Plan Review Details - Permit 08090142
Plan Review Stops For Permit 08090142
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-12-12 Cont ID  
Sent By jnguyen Date 2008-12-12 Time 09:19 Rev Time 0.00
Received By jnguyen Date 2008-10-14 Time 08:00 Sent To  
Notes
2008-12-12 09:13:5510/14/2008 - JAMES & I ANALYZED THE SITE PLANS &
 AERIALS TO ASSIGN AN ADDRESS FOR THE PROPOSED TWO-STORY
 PHOTOGRAPHIC CENTER & MUSEUM (WHICH WILL BE A PART OF
 THE NEW CITY CENTER). WE DISCOVERED THAT LILI HAD
 ALREADY PREVIOUSLY ISSUED AN ADDRESS OF 415 CLEMATIS ST
 AT THIS LOCATION. THE ADDRESS POINT OF 415 CLEMATIS ST
 EXISTS IN GIS & IN THE NARRATIVE SECTION STATES IT IS
 FOR THE PURPOSE OF A PHOTOGRAPHIC CENTER & MUSEUM.
 ALSO, IN COMMUNITYPLUS UNDER PCN# 74434321010160010 FOR
 UNIT RECORD 0002 OF 415 CLEMATIS ST, THE USE CLASS
 SECTION DISPLAYS IT FOR THE PURPOSE OF A PHOTOGRAPHIC
 CENTER & MUSEUM TOO.
  
 12/12/2008 - I CALLED STONE AT (646) 573-3629 & TOLD
 HIM THAT THE ADDRESS WAS NOT A SUITE # BASED OFF OF THE
 MAIN ADDRESS (401 CLEMATIS ST), BUT THAT WE PREVIOUSLY
 GAVE IT ITS OWN UNIQUE ADDRESS OF 415 CLEMATIS ST FOR
 THIS PARTICULAR PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2009-08-24 Cont ID  
Sent By jwitmer Date 2009-08-24 Time 09:52 Rev Time 0.50
Received By jwitmer Date 2009-08-24 Time 09:32 Sent To  
Notes
2009-08-24 09:53:12REVISION:
 A-1.00 REVISION# 9

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2009-08-04 Time 13:00 Sent To PC
Notes
2009-08-04 13:37:13REVISIONS DATED 7-13-09
 SHEETS: A1.00, A1.01, A-1.02, A4.00 & A4.01

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 12:59 Rev Time 0.50
Received By jwitmer Date 2009-08-04 Time 12:30 Sent To  
Notes
2009-08-04 12:51:02ARCHITECTURAL REVISIONS DATED 7-13-09
 SHEETS A1.00, A1.02, A4.01, A1.01 & A4.00
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-31 Cont ID  
Sent By jwitmer Date 2009-07-31 Time 12:59 Rev Time 0.75
Received By jwitmer Date 2009-07-31 Time 12:15 Sent To PC
Notes
2009-07-31 12:53:24REVISION ADD OVERHEAD DOOR INTO STORAGE 1 HR RATED WALL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 14:49 Rev Time 0.88
Received By jwitmer Date 2009-07-08 Time 13:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By jwitmer Date 2009-04-08 Time 08:49 Rev Time 0.77
Received By jwitmer Date 2009-04-07 Time 08:49 Sent To  
Notes
2009-04-07 08:51:08BUILDING PLAN REVIEW
 PERMIT: 08090142
 ADD: 415 CLEMATIS ST.
 CONT:CATALFUMO CONSTRUCTION
 TEL: (561)282-8265 J J WOLFE JR
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
  
 APRIL 6/09
 COMMENT# 2. SPOKE WITH THE NEW BUILDING OFFICIAL DOUG
 WISE AND HE WILL WAVE THE REQUIREMENT OF THE BASE
 BUILDING DESSIGNER REVIEWING THE NEW BUILD OUT PLAN.
 COMMENT# 3. DOUG ALSO RECEIVED COPIES OF THE HUFCOR
 SHOP DRAWINGS WHICH I REVIEWED AND WILL STAMP UP TODAY.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-03-02 Cont ID  
Sent By jwitmer Date 2009-03-02 Time 09:23 Rev Time 0.77
Received By jwitmer Date 2009-03-02 Time 09:23 Sent To  
Notes
2009-03-02 09:31:45BUILDING PLAN REVIEW
 PERMIT: 08090142
 ADD: 415 CLEMATIS ST.
 CONT:CATALFUMO CONSTRUCTION
 TEL: (561)282-8265 J J WOLFE JR
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) 2ND REQUEST, IF PERMITED BEFORE THE BASE BUILDING
 HAS RECEIVED THEIR CERTIFICATE OF COMPLETION THE BASE
 BUILDING DESIGNER WILL NEED TO REVIEW THE SUBMITTED
 PLANS AND AFFIX THEIR SHOP DRAWING STAMP ON THE PLANS.
 THE PLANS SUBMITTED MAY EFFECT THEIR ENERGY CALCULATION
 ASSUMPTIONS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) BUILDING PROVISO: HUFCOR FOLDING PARTITION SYSTEM TO
 PROVIDE SHOP DRAWINGS TO BE REVIEWED BY THE DESSIGNER
 OF RECORD WITH THEIR SHOP DRAWING REVIEW STAMP AFFIXED.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 APRIL 6/09
 COMMENT# 2. SPOKE WITH THE NEW BUILDING OFFICIAL DOUG
 WISE AND HE WILL WAVE THE REQUIREMENT OF THE BASE
 BUILDING DESSIGNER REVIEWING THE NEW BUILD OUT PLAN.
 COMMENT# 3. DOUG ALSO RECEIVED COPIES OF THE HUFCOR
 SHOP DRAWINGS WHICH I REVIEWED AND WILL STAMP UP TODAY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-24 Cont ID  
Sent By jwitmer Date 2008-09-24 Time 14:23 Rev Time 6.22
Received By jwitmer Date 2008-09-24 Time 14:06 Sent To  
Notes
2008-09-24 14:53:42BUILDING PLAN REVIEW
 PERMIT: 08090142 (PLAN REVIEW)
 ADD: 401 CLEMATIS ST. SUITE # .
 CONT: (PLAN REVIEW) CONTACT: TED DAVIS
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.THE COVER SHEEET
 NEGLECTS THE 2007 SUPPLEMENTS TO THE 2004 FBC, PLEASE
 CORRECT. 106.1.2 ADDITIONAL INFORMATION REQUIRED,
 553.73FL S S .
  
