Plan Review Stops For Permit 08090166 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2009-02-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-02-11 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-02-11 |
Time |
14:10 |
Sent To |
PC |
|
Notes |
2009-02-11 14:11:08 | NEED SEPARATE FOR THE LIFT STATION. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2009-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-01-13 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-01-13 |
Time |
09:50 |
Sent To |
PC |
|
Notes |
2009-01-13 10:20:59 | ELECTRICAL POLE BUILDING REVIEW THIRD CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- PERMIT APPLICATION IS FOR THE LIFT STATION | | ELECTRICAL WORK ONLY. A SEPARATE PERMIT APPLICATION IS | | REQUIRED FOR THE LIFT STATION. THE FOLLOWING COMMENTS | | APPLY ONLY TO THE ELECTRICAL WORK ON PERMIT APPLICATION | | SUBMITTED. | | | | 2- LIGHT POLE ENGINEERED CALCULATIONS SUBMITTED: | | A) "ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, | | ADDRESS AND NUMBER ON EACH SHEET" AS REQUIRED BY SEC. | | 61G15-23.002(2) OF FLORIDA ADMINISTRATIVE CODE AND | | CHAPTER 471 FLORIDA STATUTE. | | | | B) NEED TO PROVIDE THE ENGINEERING FIRM "PRINCIPAL | | ENGINEERING" CERTIFICATE OF AUTHORIZATION NUMBER AS | | REQUIRED BY SEC. 61G15-23.002(2) OF FLORIDA | | ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. | | | | C) ALL SHEETS NEED TO BE SIGNED AND SEALED WITH | | ORIGINAL SEAL AND SIGNATURE, NOT COPY OF THE SIGNATURE. | | SEE FLORIDA ADMINISTRATIVE CODE SECTION AND FLORIDA | | STATUTE SECTION CITED ABOVE. CALCULATIONS SUBMITTED ARE | | SEALED ONLY ON THE FRONT PAGE AND THE SIGNATURE IS A | | PHOTOCOPY. RESUBMIT CALCULATIONS COMPLYING WITH ALL THE | | ADMINISTRATIVE CODE AND FLORIDA STATUTE REQUIREMENTS. | | | | 3- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED | | CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED | | CALCULATIONS REQUIRED ON ITEM #1 ABOVE. ENGINEER TO | | REVIEW THOSE SHOP DRAWINGS PRIOR TO SUBMITTAL TO THIS | | OFFICE. | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL | | ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-11-06 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-11-06 |
Time |
11:05 |
Sent To |
PC |
|
Notes |
2008-11-06 11:39:04 | ELECTRICAL POLE BUILDING REVIEW SECOND CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | ***NOTE: NONE OF THE COMMENTS FROM FIRST CHECKLIST WERE | | ADDRESSED. SEE COMMENTS BELOW: | | | | 1- PROVIDE THE LIGHT POLE ENGINEERED CALCULATIONS AS | | REQUIRED BY NOTE ON LIGHT POLE DETAIL AND BY SEC. 1609 | | OF FBC 2004. | | | | 2- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED | | CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED | | CALCULATIONS REQUIRED ON ITEM #1 ABOVE. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL | | ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-09-26 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-09-26 |
Time |
13:40 |
Sent To |
Z |
|
Notes |
2008-09-26 13:49:24 | ELECTRICAL POLE BUILDING REVIEW CHECKLIST. | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | 1- PROVIDE THE LIGHT POLE ENGINEERED CALCULATIONS AS | | REQUIRED BY NOTE ON LIGHT POLE DETAIL AND BY SEC. 1609 | | OF FBC 2004. | | | | 2- PROVIDE COMPLETE SPECIFICATIONS FOR PRE-STRESSED | | CONCRETE POLE TO VERIFY COMPLIANCE WITH THE ENGINEERED | | CALCULATIONS REQUIRED ON ITEM #1 ABOVE. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. NEED TO UPDATE PERMIT VALUATION TO INCLUDE ALL | | ENGINEERING FEES AND ALL CONTRACTOR LABOR AND MATERIALS | | AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2009-02-10 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2009-02-10 |
Time |
09:22 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2009-02-10 |
Time |
09:22 |
Sent To |
B |
|
Notes |
2009-02-10 09:23:04 | ELECTRIC FOR SERIVE AND LIGHT POLE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-12-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-12-22 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-12-22 |
Time |
12:21 |
