Plan Review Details - Permit 08090166
Plan Review Stops For Permit 08090166
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-02-11 Cont ID  
Sent By jgomez Date 2009-02-11 Time 14:10 Rev Time 0.00
Received By jgomez Date 2009-02-11 Time 14:10 Sent To PC
Notes
2009-02-11 14:11:08NEED SEPARATE FOR THE LIFT STATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-01-13 Cont ID  
Sent By jgomez Date 2009-01-13 Time 10:11 Rev Time 0.00
Received By jgomez Date 2009-01-13 Time 09:50 Sent To PC
Notes
2009-01-13 10:20:59ELECTRICAL POLE BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PERMIT APPLICATION IS FOR THE LIFT STATION
 ELECTRICAL WORK ONLY. A SEPARATE PERMIT APPLICATION IS
 REQUIRED FOR THE LIFT STATION. THE FOLLOWING COMMENTS
 APPLY ONLY TO THE ELECTRICAL WORK ON PERMIT APPLICATION
 SUBMITTED.
  
 2- LIGHT POLE ENGINEERED CALCULATIONS SUBMITTED:
 A) "ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS AND NUMBER ON EACH SHEET" AS REQUIRED BY SEC.
 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND
 CHAPTER 471 FLORIDA STATUTE.
  
 B) NEED TO PROVIDE THE ENGINEERING FIRM "PRINCIPAL
 ENGINEERING" CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE.
  
 C) ALL SHEETS NEED TO BE SIGNED AND SEALED WITH
 ORIGINAL SEAL AND SIGNATURE, NOT COPY OF THE SIGNATURE.
 SEE FLORIDA ADMINISTRATIVE CODE SECTION AND FLORIDA
 STATUTE SECTION CITED ABOVE. CALCULATIONS SUBMITTED ARE
 SEALED ONLY ON THE FRONT PAGE AND THE SIGNATURE IS A
 PHOTOCOPY. RESUBMIT CALCULATIONS COMPLYING WITH ALL THE
 ADMINISTRATIVE CODE AND FLORIDA STATUTE REQUIREMENTS.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED
 CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED
 CALCULATIONS REQUIRED ON ITEM #1 ABOVE. ENGINEER TO
 REVIEW THOSE SHOP DRAWINGS PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL
 ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-11-06 Cont ID  
Sent By jgomez Date 2008-11-06 Time 11:35 Rev Time 0.00
Received By jgomez Date 2008-11-06 Time 11:05 Sent To PC
Notes
2008-11-06 11:39:04ELECTRICAL POLE BUILDING REVIEW SECOND CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
  
 ***NOTE: NONE OF THE COMMENTS FROM FIRST CHECKLIST WERE
 ADDRESSED. SEE COMMENTS BELOW:
  
 1- PROVIDE THE LIGHT POLE ENGINEERED CALCULATIONS AS
 REQUIRED BY NOTE ON LIGHT POLE DETAIL AND BY SEC. 1609
 OF FBC 2004.
  
 2- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED
 CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED
 CALCULATIONS REQUIRED ON ITEM #1 ABOVE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL
 ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By jgomez Date 2008-09-26 Time 13:40 Rev Time 0.00
Received By jgomez Date 2008-09-26 Time 13:40 Sent To Z
Notes
2008-09-26 13:49:24ELECTRICAL POLE BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- PROVIDE THE LIGHT POLE ENGINEERED CALCULATIONS AS
 REQUIRED BY NOTE ON LIGHT POLE DETAIL AND BY SEC. 1609
 OF FBC 2004.
  
 2- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED
 CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED
 CALCULATIONS REQUIRED ON ITEM #1 ABOVE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL
 ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS
 AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-10 Cont ID  
Sent By dpalmer Date 2009-02-10 Time 09:22 Rev Time 0.00
Received By dpalmer Date 2009-02-10 Time 09:22 Sent To B
Notes
2009-02-10 09:23:04ELECTRIC FOR SERIVE AND LIGHT POLE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-12-22 Cont ID  
Sent By dpalmer Date 2008-12-22 Time 12:21 Rev Time 0.00
Received By dpalmer Date 2008-12-22 Time 12:21 Sent To ENG
Notes
2008-12-22 12:21:52** DENIED **
  
  
  
 1) NOTE: PLEASE SEE THE EXACT SAME COMMENTS FROM
 PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING.
  