 1D) THIS TENANT SPACE IS LEASEABLE SPACE AND WILL
 REQUIRE A SUITE ADDRESS, TO BE PROVIDED BY ADDRESS
 TECHNITION JAMES JUDGE, AND WILL NEED TO BE ON THE
 PERMIT APPLICATIONAS WELL AS PLANS.
  
 2) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING
 DESIGNER WILL NEED TO REVIEW THE SUBMITTED PLANS AND
 AFFIX THEIR SHOP DRAWING STAMP ON THE PLANS. THE PLANS
 SUBMITTED MAY EFFECT THEIR ENERGY CALCULATION
 ASSUMPTIONS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) IF PERMITED BEFORE THE BASE BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION THE BASE BUILDING
 CONTRACTOR SHALL PROVIDE A NOTIRIZED LETTER INDICATING
 ALLOWING THE CONTRACTOR OF THE TENANT SPACE TO START
 WORK BEFORE THE CERTIFICATE OF COMPLETION OF THE BASE
 BUILDING HAS BEEN ACHIEVED. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 4) SHEET A0.01 THE FIRST FLOOR INDICATES AN ASSEMBLY
 OCCUPANCY WITH A 15 SQ FT PERSON, UNCONCENTRATED,
 PLEASE PROVIDE A FLOOR PLAN WITH TABLE AND CHAIRS AS
 WELL AS FOR COMMON PATH OF TRAVEL. SHEET A1.00 ALSO IS
 MISSING A LAYOUT OF FURNATURE. TABLE 1004.1.2 & 1013.3.
  
 5) SHEET A1.00 PLEASE PROVIDE THE TENANT SEPERATION
 WALLS AND WALL RATINGS AS WELL AS THE COMMON AREAS,
 ALSO NOTE THE MECHANICAL MEZZANINE LEVEL WILL NEED TO
 SHOW WHERE THE TENANT SEPERATION WALL WILL BE LOCATED.
 SECTION 708.1. FIRE PARTITIONS, & TABLE 715.3. THIS
 SHEET DOES INDICATE THE WALL RATING OF THE TENANT WALL
 THAT DIVIDES THE PHOTO SHOP FROM THE MUSEUM BUT THE
 NORTH WALLS OF THE MUSEUM ARE NOT INDICATED ON THE
 PLANS.
  
 6) SHEET A0.01 IT APPEARS THAT THE CORRIDOR OR HALL
 (1.07) IS AN EXIT ACCESS CORRIDOR SINCE THERE ARE EXIT
 SIGNS LEADING IN THE DIRECTION OF A 2HR RATED EXIT
 PASSAGEWAY THAT LEADS FROM THE STAIRWELL. NOTE THE
 CORRIDOR THAT LEADS BACK INTO THE CITY HALL PORTION OF
 THIS BUILDING IS NOT REQUIRED TO BE RATED, FIRE OR
 SMOKE, PER TABLE 1016.1. FOR A BUSINESS OCCUPANCY. BUT
 THE ASSEMBLY OCCUPANCY THAT IS NOW BEING DIRECTEDED
 INTO THIS CORRIDOR WILL REQUIRE A 1 HR FIRE RATING PER
 TABLE 1016.1.
  
 7) SHEET A1.00 THE PHOTO SHOP ROOMS 1.12, 1.13 & 1.14
 ALL NEED TO MEET THE REQUIREMENTS OF 1014.2.1 EXCEPTION
 (2). THE DOORS ARE TO BE NOT LESS THAN 1/3RD OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED.
  
 8) SHEET A0.01, A1.00 OR A1.01 IDENTIFY THE DOOR
 OPENING NOR THE DOOR SIZE.106.1.2 / 715.3 & 1008.1.1.
  
 9) SHEET A1.01 INDICATES THE CORRIDOR WALLS OR TENANT
 SEPERATION WALLS AS 1 HR RATED PARTITIONS BY OTHERS,
 THE CITY HALL APPROVED SET OF PLANS SHEET A1-2.2 DATE
 STAMPED MAY 8, 2008 IS THE LATEST REVISION OF THIS AREA
 AND DOES NOT INDICATE THESE WALLS. PLEASE COORDINATE
 PLANS WITH THE BASE BUILDING DESIGNER AS TO WHO WILL
 TAKE RESPONSIBILITY FOR THE DESIGN OF THIS AREA.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
 708.1 FIRE PARTITIONS, TENANT SEPERATION WALLS.
  
 10) SHEET A1.01 THE EXISTING WALL LINE LOCATED ALONG
 SECTION LINE #5 ON THE BASE BUILDING SET OF PLANS WAS
 CONSIDERED NON-RATED, NON SEPERATED USE. NOW WITH A NEW
 TENANT THIS WALL WILL BECOME A TENANT SEPERATION WALL
 REQUIRING A 1 HOUR FIRE RATING, SEE SECTION 708.1.
  
 11) SHEET A1.01 NOTE ON THE LEFT SIDE OF PLANS IT
 APPEARS TO BE A DISCREPANCY WITH THE WALL LEGEND ON THE
 RIGHT SIDE OF PAGE. THIS NOTE IS DIRECTED TO 1 HR FIRE
 RATING ON ALL TENANT SEPERATION WALLS BUT IS DIRECTED
 TO A INTERIOR WALL LOCATED WITHIN THE TENANT SPACE.
 DISCREPANCY.
  
 12) SHEET A1.01 WITHIN THE PHOTORAPHY STUDIO THE PLANS
 INDICATE USE OF A SELF -SUPPORTING FOLDING PARTITION,
 NO STRUCTURAL MODIFICATIONS REQUIRED, PLEASE PROVIDE
 PRODUCT INFORMATION ON SUCH A SYSTEM,
 IS THIS SYSTEM SUPPORTED HOW? ADDITIONAL INFORMATION
 REQUIRED106.1.2 .
  
