Plan Review Details - Permit 08090106
Plan Review Stops For Permit 08090106
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-03-13 Cont ID  
Sent By jwitmer Date 2009-03-13 Time 15:08 Rev Time 0.22
Received By jwitmer Date 2009-03-13 Time 15:08 Sent To PC
Notes
2009-03-13 15:09:31LETTER OF CLARIFICATION DATED 2-23-09

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-01-21 Cont ID  
Sent By jwitmer Date 2009-01-21 Time 10:54 Rev Time 0.55
Received By jwitmer Date 2009-01-21 Time 10:54 Sent To  
Notes
2009-01-21 10:54:56REVISION# 2 DATED 12/24/08 SHEET A3.1- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-24 Cont ID  
Sent By jwitmer Date 2008-10-24 Time 14:23 Rev Time 0.77
Received By jwitmer Date 2008-10-24 Time 14:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-12 Cont ID  
Sent By jwitmer Date 2008-09-12 Time 11:12 Rev Time 1.66
Received By jwitmer Date 2008-09-12 Time 11:12 Sent To  
Notes
2008-09-12 12:03:26BUILDING PLAN REVIEW
 PERMIT: 08090106
 ADD: 2090 PALM BEACH LAKES #1000
 CONT: S .O. ENTERPRISES
 TEL: (561)827-6508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPT.12,2008
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) I INFORMATIONAL FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 2) NOTE LS.1 EXTRIOR VERTICAL EXITS INDICATE A 1 HR
 EXIT ENCLOSURE PLEASE SEE 1019.1 EXIT ENCLOSURES OVER 4
 STORIES ARE TO BE 2HR RATED. THIS PERMIT IS FOR A
 INTERIOR FIT UP AND THE EXTERIOR STIARWAYS ARE NOT
 EFFECTED, EITHER CORRECT THE NOTE OR REMOVE IT FROM THE
 PLANS.
  
 3) SHEET A3.1 DETAILS A & B INDICATE WOOD SUB-BUCKS,
 PLEASE ALLOWABLE COMBUSTABLES IN TYPE I TYPE II
 BUILDINGS. 603.1(1).
  
 4) LS AND A1.1 BOTH INDICATE DOOR 101 A SET OF DOUBLE
 DOORS PARTIALLY BLOCKING DOOR 100 EGRESS. 1008.1.1 THIS
 CODE SECTION REQUIRES A CLEAR 32" WHEN OPENED AT A 90
 DEGREE ANGLE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-02-10 Cont ID  
Sent By dpalmer Date 2009-02-10 Time 10:46 Rev Time 0.00
Received By dpalmer Date 2009-02-10 Time 10:46 Sent To PC
Notes
2009-02-10 10:46:12** PROVISO/REDLINED PLANS**
  
 1) NOTE: THE INSTALLATION OF RODS INSTALLED TO CONCRETE
 DECK ABOVE BY USE OF EPOXY AS NOTED ON PLANS NEEDS TO
 BE VERIFIED BY STRUCTURAL ENGINEER. THE METHOD, TYPE
 AND INSTALLATION PROCESS IS NOT SPECIFIED THEREFORE
 THIS NEEDS TO BE VERIFIED.
 THE STRUCTURAL INTEGRITY FOR THE INSTALLATION OF THIS
 TRANSFORMER IS IMPERATIVE FOR THE TENSION LOAD.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-01-15 Cont ID  
Sent By dpalmer Date 2009-01-15 Time 15:53 Rev Time 0.00
Received By dpalmer Date 2009-01-15 Time 15:53 Sent To  
Notes
2009-01-15 15:53:57** DENIED REVIEW OF REVISIONS**
  
  
 1) NOTE: THERE ARE A FEW ITEMS REDLINE DON PREVIOUS
 PLANS WHICH STILL NEED TO BE COORDINATED.
 THE PLANS STILL SHOW A TRANSFORMER IN FRONT OF THE
 PANELS. PLEASE VERIFY WHETHER OR NOT THE TRANSFORMER IS
 ABOVE PANELS GIVEN THE CLEARANCES PER 110.26
 PLEASE COORDINATE RISER AS BOTH PANELS ARE SHOWN AS
 125AMP MCB AND MLO ON EACH OF THE SCHEDULES YET THE
 RISER SHOWS BOTH OF THESE AS 225AMP MCB AND MLO.
 NEED TO VERIFY 240.21,310.16,240.4
 THE NEW RECEPTACLES NEED TO BE SPECIFIC. THESE ARE
 NOTED ONLY AS RECEPTACLES. ALSO THE NEW 2-POLE
 RECEPTACLES NEED TO NOTED FOR WHAT THEY WILL SERVE.
 408.4
  
