Plan Review Details - Permit 08080640
Plan Review Stops For Permit 08080640
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-12 Cont ID  
Sent By mperson Date 2008-09-12 Time 15:33 Rev Time 0.00
Received By mperson Date 2008-09-12 Time 15:32 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-11 Cont ID  
Sent By mperson Date 2008-09-11 Time 10:57 Rev Time 0.00
Received By mperson Date 2008-09-10 Time 09:20 Sent To PC
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-03 Cont ID  
Sent By mperson Date 2008-09-03 Time 09:58 Rev Time 0.00
Received By mperson Date 2008-08-29 Time 15:41 Sent To PC
Notes
2008-08-29 15:42:51TO PLUMBING $5000.00 OR LESS BOX.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-09-12 Cont ID  
Sent By mperson Date 2008-09-12 Time 15:33 Rev Time 0.00
Received By mperson Date 2008-09-12 Time 15:33 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-09-11 Cont ID  
Sent By mperson Date 2008-09-11 Time 10:15 Rev Time 0.00
Received By mperson Date 2008-09-11 Time 10:15 Sent To I
Notes
2008-09-11 10:20:04PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING PLAN REVIEW COMMENTS AS WELL AS
 THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. THE KITCHEN SINK CAN NOT DRAIN INTO THE WET VENTED
 1/2 BATH. IT MUST DRAIN DOWNSTREAM OF THE 1/2 BATH. PER
 FBC-2004 PLUMBING SECTION 909.1 WET VENT PERMITTED.
  
 **NO COMMENT RESPONSE FROM THE DESIGNER AND THE COMMENT
 WAS NOT ADDRESSED. THE RESUBMITTED RISER DIAGRAM IS
 STILL INDICATING THE KITCHEN SINK DRAINING INTO THE 1/2
 BATH 2" WET VENT. THE RESUBMITTED PLANS DO NOT INDICATE
 HOW THE 1/2 BATH WATER CLOSET WASTE AND VENT IS PIPED.
 PER THE RESUBMITTED DRAWING INDICATING KITCHEN & 1/2
 BATH ON THE SANITARY RISER IT IS ASSUMED THAT THE 2" IS
 THE VENT FOR THE WATER CLOSET. SUBMIT A SANIATRY RISER
 OF THE 1/2 BATH THAT CLEARLY SHOWS HOW ALL FIXTURES
 (WATER CLOSET & LAVATORY) ARE PLUMBED CODE COMPLIANT.
 PER FBC-2004 PLUMBING SECTION 909.1 WET VENT PERMITTED,
 SECTION 701.1 SCOPE AND SECTION 901.1 SCOPE.
  
 3. "OK" COMMENT ADDRESED.
  
 4. "OK" COMMENT ADDRESSED.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 (W.P.B. AS AMENDED) SECTION *106.3.4.3.
  
 **NO COMMENT RESPONSE AND COMMENT WAS PARTIALLY
 ADDRESSED. TWO OF THE THREE RESUBMITTED SANITARY RISER
 DIAGRAMS HAVE PHOTO COPIED SIGNATURES OF THE PERSON
 TAKING RESPONSIBILITY OF THE DRAWINGS. ORIGINAL
 SIGNATURES ARE REQUIRED. PER (W.P.B. AS AMENDED)
 SECTION 106.3.4.3.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-03 Cont ID  
Sent By mperson Date 2008-09-03 Time 09:22 Rev Time 0.00
Received By mperson Date 2008-09-03 Time 09:22 Sent To I
Notes
2008-09-03 09:58:36PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE SCOPE OF WORK ON THE PERMIT APPLICATION STATES
 "REPLACE OLD CAST IRON PIPE WITH PVC", HOWEVER THE
 SUBMITTED PLANS ARE ONLY INDICATING THE ABOVE GROUND
 SANITARY WASTE AND VENT PIPING BEING REPLACED. IS THE
 UNDERGROUND SANITARY BEING REPLACED AS WELL? IF SO AN
 ISOMETRIC WITH SIZING IS REQUIRED. PLEASE KNOW THAT THE
 PERMIT APPLICATION STATES "DESCRIE PROJECT IN DETAIL
 (FAILURE TO DO SO MAY RESULT IN DELAYS)" CLEARLY
 INDICATE THE SCOPE OF WORK ON THE PERMIT APPLICATION AS
 TO WHAT PIPING IS BEING REPLACED. PER (W.P.B. AS
 AMENDED) SECTION 105 PERMITS.
  
 2. THE KITCHEN SINK CAN NOT DRAIN INTO THE WET VENTED
 1/2 BATH. IT MUST DRAIN DOWNSTREAM OF THE 1/2 BATH. PER
 FBC-2004 PLUMBING SECTION 909.1 WET VENT PERMITTED.
  
 3. WATER-SEAL TRAPS ARE REQUIRED FOR THE FOLLOWING
 FIXTURES. CLEARLY INDICATE THEM ON THE RESUBMITTAL. PER
 FBC-2004 PLUMBING SECTION 1002.1 FIXTURE TRAPS.
  
 A} FIRST FLOOR KITCHEN SINK AND LAVATORY.
  
 B} SECOND FLOOR LAVATORY.
  
 4. A CLEANOUT IS REQUIRED AT THE BASE OF THE SECOND
 FLOOR SOIL STACK. PER FBC-2004 PLUMBING SECTION 708.3.5
 BASE OF STACK.
  
 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 (W.P.B. AS AMENDED) SECTION *106.3.4.3.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]