 13) SHEET A1.01 ROOM# 2.21 THE PHOTOGRAPHY STUDIO
 SQUARE FOOTAGE IS 1711 SQ FT. THIS AREA APPEARS TO BE
 AN ASSEMBLY OCCUPANCY WHEN THE FOLDING PARTITION IS NOT
 IN USE. CLASSROOMS WTIH 20SQ FT PER
 OCCUPANT PUTS A LOAD OF 86 OCCUPANTS, WHERE AS IF THE
 USEAGE OF THE ROOM IS MORE IN LINE WITH A VOCATIONAL
 SHOP THE SQUARE FOOTAGE USED PER OCCUPANT OF 50 WOULD
 CREATE AN OCCUPANT LOAD OF 35.
 TABLE 1016.1 WOULD REQUIRE UNDER AN ASSEMBLY OCCUPANCY
 WHEN THE OCCUPANT LOAD IS EQUAL TO OR GREATER THAN 50
 WOULD REQUIRE 1 HR RATED CORRIDORS.TABLE 1016.1 PLEASE
 PROVIDE A CODE ANYLISIS FOR THE SECOND FLOOR AS THE
 FIRST FLOOR.
  
 14) SHEET A1.01 ROOM 2.21 THE LOUNGE INDICATES WHAT
 APPEARS TO BE A KITCHEN TYPE SINK, THERE ARE NO
 ELEVATIONS OF THIS CABINETRY, PLEASE VARIFY COMPLIANCE
 WITH:
 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED WITH THE
 COUNTER OR RIM NO HIGHER THAN 34" ABOVE THE FINISH
 FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION
 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW
 FORWARD APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND
 SHALL EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH
 THE SINK.
  
 15) SHEET A4.00 DETAIL GYPSUM SOFFITS, THE PLANS DO NOT
 DECLAIR WHAT TYPE OF FASTENER, OR FREQUENCY OF ANCHOR
 THE VARIOUS WIDTH SOFFITS TO THE STRUCTURAL DECK ABOVE?
 106.1.2/ 2506.2 STANDARDS,
 TABLE 2506.2 & 1604.3.6 DEFLECTION LIMITATIONS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-09-24 Cont ID  
Sent By dpalmer Date 2009-09-24 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2009-09-24 Time 10:03 Sent To PC
Notes
2009-09-24 10:04:21LOBBY LIGHTING ONLY.
 REDLINE D13-415.1.ABC.1.1,.1.2 AND .1.3

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2009-08-05 Time 18:58 Sent To FIRE
Notes
2009-08-05 18:59:46REV E- 1.01, 1.02, 3.02 STAMPED BY ELEC.
 SHEET E1.03 NEEDS FIRE REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-07-09 Cont ID  
Sent By dpalmer Date 2009-07-09 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2009-07-09 Time 13:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By dpalmer Date 2009-04-08 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2009-04-08 Time 12:36 Sent To  
Notes
2009-04-08 12:36:23** PROVISO**
 BEFORE ROUGH ELECTRICAL INSPECTIONS.
  
 1) NOTE: ALL ELECTRICAL IN ROOMS, 1.00, 101 AND 1.02 TO
 BE COMPLETED AND REVISED TO CIRCUIT AND SHOW ALL
 ELECTRICAL FROM TENANT SPACE ELECTRICAL SERVICE.
 THIS WAS CONFIRMED WITH ELECTRICAL ENGINEER AS WELL AS
 GC AND EC.
 310.16, 240.4, 408.4 ETC
  
 **REDLINED
 LOW VOLTAGE FOR FIRE ALARM, DATA SYSTEMS EACH UNDER
 SEPARATE PERMITS.
 SERVICE ENTRANCE CONDUCTORS ENCASED IN CONCRETE PER
 230.6.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-02-25 Cont ID  
Sent By dpalmer Date 2009-02-25 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2009-02-25 Time 09:38 Sent To  
Notes
2009-02-25 09:40:55** NOTE: ONE SET OF ELECTRICAL PLANS HAVE BEEN REMOVED
 FROM SETS AND WILL BE RETAINED BY THIS OFFICE.
2009-02-25 09:38:19** DENIED 2ND REVIEW **
  
 1ST REVIEW UNDER PERMIT APPLICATION.
 2ND REVIEW.
  
  
  
 1) NOTE: PLEASE BE SURE TO ADJUST CODES AND DESIGNS FOR
 THE FOLLOWING. THE PERMIT APPLICATION HAS ONLY NOW BEEN
 MADE. PER FAC 69A-60.004 AND .003 NFPA-1 AND NFPA-101
 HAS BEEN REVISED TO THE 2006 EDITIONS OF EACH.
 THIS IS A SEPARATE ADOPTED RULING FROM THE STATE AND IS
 NOT BASED ON THE NEW CODE ADOPTIONS OF MARCH 1ST 2009.
 PLEASE REVISE ANY NEEDED DESIGNS AND REVISED CODE
 REFERENCES ON PLANS.
  