Sent To |
ENG |
|
Notes |
2008-12-22 12:21:52 | ** DENIED ** | | | | | | | | 1) NOTE: PLEASE SEE THE EXACT SAME COMMENTS FROM | | PREVIOUS REVIEW ARE STILL IN NEED OF ADDRESSING. | | | | 2) NOTE: THE VALUE FOR SCOPE OF WORK WAS NOT INCREASED. | | FBC108.3. | | | | 3) NOTE: PLEASE KNOW THERE WILL BE COMMENTS WITH | | RESPECT TO CALCULATIONS SUBMITTED FOR WIND LOADS AND | | POLES. THE CALCULATIONS CONTAIN A RAISED SEAL OVER | | PHOTO-COPIED SIGNATURES WHICH ARE NOT PERMITTED PER FAC | | 61G15-23.002, FS 471.025. SPOKE TO THE ENGINEER OF | | RECORD WITH RESPECT TO PHOTO-COPIED SIGNATURE. | | | | | | ** COMMENT #2 ABOVE NEEDS TO BE ADDRESSED FOR | | ELECTRICAL REVIEW BEFORE REVIEW STATUS MAY CHANGE. | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2008-10-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-10-28 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-10-28 |
Time |
15:39 |
Sent To |
|
|
Notes |
2008-10-28 15:39:55 | | | | | | | ** DENIED REVIEW** | | | | | | 1) NOTE: PLEASE SEE NOTES WITH RESPECT TO VALUATION OF | | THE COMPLETE SCOPE OF WORK AS SHOWN. | | VALUE WAS NOT INCREASED. FBC 108.3 | | ALL LABOR, MATERIALS, EQUIPMENT, FIXTURES, DESIGN COST, | | ETC EVEN IF ANY OF THESE ARE OWNER SUPPLIED. | | | | 2) NOTE: PLEASE SEE BUILDING COMMENTS WITH RESPECT TO | | INFORMATION REQUIRED FOR POLE(S). PLAN STATE *AS | | REQUIRED* HOWEVER NO BASIC INFORMATION WITH DIMENSIONS | | ETC ARE SHOWN. SEE NOTES FROM THE BUILDING REVIEWER. | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2008-09-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-09-11 |
Time |
08:21 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-09-11 |
Time |
08:21 |
Sent To |
B |
|
Notes |
2008-09-11 08:21:55 | | | | | | | | | ** DENIED REVIEW ** | | | | | | | | 1) NOTE: PLEASE SEE APPLIED VALUE FOR COMPLETE SCOPE OF | | WORK AS SHOWN SHALL BE PER FBC 108.3. VALUE IS TO | | INCLUDE ALL LABOR, MATERIALS EQUIPMENT, DESIGN COSTS | | ETC EVEN IS ANY OF THESE ITEMS ARE OWNER SUPPLIED. | | THE VALUE IS LOW BASED ON THE SCOPE SHOWN ON PLANS. | | EQUIPMENT ON PLANS ALONE EXCEEDS THE APPLIED VALUE. | | | | 2) NOTE: PLEASE INDICATE THE METHOD OF LIGHTING CONTROL | | FOR POLE LIGHT PER 13-415.1.ABC.1.4. | | | | | | | | | | | | **IMPORTANT** | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | TWO SETS/FOLDERS/BINDERS ETC. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | ANY DELAYS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
N |
Date |
2009-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-01-13 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-01-13 |
Time |
10:10 |
Sent To |
|
|
Notes |
2009-01-13 10:10:57 | THIS PERMIT APPLICATION IS FOR ELECTRICAL WORK ONLY. | | CONTRACTOR WAS ADVISED THAT SEPARATE PERMIT APPLICATION | | IS REQUIRED FOR THE LIFT STATION. ENGINEERING COMMENTS | | TO BE ADDRESSED ON SUCH PERMIT APPLICATION. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2008-12-10 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-12-10 |
Time |
11:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-12-10 |
Time |
11:14 |
Sent To |
Z |
|
Notes |
2008-12-10 11:20:50 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2008-11-06 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2008-11-06 |
Time |
11:05 |
Sent To |
|
|
Notes |
2008-10-22 14:50:50 | TO "Z" BOX/RESUB |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2008-11-06 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-11-06 |
Time |
07:56 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-11-06 |
Time |
07:56 |
Sent To |
B1 |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
N |
Date |
2009-01-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2009-01-13 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2009-01-13 |
Time |
10:07 |
Sent To |
|
|
Notes |
2009-01-13 10:09:15 | THIS PERMIT APPLICATION IS FOR ELECTRICAL WORK ONLY. | | CONTRACTOR WAS ADVISED THAT SEPARATE PERMIT APPLICATION | | IS REQUIRED FOR THE LIFT STATION. ZONING COMMENTS TO BE | | ADDRESSED ON SUCH PERMIT APPLICATION. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2008-12-18 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-12-18 |