 2) NOTE: THE VALUE FOR SCOPE OF WORK WAS NOT INCREASED.
 FBC108.3.
  
 3) NOTE: PLEASE KNOW THERE WILL BE COMMENTS WITH
 RESPECT TO CALCULATIONS SUBMITTED FOR WIND LOADS AND
 POLES. THE CALCULATIONS CONTAIN A RAISED SEAL OVER
 PHOTO-COPIED SIGNATURES WHICH ARE NOT PERMITTED PER FAC
 61G15-23.002, FS 471.025. SPOKE TO THE ENGINEER OF
 RECORD WITH RESPECT TO PHOTO-COPIED SIGNATURE.
  
  
 ** COMMENT #2 ABOVE NEEDS TO BE ADDRESSED FOR
 ELECTRICAL REVIEW BEFORE REVIEW STATUS MAY CHANGE.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-10-28 Cont ID  
Sent By dpalmer Date 2008-10-28 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2008-10-28 Time 15:39 Sent To  
Notes
2008-10-28 15:39:55 
  
  
 ** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SEE NOTES WITH RESPECT TO VALUATION OF
 THE COMPLETE SCOPE OF WORK AS SHOWN.
 VALUE WAS NOT INCREASED. FBC 108.3
 ALL LABOR, MATERIALS, EQUIPMENT, FIXTURES, DESIGN COST,
 ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED.
  
 2) NOTE: PLEASE SEE BUILDING COMMENTS WITH RESPECT TO
 INFORMATION REQUIRED FOR POLE(S). PLAN STATE *AS
 REQUIRED* HOWEVER NO BASIC INFORMATION WITH DIMENSIONS
 ETC ARE SHOWN. SEE NOTES FROM THE BUILDING REVIEWER.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-11 Cont ID  
Sent By dpalmer Date 2008-09-11 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2008-09-11 Time 08:21 Sent To B
Notes
2008-09-11 08:21:55 
  
  
  
 ** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SEE APPLIED VALUE FOR COMPLETE SCOPE OF
 WORK AS SHOWN SHALL BE PER FBC 108.3. VALUE IS TO
 INCLUDE ALL LABOR, MATERIALS EQUIPMENT, DESIGN COSTS
 ETC EVEN IS ANY OF THESE ITEMS ARE OWNER SUPPLIED.
 THE VALUE IS LOW BASED ON THE SCOPE SHOWN ON PLANS.
 EQUIPMENT ON PLANS ALONE EXCEEDS THE APPLIED VALUE.
  
 2) NOTE: PLEASE INDICATE THE METHOD OF LIGHTING CONTROL
 FOR POLE LIGHT PER 13-415.1.ABC.1.4.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-01-13 Cont ID  
Sent By jgomez Date 2009-01-13 Time 10:10 Rev Time 0.00
Received By jgomez Date 2009-01-13 Time 10:10 Sent To  
Notes
2009-01-13 10:10:57THIS PERMIT APPLICATION IS FOR ELECTRICAL WORK ONLY.
 CONTRACTOR WAS ADVISED THAT SEPARATE PERMIT APPLICATION
 IS REQUIRED FOR THE LIFT STATION. ENGINEERING COMMENTS
 TO BE ADDRESSED ON SUCH PERMIT APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-12-10 Cont ID  
Sent By adarroug Date 2008-12-10 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-12-10 Time 11:14 Sent To Z
Notes
2008-12-10 11:20:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-11-06 Cont ID  
Sent By jgomez Date 2008-11-06 Time 11:06 Rev Time 0.00
Received By jgomez Date 2008-11-06 Time 11:05 Sent To  
Notes
2008-10-22 14:50:50TO "Z" BOX/RESUB