 2) NOTE: AS STATED ON PREVIOUS REVIEWS. THE BASE
 BUILDING DOES NOT CONTAIN A CERTIFICATE OF OCCUPANCY.
 ALL PLANS SHALL GO BACK TO THE BASE BUILDING DESIGNERS
 OF RECORD FOR *SHOP DRAWING REVIEW STAMP* AND SIGNATURE
 FROM EACH INDIVIDUAL DESIGNER OF RECORD.
 THIS BUILDING IS UNDER THE RESPONSIBILITY OF EACH OF
 THOSE DESIGNERS UNTIL SUCH TIME THE BUILDING IS
 COMPLETE BASED ON PERMITTED SCOPE OF WORK ON PLANS FOR
 C OF O, C OF C, ETC.
 FS 471,481
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS. NO NEW
 SERVICE WITH SEPARATE METER WILL BE GRANTED. IN SEVERAL
 MEETINGS HELD BEFORE PLANS WERE RESUBMITTED THE REQUEST
 WAS MADE FOR THE SEPARATE MAIN IN ORDER FOR ALL
 ELECTRICAL IN THE TENANT SPACE TO BE FED SEPARATELY SO
 THAT THE TENANT COULD BE METERED SEPARATELY FROM FPL
 AND PAY THEIR OWN ELECTRIC BILL.
 IN THE MEETINGS HELD IT WAS AGREED TO REMOVE COMMON
 AREAS WHICH WERE BEING FED FROM TENANT MAIN AND TO HAVE
 ACTUAL TENANT SEPARATION.
 THIS WAS ALSO BASED ON THE EGRESS LIGHTING IN TENANT
 SPACE BEING FED FROM BATTERY BACK UP FIXTURES IN ORDER
 TO EXIT OCCUPANTS FROM THE BUILDING IN THE EVENT OF
 POWER FAILURE/EMERGENCY.
 THE PLANS HAVE NOW BEEN COMPLETELY REVISED TO SHOW A
 SUBSTANTIAL AMOUNT OF *GENERAL LIGHTING* WHICH HAPPENS
 TO BE BATTERY BACK UP FIXTURES ALSO BEING FED FROM THE
 CITY'S ELECTRICAL SERVICE MAIN WHICH IS PART OF THE
 CITY'S METERING AND BILLING. THIS IS NOT WHAT WAS GONE
 OVER IN THE MEETINGS AND MANY DISCUSSIONS. THIS IS
 COMPLETELY OPPOSITE FROM THE REASON A SEPARATE
 SERVICE/MAIN WAS REQUESTED IN ORDER TO METER SEPARATELY
 FOR TENANT. ESSENTIALLY BASED ON THE ELECTRICAL SHOWN
 MUCH OF THE ELECTRICAL LIGHTING IS FED FROM THE CITY'S
 ELECTRICAL SERVICE WHICH WOULD NOW AFFECT THE 700 AND
 701 SYSTEMS FOR SELECTIVE COORDINATION.
 THE TENANT BATH ROOMS AND OTHER AREAS ARE ALSO STILL
 BEING SHOWN BEING FED FROM THE BASE BUILDING'S
 ELECTRICAL SYSTEM. THIS BATHROOM IS LOCATED IN THE
 TENANT SPACE ALONG WITH SHIPPING AND RECEIVING. THIS
 WOULD ELECTRICAL SYSTEMS CROSSED INTO THE TENANT SPACE.
 THIS WILL ALSO NOT BE PERMITTED.
 THE TENANT MAY GO BACK TO THE BASE BUILDING ELECTRICAL
 SERVICE AS THERE IS SPACE, LOAD AND DESIGN FOR THE
 TENANT.
 230.2, 700.27, 700.18, 700.12F, 240.12 ETC.
  
 4) NOTE: AS NOTED ON PREVIOUS REVIEW. PLEASE SUBMIT
 COMPLETE LIGHTING PERFORMANCE CALCULATIONS BASED ON
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE SECTION AS NOTED FOR TRACK LIGHTING. THE
 WATTAGE MUST BE BASED ON THE RATING OF THE FIXTURE
 TIMES THE NUMBER OF FIXTURES, OR 30WATTS PER FOOT WHICH
 EVER IS GREATER.
  
 AN EXAMPLE: THE WATTAGE PER SQ FT SHOWN FOR MUSEUM AREA
 IS 1.7. THE CODE IN TABLE *B* ALLOWS 1.0 AND THEN ONLY
 THE ADDITIONAL FOR THE ACTUAL DISPLAY OR ACCENT
 LIGHTING IS EXEMPT. THIS IS NOT AN AREA FOR RESTORATION
 WORK WHICH IS WHAT SEEMS TO BE THE ALLOWANCE SHOWN.
  
 THE WATTAGE MUST BE BASED ON FIXTURE/BALLAST VA. SEE
 FIXTURES A AND B FOR EXAMPLE. IN THE CALCULATIONS THE
 COMPLETE FIXTURE WATTAGE IS SHOWN AT 30WATTS. HOW IS
 THIS POSSIBLE WHEN EACH OF THESE FIXTURES CONTAIN
 2-32WATT BULBS BASED ON THE FIXTURE LEGEND? EVEN WITH
 SOME OF THE MOST EFFICIENT BALLAST AVAILABLE ON THE
 MARKETS, THE WATTAGE WOULD NOT BE CUT INTO LESS THAN
 HALF. BASE ON THE CALCULATIONS AND DERIVED WATTAGE
 THERE SEEMS TO BE SOME SORT OF MISPRINT OF ACTUAL
 FIXTURE WATTAGE.
  
 ANOTHER EXAMPLE WOULD BE SPACE 1.14 WHICH SHOWS A
 FIXTURE WATTAGE FIGURED INTO THE CALCULATIONS OF 30
 WATTS HOWEVER BASED ON THE MAXIMUM WATTAGE PER FIXTURE
 AS STATED ON THE FIXTURE LEGEND THE FIXTURES WOULD BE A
 MAXIMUM OF 37WATTS. THIS WOULD BE THE WATTAGE NEEDED TO
 BE FIGURED INTO THE CALCULATIONS. THIS IS ONLY THE
 WATTAGE *IF* THE TOTAL WATTAGE OF FIXTURES TIMES THE
 NUMBER OF FIXTURES IS LOWER THAN THE 30VA PER FT OF
 TRACK ON PLANS. (AS NOTED ABOVE).
  
 THERE ARE OTHER AREAS AND ROOMS SUCH AS COMPUTER LAB
 WHICH SHOWS A *0* WATTAGE IN DESIGN. THESE CALCULATIONS
 MUST BE BASED ON SPACE BY SPACE. HOW CAN THESE VALUES
 BE *0*?
 PLEASE SEE CODE SECTIONS AS NOTED ABOVE.
 THESE ARE ONLY SOME EXAMPLES AS IS NOT A LIST OF EACH
 ITEM NOT SHOWN FOR CODE COMPLIANCE AND COORDINATION.
 FBC 106.1.1,106.1.2, CLARITY AND COORDINATION.
  
 5) NOTE: THERE SHALL BE NO STORAGE IN ELECTRICAL ROOMS
 WHICH CONTAIN ELECTRICAL PANELS, TRANSFORMERS AND OVER
 CURRENT PROTECTION. PLANS INDICATE COMPUTER STORAGE
 WHICH IS NOT PERMITTED IN ROOM 2.13.
 408.17, 240.24, 110.26.
 SHALL ALSO CONTAIN SIGNAGE: ELECTRICAL ROOM, NO STORAGE
 PER FIRE MARSHAL OR WORDS TO THAT AFFECT.
  
