 2003.
  
 2) WORK SHALL COMPLY WITH 101, SEC. 7.1.3.2 (6) AND
 (7). PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE SHALL BE LIMITED TO EQUIPMENT ALLOWED IN
 REFERENCED SECTION.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 11:03 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 11:03 Sent To  
Notes
2008-11-03 11:06:14TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-07 Cont ID  
Sent By mwennerg Date 2008-10-07 Time 11:46 Rev Time 0.00
Received By mwennerg Date 2008-09-08 Time 16:13 Sent To  
Notes
2008-09-08 16:20:44TO "COMM" BD#14

Review Stop Z ZONING
Rev No 2 Status P Date 2008-11-04 Cont ID  
Sent By jroach Date 2008-11-04 Time 17:36 Rev Time 0.00
Received By jroach Date 2008-11-04 Time 17:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2008-09-11 Cont ID  
Sent By jroach Date 2008-09-11 Time 10:44 Rev Time 0.00
Received By jroach Date 2008-09-11 Time 10:44 Sent To  
Notes
2008-09-11 10:45:24***PROVISO***
  
 NEW ANTENNAS SHALL BE PAINTED TO MATCH THE EXTERIOR OF
 THE BUILDING.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.