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION,
 CLARITY AND COORDINATION.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
 *** NOTED: THERE IS NO NEW LIGHTING PERMITTED EXCEPT IN
 ELEVATOR LOBBY AREA.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-31 Cont ID  
Sent By dpalmer Date 2008-10-31 Time 10:23 Rev Time 0.00
Received By dpalmer Date 2008-10-31 Time 10:23 Sent To  
Notes
2008-10-31 10:25:36NO NEW LIGHTING EXCEPT THE ELEVATOR LOBBY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-09-12 Cont ID  
Sent By dpalmer Date 2008-09-12 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2008-09-12 Time 12:04 Sent To  
Notes
2008-09-12 12:04:50** DENIED REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE ELECTRICAL EQUIPMENT IN CLOSET
 AREA DOES NOT MEET 110.26,408.17, 240.24. THIS IS SHOWN
 AS EXISTING HOWEVER BASED ON THIS BEING A LIFE SAFETY
 AND FIRE HAZARD, EQUIPMENT AND SPACE LOCATION/LAYOUT
 NEEDS TO CHANGE.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.2, 13-415.2.ABC.2.1, 2.2.
  
  
 3) NOTE: LIGHTING CONTROLS FOR NEW BEING INSTALLED NEED
 TO MEET 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PANEL SCHEDULE FOR NEW CIRCUITS NEED TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
  
 5) NOTE: PLEASE PLACE NOTE ON PLANS FOR SERVER ROOM
 THAT WIRING METHODS IN NEC 645 ARE NOT PERMITTED.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-01-21 Cont ID  
Sent By mwennerg Date 2009-01-21 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2009-01-21 Time 15:48 Sent To  
Notes
2009-01-21 15:48:54REVISION #2 DATED 12/24/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-10-30 Cont ID  
Sent By mwennerg Date 2008-10-30 Time 14:30 Rev Time 0.00
Received By mwennerg Date 2008-10-30 Time 14:30 Sent To  
Notes
2008-10-30 14:30:50SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-10-01 Cont ID  
Sent By mwennerg Date 2008-10-01 Time 15:27 Rev Time 0.00
Received By mwennerg Date 2008-10-01 Time 13:59 Sent To  
Notes
2008-10-01 15:27:02***DENIED***
  
 1) MORE EXIT SIGNS AND EMERGENCY LIGHTING NEEDED IN
 OPEN WORK AREA 107.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION SHALL COMPLY
 WITH NFPA 241.
  
 3) DOOR SCHEDULE REFERENCES THE INCORRECT CODE EDITION.
 LOCKING ARRANGEMENTS SHALL COMPLY WITH 101, SEC.
 7.2.1.5.
  
 4) RATED DOORS SHALL BE PROVIDED WITH UL LISTED
 CLOSERS.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-25 Cont ID  
Sent By adarroug Date 2009-02-25 Time 16:41 Rev Time 0.00
Received By adarroug Date 2009-02-25 Time 16:41 Sent To B
Notes
2009-02-25 16:42:06TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-02-09 Cont ID  
Sent By adarroug Date 2009-02-09 Time 10:31 Rev Time 0.00
Received By adarroug Date 2009-02-09 Time 10:30 Sent To E
Notes
2009-02-09 10:31:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-01-06 Cont ID  
Sent By adarroug Date 2009-01-06 Time 16:25 Rev Time 0.00
Received By adarroug Date 2009-01-06 Time 16:24 Sent To  
Notes
2009-01-06 16:25:18TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 14:03 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 14:03 Sent To  
Notes
2008-10-17 10:24:54TO "COMM" BD#20
2008-10-16 14:04:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-10-01 Cont ID  
Sent By mwennerg Date 2008-10-01 Time 15:27 Rev Time 0.00
Received By mwennerg Date 2008-09-05 Time 11:32 Sent To  
Notes
2008-09-05 11:34:18TO "COMM" BD#23