 6) NOTE: PLEASE SEE NEW WATER HEATER SHOWN UNDER
 COUNTER DOES NOT CONTAIN ANY CIRCUITING OR DISCONNECT.
 PLEASE COMPLETE SO THAT LOADS, CIRCUITING ETC MAY BE
 REVIEWED.
 4220.30,4220.31,408.4, 310.16
 FBC 106.1, 106.1.2 FOR CLARITY, ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SEE SHEET E1.03 WHICH REFERENCES THE
 2007 FBC FOR ADA COMPLIANCE. THIS PROJECT HAS BEEN
 APPLIED FOR PERMIT UNDER THE 2004 FBC W/2007 REVISION.
 PLEASE REVISE.
  
 *** IT IS IMPORTANT TO KNOW AS THERE WILL BE
 SUBSTANTIAL CHANGES TO PLANS THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW WHICH CAN NOT BE MADE AT
 THIS TIME.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 09:47 Rev Time 1.50
Received By dpalmer Date 2008-09-30 Time 09:47 Sent To  
Notes
2008-09-30 09:48:20 
 ** DENIED REVIEW **
  
 1) NOTE: PLANS HAVE BEEN SUBMITTED FOR PLAN REVIEW ONLY
 AND NOT FOR PERMITTING. PLEASE KNOW EVEN ONCE PLANS ARE
 FOUND TO BE CODE COMPLIANT FOR ISSUANCE IF PERMIT
 APPLICATION HAS NOT BEEN MADE PLANS WILL REMAIN IN A
 FAILED STATUS.
  
 2) NOTE: THE BASE BUILDING DOES NOT CONTAIN A
 CERTIFICATE OF OCCUPANCY AT THIS TIME. THE BASE
 BUILDING IS STILL UNDER THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAMS FOR ALL TRADES. IF THIS SCOPE OF
 WORK IS PERMITTED BEFORE THE CO OF THE BASE BUILDING,
 ALL PLANS AND DOCUMENTS ARE REQUIRED TO BE REVIEWED AND
 *SHOP DRAWING* REVIEW STAMPED AND SIGNED BY EACH
 DESIGNER OF RECORD FOR THE BASE BUILDING.
  
 3) NOTE: PLEASE SEE THE NEW PROPOSED SERVICE SHOWN ON
 PLANS IS NOT GRANTED PER 230.2. THE BASE BUILDING HAS
 ALLOWANCE IN EXISTING EQUIPMENT FOR THIS SPACE FOR
 FUTURE TENANT. A NEW SERVICE AS SHOWN DOES NOT MEET ANY
 ALLOWANCES TO GRANT AN ADDITIONAL SERVICE TO THIS
 SPACE. THIS HAS BEEN CONFIRMED WITH THE CHIEF
 ELECTRICAL INSPECTOR
 AS SHOWN THIS TENANT SPACE WOULD ALSO HAVE ELECTRICAL
 LIGHTING BEING FED FROM BASE BUILDING ELECTRICAL
 SYSTEMS FOR EMERGENCY LIGHTING ETC FROM ANOTHER
 SERVICE.
  
 4) NOTE: LOCATION OF ALL PROPOSED ELECTRICAL EQUIPMENT
 IS NOT CLEAR AT THIS TIME. PLANS SEEM TO INDICATE SOME
 ELECTRICAL EQUIPMENT IN THE BASE BUILDING AND NOT IN
 THE TENANT SPACE OR ELECTRICAL ROOM. THE EQUIPMENT ON
 MEZZANINE LEVEL IS IN THE CITY SPACE/EQUIPMENT ROOM
 WHICH WILL NOT BE PERMITTED. COMMON AREA CORRIDORS,
 ACCESS ETC ALL NEEDS TO BE CONFIRMED.
 110.26, 240.24
 FBC 106.1.1, FOR CLARITY AND ADDITIONAL INFORMATION
 NEEDED.
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR TENANT
 SPACE. LOADS AT THIS TIME ARE ALL SHOWN AT CONNECTED
 LOADS. HOW IS TRACK LIGHTING LOADS FIGURED? HOW ARE
 CONTINUOUS LOADS FIGURED? ARE ALL THESE ALREADY FIGURED
 INTO LOADS AS SHOWN?
 IF THIS IS THE CASE PLEASE SHOW AND INDICATE.
 PLEASE SHOW LOADS ON THE EXISTING SERVICE WHICH THIS
 TENANT SPACE WILL BE FED FROM.
 NEC 220.87, 220.43B, 220.43A, 215.3, 230.42 ETC
 FBC 106.1.1, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 6) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS. AS NO LPC
 WERE SUBMITTED A REVIEW FOR THESE SECTIONS OF THE
 FLORIDA BUILDING CODE COULD NOT BE DONE. PLEASE BE SURE
 TO SEE THE SECTIONS NOTED ABOVE SPECIFIC TO TRACK
 LIGHTING.
 PLEASE BE SURE TO COMPLETE THE FIXTURE LEGEND WITH
 SPECIFIC FIXTURES. AN EXAMPLE OF THE FIXTURES NOT
 SHOWING INFORMATION WOULD BE THE XENON STRIP LIGHTING.
  
 7) NOTE: PLEASE ADJUST CODES NOTED. SHOULD READ THE
 2004 FBC W/2007 REVISIONS.
  
 8) NOTE: PLEASE BE SURE TO SHOW CONNECTIONS OF ANY
 TRANSFORMERS PER 250.53,250.58,250.66. THERE IS A
 GROUNDING ELECTRODE RISER IN THE EXISTING BUILDING
 WHICH REQUIRES ANY TRANSFORMER TO BE CONNECTED TO. AS
 THE LOCATIONS PROPOSED FOR ELECTRICAL EQUIPMENT IS NOT
 GRANTED OR KNOWN TO BE FINAL AT THIS TIME, THE LOCATION
 OF EQUIPMENT IN THE PROXIMITY OF THE EXISTING RISER MAY
 HELP.
  
