Plan Review Details - Permit 08080594
Plan Review Stops For Permit 08080594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-10-27 Cont ID  
Sent By rmcdouga Date 2008-10-27 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2008-10-27 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-09-17 Cont ID  
Sent By rmcdouga Date 2008-09-17 Time 14:12 Rev Time 0.00
Received By rmcdouga Date 2008-09-17 Time 14:12 Sent To  
Notes
2008-09-17 14:12:522004 FBC W/2007 REVISIONS
 R-3 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) THE EXPOSURE CATEGORY FOR THE STRUCTURE IS
 INCORRECTLY SPECIFIED AS CATEGORY B ON SHEETS A1 AND
 A4. SEE R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C.
 OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING
 SURFACE UNDULATIONS OR OTHER IRREGULARITIES, HAVING
 HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING
 MORE THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE
 IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY
 BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE
 THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE
 OF MORE THAN 600 FEET (182.9 M). PLEASE CORRECT AND
 REVISE COMPONENT AND CLADDING PRESSURES ON A4.
  
 3) THE MINIMUM WALL INSULATION IS SPECIFIED AS R-4.1 ON
 THE WALL SECTION ON SHEET A4. THE ENERGY CALCULATION
 FORM LISTS A MINIMUM OF R-5. IF YOU USE THE
 PRESCRIPTIVE METHOD C OF THE ENERGY CODE, THE MINIMUM
 INSULATION FOR MASONRY WALLS IS R-5. PLEASE CORRECT.
 FBC 13-600.
  
 4) THE WINDOW BUCK DETAILS ON A4 SHOW THE DRYWALL
 SUPPORTING A PORTION OF THE WINDOW FRAMES. PLEASE
 REVISE. SEE R613.6.1.1 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE. UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR
 DOOR FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR 8" WIDE
 LINTELS. THE NOA THAT WAS SUBMITTED IS FOR 4", 6" AND
 12" LINTELS. FAC RULE 9B-72.
  
 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING. FAC RULE 9B-72.
  
 7) THE VALUATION OF THE WORK HAS BEEN INCREASED TO
 $40,509.00, ADDITIONAL PERMIT FEES OF $174.02 ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-10-14 Cont ID  
Sent By dpalmer Date 2008-10-14 Time 10:09 Rev Time 0.00
Received By dpalmer Date 2008-10-14 Time 10:09 Sent To M
Notes
2008-10-14 10:10:11SMOKE ALARMS SHALL COMPLY WITH FBC R313 AND NFPA-72
 11.5.1.1, 11.8.3 FOR ALL NEW AND EXISTING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 12:34 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 12:34 Sent To M
Notes
2008-09-10 12:35:22SMOKE ALARMS SHALL COMPLY WITH FBC R313 AND NFPA-72
 11.5.1.1, 11.8.3 FOR ALL NEW AND EXISTING.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-01-29 Cont ID  
Sent By adarroug Date 2009-01-29 Time 16:03 Rev Time 0.00
Received By adarroug Date 2009-01-29 Time 16:02 Sent To P
Notes
2009-01-29 16:03:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-01-14 Cont ID  
Sent By adarroug Date 2009-01-14 Time 08:45 Rev Time 0.00
Received By adarroug Date 2009-01-14 Time 08:45 Sent To M
Notes
2009-01-14 08:45:42TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-12-03 Cont ID  
Sent By adarroug Date 2008-12-03 Time 16:27 Rev Time 0.00
Received By adarroug Date 2008-12-03 Time 16:27 Sent To P
Notes
2008-12-03 16:27:57TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:15 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:15 Sent To Z
Notes
2008-10-03 16:15:57TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 10:31 Sent To E
Notes
2008-09-08 10:31:26TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-09-17 Cont ID  
Sent By mcruz Date 2008-09-07 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2008-08-27 Time 16:30 Sent To  
Notes
2008-08-27 16:31:43SFRTO "ZONING" SFR BOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-01-24 Cont ID  
Sent By rregueir Date 2009-01-24 Time 10:07 Rev Time 0.00
Received By rregueir Date 2009-01-24 Time 09:54 Sent To PC
Notes
2009-01-24 10:04:55REVISED AHU LOCATION

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-10-21 Cont ID  
Sent By tgordon Date 2008-10-21 Time 09:04 Rev Time 0.30
Received By tgordon Date 2008-10-21 Time 09:04 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By tgordon Date 2008-09-10 Time 14:31 Rev Time 0.30
Received By tgordon Date 2008-09-10 Time 14:31 Sent To P
Notes
2008-09-10 14:40:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE ARCHITECT RANDALL STROFF MUST SIGN AND SEAL
 MECHANICAL PLAN A3 AS HIS INFORMATION IS IN THE TITLE
 BLOCK, PER FAC 61G1-16.003.
  