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-02-01 Cont ID  
Sent By rregueir Date 2009-02-01 Time 15:12 Rev Time 0.00
Received By rregueir Date 2009-02-01 Time 15:12 Sent To PC
Notes
2009-02-01 15:12:42REVISED M2.1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-11-02 Cont ID  
Sent By rregueir Date 2008-11-02 Time 14:50 Rev Time 0.00
Received By rregueir Date 2008-11-02 Time 14:50 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-11 Cont ID  
Sent By rregueir Date 2008-09-11 Time 10:18 Rev Time 0.00
Received By rregueir Date 2008-09-10 Time 16:37 Sent To  
Notes
2008-09-11 10:18:46REVIEW #: 1ST
 ACTION: DENIED
  
 THE FOLLOWING COMMENTS HAVE BEEN GENERATED BASED ON THE
 REVIEW OF THE SUBMITTED PLANS AND SPECIFICATIONS UNDER
 THESE CODES:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. IN ACCORDANCE WITH THE REQUIREMENTS FOR A LEVEL 2
 ALTERATION, AS DECLARED ON PAGE LS.1, ALL RECONFIGURED
 SPACES INTENDED FOR OCCUPANCY IN ANY WORK AREA SHALL BE
 PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SEE FBCEB 609.1. PROVIDE SPACE BY SPACE
 VENTILATION CALCULATIONS WITH OCCUPANCY CLASSIFICATION,
 OCCUPANT LOAD, VENTILATION REQUIRED AND VENTILATION
 PROVIDED IN ACCORDANCE WITH FBCM TABLE 403.3 OR SECTION
 403.4. THE METHOD OF VENTILATION SHALL BE DECLARED ON
 THE PLANS.
  
 2. PROVIDE DESIGN CFM ON THE PLANS FOR ALL AIR
 DISTRIBUTION DEVICES TO FACILITATE A TEST AND BALANCE
 OF THE SYSTEMS IN ACCORDANCE WITH FBCB
 13-410.1.ABC.4.1. THIS IS ALSO NECESSARY TO CONFIRM
 VENTILATION RATES AS REQUIRED IN COMMENT #1 ABOVE AND
 TO SATISFY SPECIFICATIONS SECTION 15990 ON PAGE M0.1.
  
 3. FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS
 OF THE MANUFACTURER?S INSTALLATION INSTRUCTIONS AND
 LISTING IN ACCORDANCE WITH FBCM 607.2. MANUFACTURER?S
 INSTALLATION INSTRUCTIONS SHALL BE AVAILABLE ON THE JOB
 SITE AT THE TIME OF INSPECTION IN ACCORDANCE WITH THIS
 SECTION AND FBCM 304.1.
  
 4. A MINIMUM OF TWO SETS OF PLANS SHALL BE SUBMITTED
 FOR REVIEW IN ACCORDANCE WITH FBCB 106.1.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING TO ASSIST IN
 FACILITATING A TIMELY REVIEW. PROVIDE A DESCRIPTION OF
 HOW EACH COMMENT WAS ADDRESSED AS WELL AS WHERE THE
 REQUESTED INFORMATION CAN BE FOUND.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-01-30 Cont ID  
Sent By kstevens Date 2009-01-30 Time 14:14 Rev Time 0.00
Received By kstevens Date 2009-01-30 Time 14:14 Sent To  
Notes
2009-01-30 14:14:57REVISION OK -- SHT P2.1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-29 Cont ID  
Sent By kstevens Date 2008-10-29 Time 16:49 Rev Time 0.00
Received By kstevens Date 2008-10-29 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-09 Cont ID  
Sent By kstevens Date 2008-09-08 Time 12:45 Rev Time 0.00
Received By kstevens Date 2008-09-08 Time 12:44 Sent To  
Notes
2008-09-09 07:40:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. MINIMUM 2 SETS OF PLANS REQUIRED FOR REVIEW. SECTION
 106.1.
  
 2. SHT P2.1 PLUMBING FIXTURE SCHEDULE INDICATES THE
 SINK TO BE AN ELKAY MODEL DLH222210C. THIS DOES NOT
 COMPLY WITH SECTION 11-4.24.4 SINK DEPTH TO BE MAXIMUM
 6-1/2" DEEP.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  