 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3. PLEASE
 INDICATE HEIGHTS, LOCATIONS, AND LEVELS FOR ALL DEVICES
 FOR ADA COMPLIANCE.
  
 10) NOTE: AS A NOTE: THE NEW SERVICE AS SHOWN IS NOT
 GRANTED, HOWEVER 230.6 DOES NOT PERMIT A FOUR HR
 ENCLOSURE. THE CODE WOULD REQUIRE ENCASEMENT OF
 CONCRETE OF A MINIMUM OF 2 INCHES. 230.70
  
 11) NOTE: PLANS ARE SHOWING COMMON AREA SPACES BEING
 FED FROM THIS TENANT SPACE EQUIPMENT. AN EXAMPLE OF
 THIS WOULD BE THE OUTSIDE THE BATHROOMS. SEPARATION OF
 TENANT SPACES DEFINED AREAS ETC WILL ALL NEED TO BE
 SPECIFIC.
 AS THERE ARE MANY UNANSWERED QUESTIONS ON SEPARATION AT
 THIS TIME AND SOME INFORMATION NOT YET SUBMITTED, THERE
 MAY VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 12) NOTE: PROJECT WILL REQUIRE ADDRESSING FOR NEW
 SPACE. PLEASE CONTACT JAMES JUDGE FOR
 ADDRESSING.(561-822-1226) THE PLANS NEED TO SHOW THE
 MAIN ADDRESS OF 401 CLEMATIS ON ALL TITLE BLOCKS
 INCLUSIVE OF ALL TRADES. THE SUITE/UNIT NUMBER WILL BE
 SEPARATELY ASSIGNED.
 FAC 61G1-16.004, 61G15-23.002
 FBC 106.5
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-08-06 Cont ID  
Sent By mawillia Date 2009-08-06 Time 14:54 Rev Time 0.00
Received By mawillia Date 2009-08-06 Time 14:08 Sent To  
Notes
2009-08-06 14:09:54*****REVISION #6, DATED 7/21/09, APPROVED*****
  
 REVISED PLAN SHEETS E1.01 AND E1.03 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2009-08-04 Cont ID  
Sent By mawillia Date 2009-08-04 Time 13:18 Rev Time 0.00
Received By mawillia Date 2009-08-04 Time 12:54 Sent To B1
Notes
2009-08-04 13:18:35*****REVISION, DATED 7/09/2009, APPROVED*****
  
 REVISED PLAN SHEETS A1.01 & A1.02 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-07-16 Cont ID  
Sent By mawillia Date 2009-07-16 Time 16:08 Rev Time 0.00
Received By mawillia Date 2009-07-16 Time 15:24 Sent To  
Notes
2009-07-16 15:38:59*****REVISIONS, DATED 6/05/2009, APPROVED*****
  
  
 REVISED PLAN SHEETS A0.01, A1.02, FS2.2, E2.01A, AND
 E2.01B WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-04-08 Cont ID  
Sent By mawillia Date 2009-04-08 Time 13:21 Rev Time 0.00
Received By mawillia Date 2009-04-08 Time 12:54 Sent To  
Notes
2009-04-08 13:21:39*****APPROVED*****
  
  
 PLAN SHEETS A0.01, A0.02, A1.02, A1.03, FS0.1, FS2.1,
 FS2.2, E1.01, E1.03, E2.01A & E2.01B, AND E2.03 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-03-30 Cont ID  
Sent By mawillia Date 2009-03-30 Time 13:07 Rev Time 0.00
Received By mawillia Date 2009-03-30 Time 12:09 Sent To  
Notes
2009-03-30 13:03:44*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE-STAMPED WHEN THE OTHER PLAN EXAMINERS' COMMENTS
 HAVE BEEN SATISFIED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-09 Cont ID  
Sent By mcarsill Date 2008-10-09 Time 10:49 Rev Time 0.00
Received By mcarsill Date 2008-10-09 Time 10:41 Sent To  
Notes
2008-10-09 10:48:401. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. TRASH AND DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. SOME EXIT SIGNS APPEAR TO BE MISSING FROM WITHIN
 STAIR # 10 ALONG THE PATH OF THE EXIT ARROW.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL.
  
 6. PLEASE DISPLAY ALL RATED FIRE WALLS IN AND AROUND
 THE PROPOSED PHOTOGRAPHIC CENTRE.
  
 7. PLEASE CLEARLY DELINEATE ALL EMERGENCY LIGHTING
 EQUIPMENT CONTAINED WITHIN THE PROPOSED SPACE.
  
 8. NO DOOR SCHEDULE PROVIDED. A DOOR SCHEDULE SHALL
 INDICATE RATING, SIZE AND APPROPRIATE HARDWARE BEING
 PROPOSED FOR THE SPACE.
  
 9. ON PAGE A).00 PLANS INDICATE THAT INTERIOR FINISHES
 SHALL COMPLY WITH FBC 803. PLEASE INDICATE SPECIFIC
 RATINGS FOR WALLS AND CEILINGS ON THE PLANS.
  
 10. EXITS NOT PROPERLY SEPARATED IN EXHIBITION SPACE
 1.12,1.13,OR 1.14 AREA.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2009-10-27 Cont ID  
Sent By shill Date 2009-10-27 Time 10:01 Rev Time 0.00
Received By shill Date 2009-10-27 Time 10:01 Sent To  
Notes
2009-10-27 10:01:35REVISION TO DP DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 15:58 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 15:58 Sent To  
Notes
2009-09-15 15:59:37SENT TO DVPALMER.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2009-08-13 Cont ID  
Sent By jgomez Date 2009-08-13 Time 11:05 Rev Time 0.00
Received By jgomez Date 2009-08-13 Time 11:05 Sent To  
Notes
2009-08-13 11:05:44SENT TO J. WITMER'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2009-07-30 Cont ID  
Sent By jwitmer Date 2009-07-30 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2009-07-30 Time 08:10 Sent To  
Notes
2009-07-30 08:11:177-29 I TO J. WITMER