Review Stop P PLUMBING
Rev No 1 Status N Date 2008-11-06 Cont ID  
Sent By kstevens Date 2008-11-06 Time 07:56 Rev Time 0.00
Received By kstevens Date 2008-11-06 Time 07:56 Sent To B1
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status N Date 2009-01-13 Cont ID  
Sent By jgomez Date 2009-01-13 Time 10:07 Rev Time 0.00
Received By jgomez Date 2009-01-13 Time 10:07 Sent To  
Notes
2009-01-13 10:09:15THIS PERMIT APPLICATION IS FOR ELECTRICAL WORK ONLY.
 CONTRACTOR WAS ADVISED THAT SEPARATE PERMIT APPLICATION
 IS REQUIRED FOR THE LIFT STATION. ZONING COMMENTS TO BE
 ADDRESSED ON SUCH PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-12-18 Cont ID  
Sent By mcruz Date 2008-12-18 Time 09:12 Rev Time 0.00
Received By mcruz Date 2008-12-15 Time 11:13 Sent To E
Notes
2008-12-18 09:06:11PLANNING AND ZONING DEPT: ***ZONING FAILED - 2ND
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 REPEAT COMMENTS:
  
 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT
 TO ALL PROPERTY LINES. PURSUANT TO THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO AN REQUIRED SETBACK.
  
 3. PURSUANT TO THE ZLDR, SECTION 94-444(B): OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR
 PROPANE TANKS, AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS PROVIDED. SCREENING
 SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. WALLS SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS. .... PLANS FOR
 THE LAYOUT OF TRASH RECEPTACLES SHALL BE IN ACCORDANCE
 WITH THE MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-3
 (ATTACHED). CHAIN LINK ENCLOSURES ARE NOT ACCEPTABLE.
  
 NEW COMMENTS:
  
 4. CLEARLY INDICATE ON THE SITE PLAN THE LOCATION THE
 LIFT STATION AREA AND SHOW AN ENLARGED DETAIL WHICH
 INCLUDES THE COMPLIANCE OF THE ABOVE MENTIONED
 SCREENING REQUIREMENTS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2008-10-24 Cont ID  
Sent By mcruz Date 2008-10-24 Time 16:16 Rev Time 0.00
Received By mcruz Date 2008-10-24 Time 16:12 Sent To E
Notes
2008-10-24 16:16:12***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 REPEAT COMMENTS:
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT
 TO ALL PROPERTY LINES. AS PER SECTION94-305(B)(4) OF
 THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO AN REQUIRED SETBACK.
  
 4. PURSUANT THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-444(B):
 OUTDOOR INCINERATORS, GARBAGE OR TRASH RECEPTACLES,
 FUEL OIL OR PROPANE TANKS, AND STORAGE RACKS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. A
 FOUR-SIDED ENCLOSURE WITH AN OBSCURING GATE MAY BE
 REQUIRED AS A CONDITION FOR SITE PLAN APPROVAL. PLANS
 FOR THE LAYOUT OF TRASH RECEPTACLES SHALL BE IN
 ACCORDANCE WITH THE MINIMUM REQUIREMENTS SET FORTH IN
 FIGURE XIV-3 (ATTACHED). CHAIN LINK ENCLOSURES ARE NOT
 ACCEPTABLE. WALLS SHALL BE IRRIGATED AND LANDSCAPED
 WITH SHRUBS AND HEDGES PLANTED AT TWO (2) FEET
 INTERVALS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-26 Cont ID  
Sent By mcruz Date 2008-09-26 Time 16:32 Rev Time 0.00
Received By mcruz Date 2008-09-26 Time 15:58 Sent To  
Notes
2008-09-26 16:32:25***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT
 TO ALL PROPERTY LINES. PURSUANT TO THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY
 NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 4. PURSUANT TO THE ZLDR SECTION 94-444(B): LANDSCAPE
 SCREENING SHALL BE PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  