Time |
09:12 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-12-15 |
Time |
11:13 |
Sent To |
E |
|
Notes |
2008-12-18 09:06:11 | PLANNING AND ZONING DEPT: ***ZONING FAILED - 2ND | | RESUB*** | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | REPEAT COMMENTS: | | | | 2. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT | | TO ALL PROPERTY LINES. PURSUANT TO THE CITY OF WEST | | PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS | | (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY | | NOT PROJECT MORE THAN 4 FEET INTO AN REQUIRED SETBACK. | | | | 3. PURSUANT TO THE ZLDR, SECTION 94-444(B): OUTDOOR | | INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR | | PROPANE TANKS, AND STORAGE RACKS SHALL NOT BE PERMITTED | | UNLESS APPROPRIATE SCREENING IS PROVIDED. SCREENING | | SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE, | | OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD | | AND STEEL. WALLS SHALL BE LANDSCAPED WITH SHRUBS AND | | HEDGES PLANTED AT TWO-FOOT INTERVALS. .... PLANS FOR | | THE LAYOUT OF TRASH RECEPTACLES SHALL BE IN ACCORDANCE | | WITH THE MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-3 | | (ATTACHED). CHAIN LINK ENCLOSURES ARE NOT ACCEPTABLE. | | | | NEW COMMENTS: | | | | 4. CLEARLY INDICATE ON THE SITE PLAN THE LOCATION THE | | LIFT STATION AREA AND SHOW AN ENLARGED DETAIL WHICH | | INCLUDES THE COMPLIANCE OF THE ABOVE MENTIONED | | SCREENING REQUIREMENTS. | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | GENERATE ADDITIONAL COMMENTS. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1444 OR (561) 805-6720 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2008-10-24 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-10-24 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-10-24 |
Time |
16:12 |
Sent To |
E |
|
Notes |
2008-10-24 16:16:12 | ***ZONING FAILED*** | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | REPEAT COMMENTS: | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT | | TO ALL PROPERTY LINES. AS PER SECTION94-305(B)(4) OF | | THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE | | THAN 4 FEET INTO AN REQUIRED SETBACK. | | | | 4. PURSUANT THE CITY OF WEST PALM BEACH ZONING AND LAND | | DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-444(B): | | OUTDOOR INCINERATORS, GARBAGE OR TRASH RECEPTACLES, | | FUEL OIL OR PROPANE TANKS, AND STORAGE RACKS SHALL NOT | | BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED. | | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE | | CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY | | DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH | | SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS. A | | FOUR-SIDED ENCLOSURE WITH AN OBSCURING GATE MAY BE | | REQUIRED AS A CONDITION FOR SITE PLAN APPROVAL. PLANS | | FOR THE LAYOUT OF TRASH RECEPTACLES SHALL BE IN | | ACCORDANCE WITH THE MINIMUM REQUIREMENTS SET FORTH IN | | FIGURE XIV-3 (ATTACHED). CHAIN LINK ENCLOSURES ARE NOT | | ACCEPTABLE. WALLS SHALL BE IRRIGATED AND LANDSCAPED | | WITH SHRUBS AND HEDGES PLANTED AT TWO (2) FEET | | INTERVALS. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1444 OR (561) 805-6720 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2008-09-26 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2008-09-26 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2008-09-26 |
Time |
15:58 |
Sent To |
|
|
Notes |
2008-09-26 16:32:25 | ***ZONING FAILED*** | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED EQUIPMENT | | TO ALL PROPERTY LINES. PURSUANT TO THE CITY OF WEST | | PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS | | (ZLDR), SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY | | NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | 4. PURSUANT TO THE ZLDR SECTION 94-444(B): LANDSCAPE | | SCREENING SHALL BE PROVIDED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1444 OR (561) 805-6720 | | E-MAIL: [email protected] | | |
|
|