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 09:37 Rev Time 0.00
Received By shill Date 2009-07-15 Time 09:37 Sent To  
Notes
2009-07-15 09:37:16C7
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-07-10 Cont ID  
Sent By shill Date 2009-07-10 Time 16:28 Rev Time 0.00
Received By shill Date 2009-07-10 Time 16:28 Sent To  
Notes
2009-07-10 16:29:10TO MECHANICAL
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 13:49 Rev Time 0.00
Received By lmartine Date 2009-06-12 Time 13:49 Sent To  
Notes
2009-06-16 13:50:15C-11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-04-07 Cont ID  
Sent By adarroug Date 2009-04-07 Time 13:19 Rev Time 0.00
Received By adarroug Date 2009-04-07 Time 13:19 Sent To  
Notes
2009-04-07 13:38:00TO "C23"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 15:48 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 15:48 Sent To  
Notes
2009-02-09 15:48:24TO "COMM" BD#53--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-01-23 Cont ID  
Sent By btrobaug Date 2008-12-12 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2008-09-05 Time 15:29 Sent To PC
Notes
2008-09-05 15:29:42TO "COMM" BD#17

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-07-24 Cont ID  
Sent By rregueir Date 2009-07-24 Time 15:48 Rev Time 0.00
Received By rregueir Date 2009-07-24 Time 15:47 Sent To PC
Notes
2009-07-24 15:48:05REVISED M2.1 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 10:26 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 09:36 Sent To PC
Notes
2009-07-20 10:26:54REVISED M2.2 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-10 Cont ID  
Sent By rregueir Date 2009-07-10 Time 15:57 Rev Time 0.00
Received By rregueir Date 2009-07-10 Time 15:56 Sent To PC
Notes
2009-07-10 15:57:05SK-1: 8 1/2X11 REVISION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-03-30 Cont ID  
Sent By rregueir Date 2009-03-30 Time 11:07 Rev Time 0.00
Received By rregueir Date 2009-03-30 Time 10:21 Sent To  
Notes
2009-03-30 11:09:36ALL PREVIOUS REVIEW COMMENTS ADDRESSED. PLANS WILL BE
 STAMPED UPON RESUBMISSION AND PASSED REVIEW BY OTHER
 TRADES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-16 Cont ID  
Sent By rregueir Date 2008-09-16 Time 11:28 Rev Time 0.00
Received By rregueir Date 2008-09-15 Time 08:33 Sent To  
Notes
2008-09-16 11:28:30REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THIS PLAN IS BEING SUBMITTED FOR PLAN REVIEW ONLY AT
 THIS TIME. IF A PERMIT APPLICATION IS SUBMITTED PRIOR
 TO COMPLETION OF THE BASE BUILDING, THESE TENANT PLANS
 WILL NEED TO BE REVIEWED BY THE BASE BUILDING DESIGN
 TEAM FOR APPROVAL PRIOR TO SUBMISSION.
  
 1. PAGE M2.1: THE GROUP BATHROOMS ON THIS PAGE APPEAR
 AS THOUGH THEY ARE INTENDED TO BE A PART OF THIS TENANT
 SPACE RATHER THAN A PART OF THE BASE BUILDING. THIS AND
 OTHER AREAS DO NOT SHOW ANY PROVISIONS FOR TENANT
 SEPARATION. ALSO, THE EXISTING DUCTWORK SHOWN IN THIS
 AREA DOES NOT MATCH THAT SHOWN ON THE CURRENT PERMIT
 BASE BUILDING PLANS. PLEASE COORDINATE WITH THE BASE
 BUILDING DESIGN TEAM AND CONTRACTOR TO CLEARLY SHOW
 AREAS OF TENANT SEPARATION AND PROTECTION OF
 PENETRATIONS IN ACCORDANCE WITH FBCM 607.5 AND FBCM
 607.8.
  
 2. PAGE M4.1: THERE IS A NOTE INDICATING OUTSIDE AIR
 AND EXHAUST AIR ARE EXISTING AND NO CHANGES ARE NEEDED.
 HOWEVER, THE OCCUPANCY CLASSIFICATION AND OCCUPANT
 LOADS FOR VENTILATION PURPOSES WERE NOT KNOWN UNTIL
 THIS PHASE OF THE DESIGN. THEREFORE, PLEASE PROVIDE
 VENTILATION CALCULATIONS WHICH INCLUDE OCCUPANCY
 CLASSIFICATION, OCCUPANT LOADS, REQUIRED OUTSIDE AIR
 AND THE OUTSIDE AIR PROVIDED IN ACCORDANCE WITH FBCM
 TABLE 403.3.
  
 3. PAGE M5.1: DETAIL 1 IS FOR FIRE DAMPER INSTALLATION.
 THIS DETAIL IS NOT LIKELY TO CORRESPOND WITH THE FIRE
 DAMPER MANUFACTURER?S INSTALLATION INSTRUCTIONS. FIRE
 DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING PER FBCM 607.2.
 PLEASE COORDINATE THIS DETAIL WITH THE MANUFACTURER?S
 INSTRUCTIONS OR AT A MINIMUM, PROVIDE A NOTE WHICH
 DEFERS TO THE MANUFACTURER?S INSTRUCTIONS TO
 DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 08:29 Rev Time 0.00
Received By kstevens Date 2009-07-02 Time 16:56 Sent To  
Notes
2009-07-06 08:30:16REVISION OK -- SHT P2.1 -- SEE PROVISO PREVIOUS SHT
 P2.1.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-04-10 Cont ID  
Sent By kstevens Date 2009-04-10 Time 14:16 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 14:16 Sent To  
Notes
2009-04-10 14:36:53 
  
 PASSED/PROVISO
  
 1) SPOKE WITH THE BUILDING OFFICIAL DOUG WISE AND HE
 INDICATED THAT HE WILL WAIVE THE REQUIREMENT FOR THE
 SHELL DESIGNERS OF RECORD TO REVIEW THE TENANT BUILDOUT
 PRIOR TO C/O OF SHELL BUILDING.
  
 2) REVISIONS ARE REQUIRED FOR SHEETS A1.00 & A1.01
 SHOWING TABLES AND CHAIRS ON THE FLOOR PLAN FOR THE
 FIRST FLOOR AND TO SHOW CHANGES TO SHEET A1.01 FROM
 ASSEMBLY STANDING TO ASSEMBLY TABLES AND CHAIRS. ALSO
 CHANGE SF/PERSON FROM 5 TO 15.
  