 2) THE JOB ADDRESS NEEDS TO APPEAR IN THE TITLE BLOCK,
 PER WPB AMEND. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-02-23 Cont ID  
Sent By kstevens Date 2009-02-23 Time 15:49 Rev Time 0.00
Received By kstevens Date 2009-02-23 Time 15:49 Sent To  
Notes
2009-02-23 15:50:11REVISION OK -- SHT A2.

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-01-13 Cont ID  
Sent By kstevens Date 2009-01-13 Time 12:02 Rev Time 0.00
Received By kstevens Date 2009-01-13 Time 12:02 Sent To  
Notes
2009-01-13 12:08:51DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL REVISIONS TO A SIGNED, SEALED AND DATED BY THE
 ARCHITECT OF RECORD SHALL BE SIGNED, SEALED, AND DATED
 BY THE ARCHITECT OF RECORD. PLANS SHALL HAVE REQUIRED
 TITLE BLOCKS PER FAC 61G1-16.004 & FS 481.2055. SECTION
 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-10-23 Cont ID  
Sent By mperson Date 2008-10-23 Time 11:07 Rev Time 0.30
Received By mperson Date 2008-10-23 Time 11:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-09-10 Cont ID  
Sent By mperson Date 2008-09-10 Time 15:11 Rev Time 0.00
Received By mperson Date 2008-09-10 Time 15:11 Sent To B
Notes
2008-09-10 15:38:59PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A2 SANITARY ISOMETRIC RISER DIAGRAM: THE RISER
 DIAGRAM DOES NOT REFLECT THE NEW ADDITION'S FLOOR PLAN.
 THE MORNING BAR SINK IS MISSING FROM THE SANITARY
 ISOMETRIC RISER DIAGRAM. PLEASE INDICATE THE MISSING
 MORNING BAR SINK ON THE RESUBMITTAL. PER FBC-2004
 PLUMBING SECTION 701.1 SCOPE AND (W.P.B. AS AMENDED)
 SECTION 106.3.5.4 RESIDENTIAL (ONE AND TWO FAMILY) (9)
 PLUMBING.
  
 2. THE JOB ADDRESS (7193 WINDING BAY LN.) NEEDS TO
 APPEAR IN THE TITLE BLOCK ON ALL PLAN SHEETS. PER
 (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-10-10 Cont ID  
Sent By lfranco Date 2008-10-10 Time 16:50 Rev Time 0.00
Received By lfranco Date 2008-10-08 Time 12:30 Sent To E
Notes
2008-10-10 16:50:31 
 PLANNING AND ZONING: **** PASSED WITH PROVISO ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
  
 2. PURSUANT TO SECTION 94-72 THE PROPERTY IS WITHIN THE
 IBIS RPD, WITH THE UNDERLYING SINGLE FAMILY LOW DENSITY
 (SF7) RESIDENTIAL ZONING DISTRICT. THEREFORE, PURSUANT
 TO SECTION 94-611- DWELLING UNIT - ALL ROOMS IN THE
 DWELLING UNIT MUST BE ACCESSIBLE FROM THE INTERIOR OF
 THE UNIT. THE GUEST ROOM ADDITION DOES NOT COMPLY.
  
 RE-SUBMITTAL COMMENT: PER THE PLANNING AND ZONING
 DIRECTOR, CHARLES WU, THE COMMENT ABOVE, REFERENCING
 THE DEFINITION OF DWELLING UNIT WILL BE WAIVED FOR THIS
 PERMIT/ADDRESS (7193 WINDING BAY LANE) - LOT 1 ONLY.
 ANY AND ALL FUTURE PERMITS MUST COMPLY WITH SAID
 PROVISION AND AS PER AGREEMENT WITH TOM BRUNER OF KENCO
 COMMUNITIES (THE RIF GROUP).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2008-09-07 Cont ID  
Sent By mcruz Date 2008-09-07 Time 09:19 Rev Time 0.00
Received By mcruz Date 2008-09-07 Time 09:13 Sent To I
Notes
2008-09-07 09:19:37***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. AN INTERIOR CONNECTION TO THE HOUSE IS REQUIRED.
 PURSUANT TO SECTION 94-72 OF THE CITY OF WEST PALM
 BEACH ZONING AND DEVELOPMENT REGULATIONS, SINGLE FAMILY
 LOW DENSITY (SF7) RESIDENTIAL DISTRICTS ALLOWS ONLY
 SINGLE FAMILY DWELLING UNITS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  