 3) REVISIONS TO BE SUBMITTED AS SOON AS POSSIBLE. C/O
 OF TENANT SPACE WILL NOT BE ISSUED PRIOR TO REVISION
 APPROVAL.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-03-11 Cont ID  
Sent By kstevens Date 2009-03-11 Time 14:03 Rev Time 0.00
Received By kstevens Date 2009-03-11 Time 14:03 Sent To  
Notes
2009-03-11 15:32:30PLAN REVIEW DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. SINCE THE SHELL BUILDING HAS NOT BEEN COMPLETED, AND
 NO CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED, BUT DESIGN
 TEAM OF THE SHELL BUILDING SHALL REVIEW THE PLANS FOR
 THE BUILD-OUT AND IF APPROVED, SHALL THEN STAMP THE
 PLANS AS REVIEWED AND ACCEPTED WITH A SHOP DRAWING
 STAMP OF APPROVAL.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
 SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLAN. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****NO WRITTEN RESPONSE, COMMENT NOT ADDRESSED. PLEASE
 SHOW COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.6. EXPOSED PIPES & SURFACES
 C. 11-4.24.7 FAUCETS
 SUCH INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL
 CODES SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A
 SUBSTITUTE FOR SPECIFIC INFORMATION.
  
 7. OK
  
 **********NEW COMMENT**********
  
 1B. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.2 & 403.1. FIRST FLOOR AS SHOWN THE A-3
 OCCUPANCY REQUIRES 4 WATER CLOSETS FOR THE MEN AND 7
 WATER CLOSETS FOR THE WOMEN. 3 WATER CLOSETS ARE
 PROVIDED FOR EACH. THE ASSEMBLY ALSO REQUIRES 5 LAVS.
 ONLY 4 LAVS PROVIDED. THE MERCANTILE REQUIRES 1 WATER
 CLOSET AND 1 LAV. -- THE SECOND FLOOR UNDER THE
 ALTERNATE OCCUPANCY CALCULATION FOR SPACE B, (86),
 ADDED TO SPACE A, (31), IS INDICATED AS 117 PERSONS.
 PER TABLE 403.1 (1 PER 25 FOR THE FIRST 50 AND 1 FOR
 EVERY 50 AFTER THAT REQUIRES 4 W/C'S - 6 PROVIDED, 1
 PER 40 FOR THE FIRST 50 AND ONE FOR 80 AFTER THAT
 REQUIRES 3 LAVS - 4 PROVIDED). THE DRINKING FOUNTAINS
 (2) ARE SUFFICIENT IF PIPED SEPARATELY TO THE SANITARY
 AND WATER SUPPLY. PLEASE SHOW COMPLIANCE WITH TABLE
 403.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO TRANSMITTAL LETTER SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By kstevens Date 2008-09-10 Time 11:00 Rev Time 0.00
Received By kstevens Date 2008-09-09 Time 12:57 Sent To  
Notes
2008-09-10 11:30:29PLAN REVIEW DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SINCE THE SHELL BUILDING HAS NOT BEEN COMPLETED, AND
 NO CERTIFICATE OF OCCUPANCY HAS BEEN ISSUED, BUT DESIGN
 TEAM OF THE SHELL BUILDING SHALL REVIEW THE PLANS FOR
 THE BUILD-OUT AND IF APPROVED, SHALL THEN STAMP THE
 PLANS AS REVIEWED AND ACCEPTED WITH A SHOP DRAWING
 STAMP OF APPROVAL.
  
 2. THE ADDRESS AND SPACE NUMBER SHALL BE INDICATED IN
 THE TITLE BLOCK OF EACH SHEET. SECTION 106.1.1.
  
 3. SHT A0.00 CODES & STANDARDS SHALL READ 2004 BUILDING
 CODE WITH 2005, 2006 & 2007 REVISIONS. SECTION 106.1.2.
  
 4. SHT A0.01 OCCUPANCY & EGRESS ANALYSIS INDICATES
 ASSEMBLY OCCUPANCY - UNCONSENTRATED NET SF 15. PER
 TABLE 1004.1.2 IT CALLS FOR TABLES & CHAIRS. PLEASE
 SHOW THE TABLES & CHAIRS ON THE FLOOR PLAN FOR THE
 ASSEMBLY OCCUPANCY.
  
 5. SHT A0.02 LOUNGE ROOM 2.24 DOES NOT REFLECT
 INFORMATION SHOWN ON SHT P2.1. A SINK IS SHOWN ON THE
 PLUMBING SHEET BUT NOT ON THE ARCHITECTURAL SHEET.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 6. SUBMIT A DETAIL FOR THE LOUNGE SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
 SHOW THE CLEAR FLOOR SPACE ON THE FLOOR PLAN. CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
  
 7. SHT P2.1 A WATER HAMMER ARRESTOR IS REQUIRED ON THE
 WATER SUPPLY LINE TO THE REF. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-02-19 Cont ID  
Sent By mflis Date 2009-02-19 Time 09:19 Rev Time 0.00
Received By mflis Date 2009-02-19 Time 09:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-15 Cont ID  
Sent By mflis Date 2008-09-15 Time 09:31 Rev Time 0.00
Received By mflis Date 2008-09-15 Time 09:31 Sent To  
Notes
2008-09-15 09:34:51ZONING REVIEW: FAILED
  
 1) CONFIRM ACCESS FROM DOOR OPENING ONTO CLEMATIS IS OK
 WITH PROPOSED GRADE AT SIDEWALK. THIS HAS BEEN AN ISSUE
 WITH OTHER DOORS ON STREET.
  
 2) ALONG INTERIOR OF WALL ALONG CLEMATIS STREET, THE
 FIRST FLOOR PLAN SEEMS TO INDICATE SOME FEATURES JUST
 NORTH OF WALL ASSEMBLY. THESE DO NOT SHOW UP IN ANY
 SECTIONS OR OTHER DETAILS. IS THIS SOMETHING IN THE
 FLOOR TREATMENT? PLEASE CONFIRM WHAT THE DRAWING IS
 SHOWING.
  
 MATT FLIS - 822-1445